Standards and description of circuit-breakers: Difference between revisions
m (1 revision: no page modification, previous revision = imported ch.H pages cleaned-up) |
CleanUp2016 (talk | contribs) (Cleanup_2016) |
||
Line 1: | Line 1: | ||
{{Menu_LV_switchgear_functions_and_selection}} | {{Menu_LV_switchgear_functions_and_selection}} | ||
__TOC__ | __TOC__ | ||
Line 5: | Line 6: | ||
{{Highlightbox| | {{Highlightbox| | ||
Industrial circuit-breakers must comply with IEC 60947-1 and 60947-2 or other equivalent standards. | Industrial circuit-breakers must comply with IEC 60947-1 and 60947-2 or other equivalent standards. | ||
Domestic-type circuit-breakers must comply with IEC standard 60898, or an equivalent national standard | |||
}} | Domestic-type circuit-breakers must comply with IEC standard 60898, or an equivalent national standard}} | ||
For industrial LV installations the relevant IEC standards are, or are due to be: | For industrial LV installations the relevant IEC standards are, or are due to be: | ||
*60947-1: general rules | *60947-1: general rules | ||
*60947-2: part 2: circuit-breakers | *60947-2: part 2: circuit-breakers | ||
Line 20: | Line 20: | ||
*60947-8: Part 8: Control units for built-in thermal protection (PTC) for rotating electrical machines. | *60947-8: Part 8: Control units for built-in thermal protection (PTC) for rotating electrical machines. | ||
For domestic and similar LV installations, the appropriate standard is IEC 60898, or an equivalent national standard. | For domestic and similar LV installations, the appropriate standard is IEC 60898, or an equivalent national standard. | ||
== Description == | == Description == | ||
Line 33: | Line 33: | ||
**Either: a thermal-magnetic device, in which a thermally-operated bi-metal strip detects an overload condition, while an electromagnetic striker pin operates at current levels reached in short-circuit conditions, or | **Either: a thermal-magnetic device, in which a thermally-operated bi-metal strip detects an overload condition, while an electromagnetic striker pin operates at current levels reached in short-circuit conditions, or | ||
**An electronic relay operated from current transformers, one of which is installed on each phase | **An electronic relay operated from current transformers, one of which is installed on each phase | ||
*A space allocated to the several types of terminal currently used for the main power circuit conductors | *A space allocated to the several types of terminal currently used for the main power circuit conductors | ||
{{FigImage|DB422405_EN|svg|H24|Main parts of a circuit-breaker}} | |||
Domestic circuit-breakers (see {{FigRef|H25}}) complying with IEC 60898 and similar national standards perform the basic functions of: | Domestic circuit-breakers (see {{FigRef|H25}}) complying with IEC 60898 and similar national standards perform the basic functions of: | ||
Line 43: | Line 41: | ||
*Protection against overcurrent | *Protection against overcurrent | ||
{{FigImage|PB116761|jpg|H25|Domestic-type circuit-breaker providing overcurrent protection and circuit isolation features}} | |||
Some models can be adapted to provide sensitive detection (30 mA) of earth-leakage current with CB tripping, by the addition of a modular block, while other models (RCBOs, complying with IEC 61009 and CBRs complying with IEC 60947-2 Annex B) have this residual current feature incorporated as shown in {{FigureRef|H26}}. | Some models can be adapted to provide sensitive detection (30 mA) of earth-leakage current with CB tripping, by the addition of a modular block, while other models (RCBOs, complying with IEC 61009 and CBRs complying with IEC 60947-2 Annex B) have this residual current feature incorporated as shown in {{FigureRef|H26}}. | ||
{{FigImage|PB116762|jpg|H26|Domestic-type circuit-breaker as above (Fig. H25) with incorparated protection against electric shocks}} | |||
Apart from the above-mentioned functions further features can be associated with the basic circuit-breaker by means of additional modules, as shown in {{FigureRef|H27}}; notably remote control and indication (on-off-fault). | Apart from the above-mentioned functions further features can be associated with the basic circuit-breaker by means of additional modules, as shown in {{FigureRef|H27}}; notably remote control and indication (on-off-fault). | ||
{{FigImage|DB422406_EN|svg|H27|“Acti 9” system of LV modular switchgear components}} | |||
