Functions of a substation with LV metering: Difference between revisions
(guide 2016) |
*>CleanUpAuto (clean-up 2016 - imported revision step 20) |
||
Line 5: | Line 5: | ||
Connection to the MV network can be made: | Connection to the MV network can be made: | ||
* By a single service cable or overhead line, | * By a single service cable or overhead line, | ||
* By dual parallel feeders via two mechanically interlocked load-break switches | * By dual parallel feeders via two mechanically interlocked load-break switches | ||
Line 13: | Line 12: | ||
Since the ban of PCB in most of the countries, the remaining available insulation technologies for the transformers are: | Since the ban of PCB in most of the countries, the remaining available insulation technologies for the transformers are: | ||
* Oil-immersed for transformer preferably located outside premises | * Oil-immersed for transformer preferably located outside premises | ||
* Dry-type, cast-resin preferred for transformers located inside premises such as buildings receiving the public. | * Dry-type, cast-resin preferred for transformers located inside premises such as buildings receiving the public. | ||
Line 37: | Line 35: | ||
A substation with LV metering may include one single emergency generator connected at low voltage level on the main LV distribution switchboard. | A substation with LV metering may include one single emergency generator connected at low voltage level on the main LV distribution switchboard. | ||
The generator may be sized either for the supply of the whole installation or for a part only. In this case a load shedding system must be associated to the generator. The loads requiring an emergency supply may also be grouped on a dedicated LV busbar (see | The generator may be sized either for the supply of the whole installation or for a part only. In this case a load shedding system must be associated to the generator. The loads requiring an emergency supply may also be grouped on a dedicated LV busbar (see {{FigRef|B32}}). | ||
An '''U'''ninterruptible '''P'''ower '''S'''upply (UPS) may be added when required at LV level to avoid the interruption of the supply during the starting of the emergency generator. | An '''U'''ninterruptible '''P'''ower '''S'''upply (UPS) may be added when required at LV level to avoid the interruption of the supply during the starting of the emergency generator. | ||
Line 53: | Line 51: | ||
The MV/LV transformer is connected to a main LV distribution switchboard equipped with a LV general circuit breaker ensuring: | The MV/LV transformer is connected to a main LV distribution switchboard equipped with a LV general circuit breaker ensuring: | ||
* The general protection of the LV installation | * The general protection of the LV installation | ||
* The general isolation of the LV circuits, according to the rules of protection of the persons working in an electrical installations | * The general isolation of the LV circuits, according to the rules of protection of the persons working in an electrical installations | ||
Line 63: | Line 60: | ||
The diagram '''(Fig. B33)''' shows: | The diagram '''(Fig. B33)''' shows: | ||
* The different methods to connect a MV/LV substation to the utility supply: | * The different methods to connect a MV/LV substation to the utility supply: | ||
**Single-line service | **Single-line service |
Revision as of 18:01, 15 November 2016
Connection to the MV network
Connection to the MV network can be made:
- By a single service cable or overhead line,
- By dual parallel feeders via two mechanically interlocked load-break switches
- Via a ring main unit including two load-break switches.
MV/LV Transformers
Since the ban of PCB in most of the countries, the remaining available insulation technologies for the transformers are:
- Oil-immersed for transformer preferably located outside premises
- Dry-type, cast-resin preferred for transformers located inside premises such as buildings receiving the public.
Local regulations define where the use of cast resin transformers is mandatory.
Metering
Most of the LV metering and billing principles take into account the MV/ LV transformer losses.
The characteristics and the location of the VT’s and CT’s dedicated to the metering must comply with the utility’s requirements.
The metering current transformers are generally installed in the LV terminal box of the power transformer, alternatively they can be installed in a dedicated compartment in the main LV switchboard.
The compartments housing the metering VT’s and CT’s are generally sealed by the utility.
The meters are mounted on a dedicated panel accessible by the utility at any time.
Local emergency generators
Emergency standby generators are intended to maintain the supply to the essential loads, in the event of failure of the utility power supply.
A substation with LV metering may include one single emergency generator connected at low voltage level on the main LV distribution switchboard.
The generator may be sized either for the supply of the whole installation or for a part only. In this case a load shedding system must be associated to the generator. The loads requiring an emergency supply may also be grouped on a dedicated LV busbar (see Fig. B32).
An Uninterruptible Power Supply (UPS) may be added when required at LV level to avoid the interruption of the supply during the starting of the emergency generator.
Fig. B32: Emergency generator at LV Level
Capacitors
Capacitors are intended to maintain the power factor of the installation at the contractual value specified by the utility. The capacitor banks are connected on the main LV switchboard and can be fixed or adjustable by means of steps controlled by a regulator.
See chapter Power Factor Correction
LV main switchboard
The MV/LV transformer is connected to a main LV distribution switchboard equipped with a LV general circuit breaker ensuring:
- The general protection of the LV installation
- The general isolation of the LV circuits, according to the rules of protection of the persons working in an electrical installations
- The protection of the MV/LV transformer against overload
To comply with the interlocking requirements defined in 3.3, the circuit breaker must be equipped with padlocking facilities for locking it in open position.
Simplified electrical network diagram
The diagram (Fig. B33) shows:
- The different methods to connect a MV/LV substation to the utility supply:
- Single-line service
- Single line service with provision for future connection to a ring or to dual parallel feeders
- Dual parallel feeders
- Loop or ring-main service
- The protection of the MV/LV transformer, either by a load break switch or by a circuit breaker
- The LV metering
- The main LV switchboard.
Fig. B33: Consumer substation with LV metering