Ground Fault Protection (GFP)
Different type of ground fault protections
(see Fig. F27)
Three types of GFP are possible dependind on the measuring device installed :
Residual Sensing RS
The “insulation fault” current is calculated using the vectorial sum of currents of current transformers secondaries. The current transformer on the neutral conductor is often outside the circuit-breaker.
Source Ground Return SGR
The insulation fault current is measured in the neutral – earth link of the LV transformer. The current transformer is outside the circuit-breaker.
Zero Sequence ZS
The insulation fault is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values.
Positioning GFP devices in the installation
Type / installation level | Main-distribution | Sub-distribution | Comments |
---|---|---|---|
Source Ground Return (SGR) | Possible | Used | |
Residual Sensing (RS) (SGR) | Possible | Recommended or required | Often used |
Zero Sequence (SGR) | Possible | Recommended or required | Rarely used |