The neutral conductor

From Electrical Installation Guide
Revision as of 07:22, 2 February 2010 by Wikiadmin (talk | contribs)

The c.s.a. and the protection of the neutral conductor, apart from its current-carrying requirement, depend on several factors, namely:

  • The type of earthing system, TT, TN, etc.
  • The harmonic currents
  • The method of protection against indirect contact hazards according to the methods described below

   The color of the neutral conductor is statutorily blue. PEN conductor, when insulated, shall be marked by one of the following 
   methods:

  • Green-and-yellow throughout its length with, in addition, light blue markings at the terminations, or
  • Light blue throughout its length with, in addition, green-and-yellow markings at the terminations

 

Sizing the neutral conductor

Influence of the type of earthing system

TT and TN-S schemes 

  • Single-phase circuits or those of c.s.a. ≤ 16 mm2 (copper) 25 mm2 (aluminium): the c.s.a. of the neutral conductor must be equal to that of the phases
  • Three-phase circuits of c.s.a. > 16 mm2 copper or 25 mm2 aluminium: the c.s.a. of the neutral may be chosen to be:

  -  Equal to that of the phase conductors, or
  -  Smaller, on condition that:
  -  The current likely to flow through the neutral in normal conditions is less than the permitted value Iz. The influence of triplen(1)   
     harmonics must be given particular consideration or
  -  The neutral conductor is protected against short-circuit, in accordance with the following Sub-clause G-7.2
  -  The size of the neutral conductor is at least equal to 16 mm2 in copper or 25 mm2 in aluminium

(1) Harmonics of order 3 and multiple of 3

TN-C scheme
The same conditions apply in theory as those mentioned above, but in practice, the neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor (see Figure G58 “c.s.a. of PEN conductor” column).
IT scheme
In general, it is not recommended to distribute the neutral conductor, i.e. a 3-phase 3-wire scheme is preferred. When a 3-phase 4-wire installation is necessary, however, the conditions described above for TT and TN-S schemes are applicable.

Influence of harmonic currents

Effects of triplen harmonics

Harmonics are generated by the non-linear loads of the installation (computers, fluorescent lighting, rectifiers, power electronic choppers) and can produce high currents in the Neutral. In particular triplen harmonics of the three Phases have a tendency to cumulate in the Neutral as:

  • Fundamental currents are out-of-phase by 2π/3 so that their sum is zero
  • On the other hand, triplen harmonics of the three Phases are always positioned in the same manner with respect to their own fundamental, and are in phase with each other (see Fig. G63a).


FigG63a.jpg














Fig. G63a:Triplen harmonics are in phase and cumulate in the Neutral


Figure G63b shows the load factor of the neutral conductor as a function of the percentage of 3rd harmonic.
In practice, this maximum load factor cannot exceed [math]\displaystyle{ \sqrt 3 }[/math].



FigG63b.jpg




















Fig. G63b: Load factor of the neutral conductor vs the percentage of 3rd harmonic


Reduction factors for harmonic currents in four-core and five-core cables with four cores carrying current
The basic calculation of a cable concerns only cables with three loaded conductors i.e there is no current in the neutral conductor. Because of the third harmonic current, there is a current in the neutral. As a result, this neutral current creates an hot environment for the 3 phase conductors and for this reason, a reduction factor for phase conductors is necessary (see Fig. G63).
Reduction factors, applied to the current-carrying capacity of a cable with three loaded conductors, give the current-carrying capacity of a cable with four loaded conductors, where the current in the fourth conductor is due to harmonics. The reduction factors also take the heating effect of the harmonic current in the phase conductors into account.

  • Where the neutral current is expected to be higher than the phase current, then the cable size should be selected on the basis of the neutral current
  • Where the cable size selection is based on a neutral current which is not significantly higher than the phase current, it is necessary to reduce the tabulated current carrying capacity for three loaded conductors
  • If the neutral current is more than 135% of the phase current and the cable size is selected on the basis of the neutral current then the three phase conductors will not be fully loaded. The reduction in heat generated by the phase conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any reduction factor to the current carrying capacity for three loaded conductors.
  • In order to protect cables, the fuse or circuit-breaker has to be sized taking into account the greatest of the values of the line currents (phase or neutral). However, there are special devices (for example the Compact NSX circuit breaker equipped with the OSN tripping unit), that allow the use of a c.s.a. of the phase conductors smaller than the c.s.a. of the neutral conductor. A big economic gain can thus be made.

