Short-circuit current: Difference between revisions
m (1 revision imported: Migrated pages - removed CN links) |
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "") |
||
Line 12: | Line 12: | ||
{{Section-TOC}} | {{Section-TOC}} | ||
Latest revision as of 09:49, 22 June 2022
Knowing the levels of 3-phase symmetrical short-circuit currents (Isc) at different points in an installation is an essential feature of its design
A knowledge of 3-phase symmetrical short-circuit current values (Isc) at strategic points of an installation is necessary in order to determine switchgear (breaking capacity), cables (thermal withstand rating), protective devices (selective trip settings) and so on...
In the following notes a 3-phase short-circuit of zero impedance (the so-called bolted short-circuit) fed through a typical MV/LV distribution transformer will be examined. Except in very unusual circumstances, this type of fault is the most severe, and is certainly the simplest to calculate.
Short-circuit currents occurring in a network supplied from a generator and also in DC systems are dealt with in Chapter Characteristics of particular sources and loads.
The simplified calculations and practical rules which follow give conservative results of sufficient accuracy, in the large majority of cases, for installation design purposes.
Pages in this section
- Short-circuit current at the secondary terminals of a MV/LV distribution transformer
- 3-phase short-circuit current (Isc) at any point within a LV installation
- Isc at the receiving end of a feeder as a function of the Isc at its sending end
- Short-circuit current supplied by a generator or an inverter