Requirements applicable to special installations and locations

From Electrical Installation Guide
Revision as of 04:22, 27 November 2014 by LMischler (talk | contribs) (Text updated (guide 2015))

Home > Residential premises and other special locations > Requirements applicable to special installations and locations

Figure Q20 below summarizes the main requirements prescribed in many national and international standards.
Note: Section in brackets refer to sections of IEC 60364-7
(example: "section 701" means IEC60364-7-701)



Locations Protection principles                       IP level Wiring and cables Switchgear Socket-outlets Installation materials
Domestic dwellings and other habitations
  • TT or TN-S systems
  • Differential protection

- 300 mA if the earth electrode resistance is ≤ 80 ohms instantaneous or short time delay (type S)

- 30 mA if the earth electrode resistance is ≥ 500 ohms

  • surge arrester at the origin of the installation if 

- supply is from overhead line with bare conductors, and if
- the keraunic level > 25

  • a protective earth (PE) conductor on all circuits
20     Switch operating handles and similar devices on distribution panels, to be mounted between 1 metre and 1.80 metre above the floor
Protection by 30 mA RCDs
 
    
Bathrooms or shower rooms (section 701) Supplementary equipotential bonding in zones 0, 1, 2 and 3              
Zone 0 SELV 12 V only 27 Class II limited to strict minimum        Special appliances
Zone 1 SELV 12 V 25 Class II limited to strict minimum       Special appliances
Water heater
Zone 2 SELV 12 V or 30 mA RCD 24 Class II limited to strict minimum            Special appliances
Water heater
Class II luminaires
Zone 3   21   Only socket-outlets protected by :
  • 30 mA RCD or
  • Electrical separation or
  • SELV 50 V
  
Swimming baths
(section 702)
Supplementary equipotential bonding in zones 0, 1, and 2                 
Zone 0 SELV 12 V 28 Class II
limited to
strict minimum
        Special appliances
Zone 1   25 Class II
limited to
strict minimum
      Special appliances
Zone 2   22
(indoor)
24
(outdoor)
      Only socket-outlets protected by :
  • 30 mA RCD or
  • electrical separation or
  • SELV 50 V
  
Saunas
(section 703)
  24 Class II         Adapted to temperature
Work sites
(section 704)
Conventional voltage limit UL reduced to 25 V 44 Mechanically
protected
     Protection by 30 mA RCDs  
Agricultural and
horticultural
establishments
(section 705)
Conventional voltage limit UL reduced to 25 V
Protection against fire risks by 500 mA RCDs                 
35      Protection by 30 mA RCDs  
Restricted 
conductive
locations (section 706)
   2x              Protection of:                                
  • Portable tools by:

 - SELV or
 - Electrical separation

  • Hand-held lamps

  - By SELV

  • Fixed equipement by

  - SELV
  - Electrical separation
  - 30 mA RCDs   
  - Special 
    supplementary
    equipotential bonding

Fountains
(section 702)
Protection by 30 mA RCDs and equipotential bonding of all exposed
and extraneous conductive parts
         
Caravan park
(section 708)
  55 Flexible cable of 25 metres length      Socket-outlets shall be placed
at a height of
0.80 m to 1.50 m from the ground.
Protection of
circuits by
30 mA RCDs
(one per 6
socket-outlets)
 
Marinas and pleasure
craft (section 709)
The cable length for connection to pleasure craft must not exceeded 25 m       Protection of
circuits by
30 mA RCDs
(one per 6
socket-outlets)
 
Medical locations
Group 2 : Operating
theatres and similar (section 710)
IT medical system equipotential
grouding, limited to one operating
theatre and not exceeding 10 kVA
     Only magnetic
protection for the
primary of LV/LV
transformer. Monitoring
of secondary loads
and transformer
temperature
Protection of circuits by thermal-magnetic protection only. One to three per circuit.     
Medical locations
Group 1 :
Hospitalization and similar (section 710)
TT or TNS         Protection by
30 mA RCDs
 
Exhibitions, shows and
stands (section 711)
TT or TN-S systems 4x     Protection by
30 mA RCDs
 
Balneotherapy
(cure-centre baths)
Individual: see section 701 (volumes 0 and 1)
Collective: see section 702 (volumes 0 and 1)
         
Motor-fuel filling
stations
Explosion risks in security zones   Limited to the necessary minimum      
Motor vehicules Protection by RCDs or by electrical separation          
External lighting
installations (section 714)
  23     Protection by
30 mA RCDs
 
Mobile or transportable
units (section 717)
The use of TN-C system is not permitted inside any unit       30 mA RCDs
must be used for
all socket-outlets 
supplying 
equipment 
outside the unit 
 

Fig. Q20: Main requirements prescribed in many national and international standards 

ru:Стандарты по устройству электроустановок для жилых помещений и коттеджей zh:住宅电气标准

Share