SPD and protection device coordination table: Difference between revisions
*>CleanUpAuto (clean-up 2016 - imported revision step 20) |
m (1 revision: no page modification, previous revision = imported ch.J pages cleaned-up) |
(No difference)
|
Revision as of 09:55, 2 December 2016
The table in Figure J37 below shows the coordination of disconnecting circuit breakers (external SCPD) for Type 1 and 2 SPDs of the Schneider Electric brand for all levels of short-circuit currents.
Coordination between SPD and its disconnecting circuit breakers, indicated and guaranteed by Schneider Electric, ensures reliable protection (lightning wave withstand, reinforced protection of impedant short-circuit currents, etc.)
All circuit breakers are C curve
(*) Compact NSX in this case is for lightning impulse current withstand.
Fig. J37: Coordination table between SPDs and their disconnecting circuit breakers of the Schneider Electric brand
Coordination with upstream protection devices
Coordination with overcurrent protection devices
In an electrical installation, the external SCPD is an apparatus identical to the protection apparatus: this makes it possible to apply discrimination and cascading techniques for technical and economic optimization of the protection plan.
Coordination with residual current devices
If the SPD is installed downstream of an earth leakage protection device, the latter should be of the "si" or selective type with an immunity to pulse currents of at least 3 kA (8/20 μs current wave).