Chapter G

Sizing and protection of conductors


Conductors in parallel: Difference between revisions

From Electrical Installation Guide
m (1 revision)
*>CleanUpAuto
(clean-up 2016 - imported revision step 20)

Revision as of 15:28, 25 November 2016


Conductors of the same cross-sectional-area, the same length, and of the same material, can be connected in parallel.

The maximum permissible current is the sum of the individual-core maximum currents, taking into account the mutual heating effects, method of installation, etc.

Protection against overload and short-circuits is identical to that for a single-cable circuit.

The following precautions should be taken to avoid the risk of short-circuits on the paralleled cables:

  • Additional protection against mechanical damage and against humidity, by the introduction of supplementary protection
  • The cable route should be chosen so as to avoid close proximity to combustible materials

ru:Параллельное соединение проводов zh:并联导线

Share