Common-mode impedance coupling: Difference between revisions

From Electrical Installation Guide
m (1 revision)
*>CleanUpAuto
(clean-up 2016 - imported revision step 20)
Line 4: Line 4:
== Definition  ==
== Definition  ==


Two or more devices are interconnected by the power supply and communication cables (see '''Fig. R32'''). When external currents (lightning, fault currents, disturbances) flow via these common-mode impedances, an undesirable voltage appears between points A and B '''which are supposed to be equipotential'''. This&nbsp;stray voltage can disturb low-level or fast electronic circuits.<br>All cables, including the protective conductors, have an impedance, particularly at high frequencies.  
Two or more devices are interconnected by the power supply and communication cables (see {{FigRef|R32}}). When external currents (lightning, fault currents, disturbances) flow via these common-mode impedances, an undesirable voltage appears between points A and B '''which are supposed to be equipotential'''. This stray voltage can disturb low-level or fast electronic circuits.<br>All cables, including the protective conductors, have an impedance, particularly at high frequencies.
 
----


[[File:Fig R22.jpg|none]]
[[File:Fig R22.jpg|none]]
The exposed conductive parts (ECP) of devices 1 and 2 are connected to a common earthing terminal via connections with impedances Z1 and Z2.<br>The stray overvoltage flows to the earth via Z1. The potential of device 1 increases to Z1 I1. The difference in potential with device 2 (initial potential = 0) results in the appearance of current I2.<br><math>Z1\, I1=\left ( Zsign\, + Z2 \right )I2\Rightarrow \frac{I2}{I1}=\frac{Z1}{\left ( Zsign\, + Z2 \right )}</math> <br>
The exposed conductive parts (ECP) of devices 1 and 2 are connected to a common earthing terminal via connections with impedances Z1 and Z2.<br>The stray overvoltage flows to the earth via Z1. The potential of device 1 increases to Z1 I1. The difference in potential with device 2 (initial potential = 0) results in the appearance of current I2.<br><math>Z1\, I1=\left ( Zsign\, + Z2 \right )I2\Rightarrow \frac{I2}{I1}=\frac{Z1}{\left ( Zsign\, + Z2 \right )}</math> <br>


Current I2, present on the signal line, disturbs device 2. <br><br>'''''Fig. R32:''' Definition of common-mode impedance coupling''  
Current I2, present on the signal line, disturbs device 2. <br><br>'''''Fig. R32:''' Definition of common-mode impedance coupling''
 
----


== Examples  ==
== Examples  ==


(see '''Fig. R33''')  
(see {{FigRef|R33}})  


*Devices linked by a common reference conductor (e.g. PEN, PE) affected by fast or intense (di/dt) current variations (fault current, lightning strike, short-circuit, load changes, chopping circuits, harmonic currents, power factor correction capacitor banks, etc.)
*Devices linked by a common reference conductor (e.g. PEN, PE) affected by fast or intense (di/dt) current variations (fault current, lightning strike, short-circuit, load changes, chopping circuits, harmonic currents, power factor correction capacitor banks, etc.)
*A common return path for a number of electrical sources
*A common return path for a number of electrical sources


----
[[File:Fig_R23.jpg|none]]
[[File:Fig_R23.jpg|none]]
'''''Fig. R33:''' Example of common-mode impedance coupling''
'''''Fig. R33:''' Example of common-mode impedance coupling''
----


== Counter-measures  ==
== Counter-measures  ==


(see '''Fig. R34''')  
(see {{FigRef|R34}})  


If they cannot be eliminated, common-mode impedances must at least be as low as possible. To reduce the effects of common-mode impedances, it is necessary to:  
If they cannot be eliminated, common-mode impedances must at least be as low as possible. To reduce the effects of common-mode impedances, it is necessary to:  
Line 39: Line 32:


*Reduce the level of the disturbing currents by adding common-mode filtering and differential-mode inductors
*Reduce the level of the disturbing currents by adding common-mode filtering and differential-mode inductors
----


[[File:Fig R24.jpg|none]]
[[File:Fig R24.jpg|none]]
If the impedance of the parallel earthing conductor PEC (Z&nbsp;sup) is very low compared to Z sign, most of the disturbing current flows via the PEC, i.e. not via the signal line as in the previous case.<br>The difference in potential between devices 1 and 2 becomes very low and the disturbance acceptable. <br><br>
If the impedance of the parallel earthing conductor PEC (Z&nbsp;sup) is very low compared to Z sign, most of the disturbing current flows via the PEC, i.e. not via the signal line as in the previous case.<br>The difference in potential between devices 1 and 2 becomes very low and the disturbance acceptable. <br><br>


'''''Fig. R34:''' Counter-measures of common-mode impedance coupling''  
'''''Fig. R34:''' Counter-measures of common-mode impedance coupling''
 
----
 
 


[[ru:Гальваническая (кондуктивная) связь]]
[[ru:Гальваническая (кондуктивная) связь]]
[[zh:共模阻抗耦合]]
[[zh:共模阻抗耦合]]

Revision as of 17:50, 13 December 2016

Definition

Two or more devices are interconnected by the power supply and communication cables (see Fig. R32). When external currents (lightning, fault currents, disturbances) flow via these common-mode impedances, an undesirable voltage appears between points A and B which are supposed to be equipotential. This stray voltage can disturb low-level or fast electronic circuits.
All cables, including the protective conductors, have an impedance, particularly at high frequencies.

Fig R22.jpg

The exposed conductive parts (ECP) of devices 1 and 2 are connected to a common earthing terminal via connections with impedances Z1 and Z2.
The stray overvoltage flows to the earth via Z1. The potential of device 1 increases to Z1 I1. The difference in potential with device 2 (initial potential = 0) results in the appearance of current I2.
[math]\displaystyle{ Z1\, I1=\left ( Zsign\, + Z2 \right )I2\Rightarrow \frac{I2}{I1}=\frac{Z1}{\left ( Zsign\, + Z2 \right )} }[/math]

Current I2, present on the signal line, disturbs device 2.

Fig. R32: Definition of common-mode impedance coupling

Examples

(see Fig. R33)

  • Devices linked by a common reference conductor (e.g. PEN, PE) affected by fast or intense (di/dt) current variations (fault current, lightning strike, short-circuit, load changes, chopping circuits, harmonic currents, power factor correction capacitor banks, etc.)
  • A common return path for a number of electrical sources
Fig R23.jpg

Fig. R33: Example of common-mode impedance coupling

Counter-measures

(see Fig. R34)

If they cannot be eliminated, common-mode impedances must at least be as low as possible. To reduce the effects of common-mode impedances, it is necessary to:

  • Reduce impedances:

  - Mesh the common references,
  - Use short cables or flat braids which, for equal sizes, have a lower impedance than round cables,
  - Install functional equipotential bonding between devices.

  • Reduce the level of the disturbing currents by adding common-mode filtering and differential-mode inductors
Fig R24.jpg

If the impedance of the parallel earthing conductor PEC (Z sup) is very low compared to Z sign, most of the disturbing current flows via the PEC, i.e. not via the signal line as in the previous case.
The difference in potential between devices 1 and 2 becomes very low and the disturbance acceptable.

Fig. R34: Counter-measures of common-mode impedance coupling