== Possible alternative locations in certain circumstances ==
== Possible alternative locations in certain circumstances ==


(see  {{FigRef|G7b}})
(see {{FigRef|G7b}})


The protective device may be placed part way along the circuit:  
The protective device may be placed part way along the circuit:  
Line 32: Line 32:
Either  
Either  
*The protective device P1 is calibrated to protect the cable S2 against overloads and short-circuits
*The protective device P1 is calibrated to protect the cable S2 against overloads and short-circuits
Or  
Or  
*Where the breaking of a circuit constitutes a risk, e.g.
*Where the breaking of a circuit constitutes a risk, e.g.
** Excitation circuits of rotating machines  
** Excitation circuits of rotating machines  
Line 42: Line 40:
No circuit interruption can be tolerated, and the protection of the cabling is of secondary importance.  
No circuit interruption can be tolerated, and the protection of the cabling is of secondary importance.  


[[File:FigG07a.jpg]]   '''[a]'''
{{Gallery|G7|Location of protective devices|170px|
 
|DB422286a.svg|a|
[[File:FigG07b.jpg]]   '''[b]'''
|DB422286b_EN.svg|b|
 
|DB422286c_EN.svg|c|}}
[[File:FigG07c.jpg]]   '''[c]'''
 
</big>
'''''Fig. G7:'''''<i>&nbsp;Location of protective devices</i>


[[ru:Расположение защитных устройств]]
[[ru:Расположение защитных устройств]]
[[zh:保护装置的安装位置]]
[[zh:保护装置的安装位置]]

Revision as of 23:12, 27 November 2016


A protective device is, in general, required at the origin of each circuit

General rule

(see Fig. G7a)

A protective device is necessary at the origin of each circuit where a reduction of permissible maximum current level occurs.

Possible alternative locations in certain circumstances

(see Fig. G7b)

The protective device may be placed part way along the circuit:

  • If AB is not in proximity to combustible material, and
  • If no socket-outlets or branch connections are taken from AB

Three cases may be useful in practice:

  • Consider case (1) in the diagram
    • AB ≤ 3 metres, and
    • AB has been installed to reduce to a practical minimum the risk of a short-circuit (wires in heavy steel conduit for example)
  • Consider case (2)
    • The upstream device P1 protects the length AB against short-circuits in accordance
  • Consider case (3)
    • The overload device (S) is located adjacent to the load. This arrangement is convenient for motor circuits. The device (S) constitutes the control (start/stop) and overload protection of the motor while (SC) is: either a circuit-breaker (designed for motor protection) or fuses type aM
    • The short-circuit protection (SC) located at the origin of the circuit conforms with the principles

Circuits with no protection

(see Fig. G7c)

Either

  • The protective device P1 is calibrated to protect the cable S2 against overloads and short-circuits

Or

  • Where the breaking of a circuit constitutes a risk, e.g.
    • Excitation circuits of rotating machines
    • circuits of large lifting electromagnets
    • the secondary circuits of current transformers

No circuit interruption can be tolerated, and the protection of the cabling is of secondary importance.