Moulded-case circuit-breakers complying with IEC 60947-2 are available from 100 to 630 A and provide a similar range of auxiliary functions to those described above (see {{FigureRef|H28}}). | Moulded-case circuit-breakers complying with IEC 60947-2 are available from 100 to 630 A and provide a similar range of auxiliary functions to those described above (see {{FigureRef|H28}}). | ||
{{FigImage|PB105112-z|jpg|H28|Example of a Compact NSX industrial type of circuit-breaker capable of numerous auxiliary functions}} | |||
Air circuit-breakers of large current ratings, complying with IEC 60947-2, are generally used in the main switch board and provide protector for currents from 630 A to 6300 A, typically.(see | Air circuit-breakers of large current ratings, complying with IEC 60947-2, are generally used in the main switch board and provide protector for currents from 630 A to 6300 A, typically.(see {{FigureRef|H29}}). | ||
In addition to the protection functions, the Micrologic unit provides optimized functions such as measurement (including power quality functions), diagnosis, communication, control and monitoring. | In addition to the protection functions, the Micrologic unit provides optimized functions such as measurement (including power quality functions), diagnosis, communication, control and monitoring. |
Revision as of 00:28, 2 December 2016
Standards
Industrial circuit-breakers must comply with IEC 60947-1 and 60947-2 or other equivalent standards.
Domestic-type circuit-breakers must comply with IEC standard 60898, or an equivalent national standard
For industrial LV installations the relevant IEC standards are, or are due to be:
- 60947-1: general rules
- 60947-2: part 2: circuit-breakers
- 60947-3: part 3: switches, disconnectors, switch-disconnectors and fuse combination units
- 60947-4: part 4: contactors and motor starters
- 60947-5: part 5: control-circuit devices and switching elements
- 60947-6: part 6: multiple function switching devices
- 60947-7: part 7: ancillary equipment
- 60947-8: Part 8: Control units for built-in thermal protection (PTC) for rotating electrical machines.
For domestic and similar LV installations, the appropriate standard is IEC 60898, or an equivalent national standard.
Description
Figure H24 shows schematically the main parts of a LV circuit-breaker and its four essential functions:
- The circuit-breaking components, comprising the fixed and moving contacts and the arc-dividing chamber
- The latching mechanism which becomes unlatched by the tripping device on detection of abnormal current conditions
This mechanism is also linked to the operation handle of the breaker.
- A trip-mechanism actuating device:
- Either: a thermal-magnetic device, in which a thermally-operated bi-metal strip detects an overload condition, while an electromagnetic striker pin operates at current levels reached in short-circuit conditions, or
- An electronic relay operated from current transformers, one of which is installed on each phase
- A space allocated to the several types of terminal currently used for the main power circuit conductors
Domestic circuit-breakers (see Fig. H25) complying with IEC 60898 and similar national standards perform the basic functions of:
- Isolation
- Protection against overcurrent
Some models can be adapted to provide sensitive detection (30 mA) of earth-leakage current with CB tripping, by the addition of a modular block, while other models (RCBOs, complying with IEC 61009 and CBRs complying with IEC 60947-2 Annex B) have this residual current feature incorporated as shown in Figure H26.
Apart from the above-mentioned functions further features can be associated with the basic circuit-breaker by means of additional modules, as shown in Figure H27; notably remote control and indication (on-off-fault).
Moulded-case circuit-breakers complying with IEC 60947-2 are available from 100 to 630 A and provide a similar range of auxiliary functions to those described above (see Figure H28).
Air circuit-breakers of large current ratings, complying with IEC 60947-2, are generally used in the main switch board and provide protector for currents from 630 A to 6300 A, typically.(see Figure H29).
In addition to the protection functions, the Micrologic unit provides optimized functions such as measurement (including power quality functions), diagnosis, communication, control and monitoring.