Additional protection: High sensitivity RCDs: Difference between revisions

From Electrical Installation Guide
Home > Protection against electric shocks and electrical fires > Additional protection: High sensitivity RCDs
m (1 revision imported: Migrated pages - removed CN links)
m (updated link - destination page has been renamed)
Line 28: Line 28:
It is also recommended to limit the number of socket-outlets protected by a high sensitivity RCD (e.g. 10 socket-outlets for one RCD).
It is also recommended to limit the number of socket-outlets protected by a high sensitivity RCD (e.g. 10 socket-outlets for one RCD).


The page [[recommendations applicable to special installations and locations]] itemizes various common locations in which RCDs of high sensitivity are mandatory (in some countries), but in any case, are highly recommended as an effective protection against both contact with live parts and contact with conductive parts in fault conditions.
The page [[Requirements applicable to special installations and locations]] itemizes various common locations in which RCDs of high sensitivity are mandatory (in some countries), but in any case, are highly recommended as an effective protection against both contact with live parts and contact with conductive parts in fault conditions.


High sensitivity RCDs are suitable for all types of earthing systems. See {{FigRef|F10}} '''(a)''' for TT or TN systems, and '''(b)''' for IT system.
High sensitivity RCDs are suitable for all types of earthing systems. See {{FigRef|F10}} '''(a)''' for TT or TN systems, and '''(b)''' for IT system.

Revision as of 18:20, 9 August 2021

An additional measure of protection against the hazards of contact with live parts is provided by the use of residual current operating device, which operates at 30 mA or less, and are referred to as High Sensitivity RCDs

All the preceding protective measures are preventive, but experience has shown that for various reasons they cannot be regarded as being infallible. Among these reasons may be cited:

  • Lack of proper maintenance
  • Imprudence, carelessness
  • Normal (or abnormal) wear and tear of insulation; for instance flexure and abrasion of connecting leads
  • Accidental contact
  • Immersion in water, etc. A situation in which insulation is no longer effective.

In order to protect users in such circumstances, highly sensitive fast tripping devices, based on the detection of residual currents to earth (which may or may not be through a human being or animal) are used to disconnect the power supply automatically, and with sufficient rapidity to prevent injury to, or death by electrocution, of a normally healthy human being (see Fig. F8).

Fig. F8 – Additional protection by RCD

These devices operate on the principle of residual current measurement, in which any difference between the current entering a circuit and that leaving it (on a system supplied from an earthed source) is flowing to earth, either through faulty insulation or through contact of an earthed part, such as a person, with a live conductor.

Standardized residual current devices, referred to as RCDs, sufficiently sensitive for protection against contact with live parts are rated at 30 mA of residual current. The response time as defined in IEC 61008 and 61009 is fast enough to provide protection. See Fig. F9.

Fig. F9 – Tripping curve of High Sensitivity 30mA RCD (in blue) compared to body sensitivity curves

According to IEC 60364-4-41, additional protection by means of high sensitivity RCDs (IΔn ≤ 30 mA) must be provided for:

  • circuits supplying general use socket-outlets with a rated current ≤ 32 A liable to be used by ordinary persons,
  • for circuits supplying mobile equipment with a rated current ≤ 32 A for use outdoors,
  • AC final circuits supplying luminaires, in dwelling.

It is also recommended to limit the number of socket-outlets protected by a high sensitivity RCD (e.g. 10 socket-outlets for one RCD).

The page Requirements applicable to special installations and locations itemizes various common locations in which RCDs of high sensitivity are mandatory (in some countries), but in any case, are highly recommended as an effective protection against both contact with live parts and contact with conductive parts in fault conditions.

High sensitivity RCDs are suitable for all types of earthing systems. See Fig. F10 (a) for TT or TN systems, and (b) for IT system.