Chapter G

Sizing and protection of conductors


Protection of the neutral conductor

From Electrical Installation Guide
Revision as of 15:28, 25 November 2016 by LMischler (talk | contribs) (1 revision: no page modification, previous revision = imported ch.G pages cleaned-up)

Home > Sizing and protection of conductors > The neutral conductor > Protection of the neutral conductor


(see Fig. G64)

Protection against overload

If the neutral conductor is correctly sized (including harmonics), no specific protection of the neutral conductor is required because it is protected by the phase protection.
However, in practice, if the c.s.a. of the neutral conductor is lower than the phase c.s.a, a neutral overload protection must be installed.

PictoChap7a.jpg
Protection against short-circuit

If the c.s.a. of the neutral conductor is lower than the c.s.a. of the phase conductor, the neutral conductor must be protected against short-circuit.
If the c.s.a. of the neutral conductor is equal or greater than the c.s.a. of the phase conductor, no specific protection of the neutral conductor is required because it is protected by the phase protection.

PictoChap7b.jpg