LED lamps and fixtures: Difference between revisions

From Electrical Installation Guide
*>CleanUpAuto
(clean-up 2016 - imported revision step 20)
m (1 revision: no page modification, previous revision = imported ch.A pages cleaned-up)

Revision as of 15:38, 14 November 2016


See also "Lighting circuits" for more details


A lamp or luminaire with LED technology is powered by a driver:

  • can be integrated into the bulb (tube or lamp for retrofit) : in this case refer to the power indicated on the lamp
  • if separated : in that case it is necessary to take into account the power dissipated in the driver and the power indicated for one or several associated LED modules.

This technology has a very short start-up time. On the other hand, the inrush current at the powering is generally much higher than for fluorescent lamp with electronic ballast.

Note: The power in Watts indicated on the LED module with a separated driver doesn’t include the power dissipated in the driver.

Power demand (W) at 230 V Power factor Starting Luminous efficiency (lumens per watt) Average timelife Utilization
Inrush current Ip/In Inrush current time (microsec) Full Time to start
3 to 400 W > 0.9 Up to 250 < 250 microsec < 0.5 to 1 sec 100 to 140 20000 to 50000
  • All lighting applications in all domains (housing,commercial and industrial building, infrastructure)

Fig. A8b: Main characteristics of LED lamps & fixtures

Share