Conductors of the same cross-sectional-area, the same length, and of the same material, can be connected in parallel.<br>
Conductors of the same cross-sectional-area, the same length, and of the same material, can be connected in parallel.


The maximum permissible current is the sum of the individual-core maximum currents, taking into account the mutual heating effects, method of installation, etc.<br>
The maximum permissible current is the sum of the individual-core maximum currents, taking into account the mutual heating effects, method of installation, etc.


Protection against overload and short-circuits is identical to that for a single-cable circuit.<br>
Protection against overload and short-circuits is identical to that for a single-cable circuit.


The following precautions should be taken to avoid the risk of short-circuits on the paralleled cables:  
The following precautions should be taken to avoid the risk of short-circuits on the paralleled cables:  
*Additional protection against mechanical damage and against humidity, by the introduction of supplementary protection  
*Additional protection against mechanical damage and against humidity, by the introduction of supplementary protection  
*The cable route should be chosen so as to avoid close proximity to combustible materials<br>
*The cable route should be chosen so as to avoid close proximity to combustible materials


[[ru:Параллельное соединение проводов]]
[[ru:Параллельное соединение проводов]]
[[zh:并联导线]]
[[zh:并联导线]]

Revision as of 23:13, 27 November 2016


Conductors of the same cross-sectional-area, the same length, and of the same material, can be connected in parallel.

The maximum permissible current is the sum of the individual-core maximum currents, taking into account the mutual heating effects, method of installation, etc.

Protection against overload and short-circuits is identical to that for a single-cable circuit.

The following precautions should be taken to avoid the risk of short-circuits on the paralleled cables:

  • Additional protection against mechanical damage and against humidity, by the introduction of supplementary protection
  • The cable route should be chosen so as to avoid close proximity to combustible materials