Photovoltaic system: electrical equipments selection

From Electrical Installation Guide
Revision as of 14:59, 16 October 2013 by Mathieu GUILLOT (talk | contribs)

Grid connected PV system <= 10kW (Residential)

One single phase inverter

  • Typically, a 5kW grid-connected single-phase inverter. with UOC MAX  600V.
  • One or two strings – Isctc < 25A, IAC < 32A.
  • In this design there is no string protection.
  • A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
Fig P22.png
Needs String junction box PV array main switch Inverter AC box (400V)
Switchgears and control
Isolation || • || • (d) || (a) || • (d)
Switching
(Making & breaking
rated current || •
DC21B || (a) || • (d) ||
Control || • (b) || • (d) || (e) || • (d)
Over-current protection || (c) || || ||
Protection against
Insulation fault || || || (h) || (h)
RCD type B or A SI
Surge protection • type 2 • type 1 or 2
Enclosure Outdoor IP5x
Double insulation
Indoor IP5x
Double insulation
Standard AC requirement +
grid code requirement


Fig. P23 : 10-100kW single multi MPPT inverter

Share