Motor control systems: Difference between revisions
From Electrical Installation Guide
CleanUp2016 (talk | contribs) (Cleanup_2016_while rechecking) |
(update_2018) |
||
Line 55: | Line 55: | ||
| Higher cost | | Higher cost | ||
|- | |- | ||
{{TableEnd|Tab1387| | {{TableEnd|Tab1387|N74|Main characteristics of different motor control solutions}} |
Revision as of 03:02, 16 June 2018
Different kinds of motor control solution are compared in the following tables.
Type | Is/In | Ts/Tn | Speed control | Torque control | Pros | Cons |
---|---|---|---|---|---|---|
Direct on line | 5-10 | 5-10 | No | No | Reduced cost, high starting torque | High in-rush current |
Star – Delta | 2-3 | 1-2 | No | No | Reduced in-rush current | Reduced starting torque |
Auto-transformer | 2-3 | 1-2 | No | No | Reduced in-rush current | High weight |
Soft starter | 3-5 | 1.5-2.5 | No | Yes | Reduced in-rush current, controlled start and stop | Reduced starting torque |
Variable speed drive | 1.5 | 1.5-2 | Yes | Yes | Controlled speed, Energy saving at reduced speed | Higher cost |
Fig. N74 – Main characteristics of different motor control solutions