At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see '''Fig. N31''').  
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N31}}).
 
----


[[File:FigN31.jpg|none]]
[[File:FigN31.jpg|none]]
'''''Fig N31:''' Transformer-energizing inrush current''
'''''Fig N31:''' Transformer-energizing inrush current''
----


The magnitude of the current peak depends on:  
The magnitude of the current peak depends on:  

Revision as of 08:53, 8 December 2016


At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N31).

FigN31.jpg

Fig N31: Transformer-energizing inrush current

The magnitude of the current peak depends on:

  • The value of voltage at the instant of energization
  • The magnitude and polarity of the residual flux existing in the core of the transformer
  • Characteristics of the load connected to the transformer

The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.