PB103191 C1 3P TM100D.jpg










Compact NSX100 circuit breaker



Third harmonic content of phase current (%) Reduction factor
Size selection is based on  phase current Size selection is based on neutral current
0 -15                                                 1.0 -
15 - 33 0.86 -
33 - 45 - 0.86
> 45 -           1.0                                                             

Fig. G63: Reduction factors for harmonic currents in four-core and five-core cables (according to IEC 60364-5-52)


Examples

Consider a three-phase circuit with a design load of 37 A to be installed using four-core PVC insulated cable clipped to a wall, installation method C. From Figure G24, a 6 mm2 cable with copper conductors has a current-carrying capacity of 40 A and hence is suitable if harmonics are not present in the circuit.

  • If 20 % third harmonic is present, then a reduction factor of 0,86 is applied and the design load becomes: 37/0.86 = 43 A. For this load a 10 mm2 cable is necessary.  In this case, the use of a special protective device (Compact NSX equipped with the OSN trip unit for instance) would allow the use of  a 6 mm2 cable for the phases and of 10 mm2 for the neutral.
  • If 40 % third harmonic is present, the cable size selection is based on the neutral current which is: 37 x 0,4 x 3 = 44,4 A and a reduction factor of 0,86 is applied, leading to a design load of: 44.4/0.86 = 51.6 A.  For this load a 10 mm2 cable is suitable.
  • If 50 % third harmonic is present, the cable size is again selected on the basis of the neutral current, which is: 37 x 0,5 x 3 = 55,5 A.In this case the rating factor is 1 and a 16 mm2 cable is required.  In this case, the use of a special protective device (Compact NSX equipped with the OSN trip for instance) would allow the use of a   6 mm2 cable for the phases and of 10mm2 for the neutral.


Protection of the neutral conductor

(see Fig. G64)

Protection against overload

If the neutral conductor is correctly sized (including harmonics), no specific protection of the neutral conductor is required because it is protected by the phase protection.
However, in practice, if the c.s.a. of the neutral conductor is lower than the phase c.s.a, a neutral overload protection must be installed.

PictoChap7a.jpg

Protection against short-circuit

If the c.s.a. of the neutral conductor is lower than the c.s.a. of the phase conductor, the neutral conductor must be protected against short-circuit.
If the c.s.a. of the neutral conductor is equal or greater than the c.s.a. of the phase conductor, no specific protection of the neutral conductor is required because it is protected by the phase protection.

PictoChap7b.jpg




Breaking of the neutral conductor


PictoChap7c.jpg



(see Fig. G64)
The need to break or not the neutral conductor is related to the protection against indirect contact.
In TN-C scheme
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.
In TT, TN-S and IT schemes
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.


Isolation of the neutral conductor


PictoChap7d.jpg



(see Fig. G64)
It is considered to be the good practice that every circuit be provided with the means for its isolation.



TT TN-C TN-S IT
Single-phase
(Phase-Neutral)
FigG64a.jpg




or

FigG64d.jpg
FigG64b.jpg








FigG64a.jpg








FigG64c.jpg


(B)


or

FigG64a.jpg
Single-phase
(Phase-Phase)
FigG64h.jpg


(A)

or

FigG64j.jpg
FigG64j.jpg








FigG64h.jpg


(A)

or

FigG64j.jpg
FigG64j.jpg








Three-phase
four wires
Sn ≥ Sph
FigG64e.jpg












FigG64f.jpg












FigG64e.jpg












FigG64g.jpg





(B)

FigG64e.jpg
Three-phase
four wires
Sn < Sp
FigG64g.jpg












 
FigG64g.jpg












FigG64g.jpg





(B)

FigG64e.jpg

(A) Authorized for TT or TN-S systems if a RCD is installed at the origin of the circuit or upstream of it, and if no artificial neutral is  
     distributed downstream of its location
(B) The neutral overcurrent protection is not necessary:

  • If the neutral conductor is protected against short-circuits by a device placed upstream, or,
  • If the circuit is protected by a RCD which sensitivity is less than 15% of the neutral admissible current.

Fig. G64: The various situations in which the neutral conductor may appear

Share