Ground Fault Protection (GFP): Difference between revisions

From Electrical Installation Guide
m (1 revision)
*>CleanUpAuto
(clean-up 2016 - imported revision step 20)
Line 4: Line 4:
== Different type of ground fault protections  ==
== Different type of ground fault protections  ==


(see '''Fig. F27''')<br>
(see {{FigRef|F27}})<br>


Three types of GFP are possible dependind on the measuring device installed&nbsp;:  
Three types of GFP are possible dependind on the measuring device installed&nbsp;:  
Line 14: Line 14:
*“Source Ground Return” SGR
*“Source Ground Return” SGR


The «&nbsp;insulation fault current&nbsp;» is measured in the neutral – earth link of the LV&nbsp;transformer. The current transformer is outside the circuit-breaker.&nbsp;
The «&nbsp;insulation fault current&nbsp;» is measured in the neutral – earth link of the LV transformer. The current transformer is outside the circuit-breaker.


*“Zero Sequence” ZS
*“Zero Sequence” ZS


The «&nbsp;insulation fault&nbsp;» is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values.  
The «&nbsp;insulation fault&nbsp;» is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values.
 
----


[[File:FigF27.jpg|500px|none]]
[[File:FigF27.jpg|500px|none]]
'''''Fig. F27:'''''<i>&nbsp;Different types of ground fault protections</i>  
'''''Fig. F27:'''''<i>&nbsp;Different types of ground fault protections</i>
 
----


== Positioning GFP devices in the installation  ==
== Positioning GFP devices in the installation  ==


{| class="wikitable" style="width: 65%; height: 63px;"
{| class="wikitable"
|-
|-
! Type / installation level  
! Type / installation level  
Line 37: Line 33:
|-
|-
| Source Ground Return (SGR)  
| Source Ground Return (SGR)  
| {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\Box }}  
| {{EmptyBlueSquare}}  
| &nbsp;
|  
| Used
| Used
|-
|-
| Residual Sensing (RS) (SGR)  
| Residual Sensing (RS) (SGR)  
| {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\Box }}  
| {{EmptyBlueSquare}}  
| {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}&nbsp;
| {{BlueSquare}}
| Often used
| Often used
|-
|-
| Zero Sequence (SGR)  
| Zero Sequence (SGR)  
| {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\Box }}  
| {{EmptyBlueSquare}}  
| {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}  
| {{BlueSquare}}  
| Rarely used
| Rarely used
|}
|}

Revision as of 15:14, 24 November 2016


Different type of ground fault protections

(see Fig. F27)

Three types of GFP are possible dependind on the measuring device installed :

  • “Residual Sensing” RS

The “insulation fault” current is calculated using the vectorial sum of currents of current transformers secondaries. The current transformer on the neutral conductor is often outside the circuit-breaker.

  • “Source Ground Return” SGR

The « insulation fault current » is measured in the neutral – earth link of the LV transformer. The current transformer is outside the circuit-breaker.

  • “Zero Sequence” ZS

The « insulation fault » is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values.

FigF27.jpg

Fig. F27: Different types of ground fault protections

Positioning GFP devices in the installation

Type / installation level Main-distribution Sub-distribution Comments
Source Ground Return (SGR) [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\definecolor{myblue}{rgb}{0.26,0.71,0.9}\color{myblue}\square }[/math] Used
Residual Sensing (RS) (SGR) [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\definecolor{myblue}{rgb}{0.26,0.71,0.9}\color{myblue}\square }[/math] [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\definecolor{myblue}{rgb}{0.26,0.71,0.9}\color{myblue}\blacksquare }[/math] Often used
Zero Sequence (SGR) [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\definecolor{myblue}{rgb}{0.26,0.71,0.9}\color{myblue}\square }[/math] [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\definecolor{myblue}{rgb}{0.26,0.71,0.9}\color{myblue}\blacksquare }[/math] Rarely used

[math]\displaystyle{ \color{RoyalBlue}\Box }[/math] Possible
[math]\displaystyle{ \color{RoyalBlue}\blacksquare }[/math] Recommended or required

ru:Защита от замыканий на землю zh:接地故障防护 (GFP)

Share