Motor control systems

From Electrical Installation Guide
Revision as of 08:53, 8 December 2016 by LMischler (talk | contribs) (1 revision: no page modification, previous revision = imported ch.N pages cleaned-up)

Home > Characteristics of particular sources and loads > Asynchronous motors > Motor control systems


Different kinds of motor control solution are compared in the following tables.

Is / In Ts / Tn Speed control Torque control
Direct on line 5-10 5-10 No No
Star – Delta 2-3 1-2 No No
Auto-transformer 2-3 1-2 No No
Soft starter 3-5 1.5-2.5 No Yes
Variable speed drive 1.5 1.5-2 Yes Yes
pros cons
Direct on line

Reduced cost, high starting torque

High in-rush current

Star – Delta Reduced in-rush current Reduced starting torque
Auto-transformer Reduced in-rush current High weight
Soft starter

Reduced in-rush current, controlled start and stop

Reduced starting torque
Variable speed drive

Controlled speed, Energy saving at reduced speed

Higher cost

Fig. N63: Comparison of different motor control solutions

Share