Calculation of minimum levels of short-circuit current
If a protective device in a circuit is intended only to protect against short-circuit faults, it is essential that it will operate with certainty at the lowest possible level of short-circuit current that can occur on the circuit
In general, on LV circuits, a single protective device protects against all levels of current, from the overload threshold through the maximum rated short-circuit current breaking capability of the device. The protection device should be able to operate in a maximum time to ensure people and circuit safety, for all short-circuit current or fault current that may occur. To check that behavior, calculation of minimal short-circuit current or fault current is mandatory.
In addition, in certain cases overload protective devices and separate short-circuit protective devices are used.
Examples of such arrangements
Figures G40 to G42 show some common arrangements where overload and short-circuit protections are achieved by separate devices.
Fig. G40: Circuit protected by aM fuses
Fig. G41: Circuit protected by circuit-breaker without thermal overload relay
Fig. G42a: Circuit-breaker D provides protection against short-circuit faults as far as and including the load
As shown in Figures G40 and G41, the most common circuits using separate devices control and protect motors.
Figure G42a constitutes a derogation in the basic protection rules, and is generally used on circuits of prefabricated bustrunking, lighting rails, etc.
Variable speed drive
Figure G42b shows the functions provided by the variable speed drive, and if necessary some additional functions provided by devices such as circuit-breaker, thermal relay, RCD.
Protection to be provided | Protection generally provided by the variable speed drive | Additional protection if not provided by the variable speed drive |
---|---|---|
Cable overload | Yes | CB / Thermal relay |
Motor overload | Yes | CB / Thermal relay |
Downstream short-circuit | Yes | |
Variable speed drive overload | Yes | |
Overvoltage | Yes | |
Undervoltage | Yes | |
Loss of phase | Yes | |
Upstream short-circuit | Circuit-breaker (short-circuit tripping) | |
Internal fault | Circuit-breaker (short-circuit and overload tripping) | |
Downstream earth fault (indirect contact) | (self protection) | RCD ≥ 300 mA or CB in TN earthing system |
Direct contact fault | RCD ≤ 30 mA |
Fig. G42b: Protection to be provided for variable speeed drive applications
Conditions to be fulfilled
The protective device must fulfill:
- instantaneous trip setting Im < Iscmin for a circuit-breaker
- fusion current Ia < Iscmin for a fuse
The protective device must therefore satisfy the two following conditions:
- Its breaking capacity must be greater than Isc, the 3-phase short-circuit current at its point of installation
- Elimination of the minimum short-circuit current possible in the circuit, in a time tc compatible with the thermal constraints of the circuit conductors, where:[math]\displaystyle{ tc \ge \frac{k^2S^2}{Isc_{min}\, ^2} }[/math]
(valid for tc < 5 seconds)
where S is the cross section area of the cable, k is a factor depending of the cable conductor material, the insulation material and initial temperature.
Example: for copper XLPE, initial temperature 90 °C, k = 143 (see IEC60364-4-43 §434.3.2 table 43A).
Comparison of the tripping or fusing performance curve of protective devices, with the limit curves of thermal constraint for a conductor shows that this condition is satisfied if:
- Isc (min) > Im (instantaneous or short timedelay circuit-breaker trip setting current level), (see Fig. G43)
- Isc (min) > Ia for protection by fuses. The value of the current Ia corresponds to the crossing point of the fuse curve and the cable thermal withstand curve (see Fig. G44 and G45)
Fig. G43: Protection by circuit-breaker
Fig. G44: Protection by aM-type fuses
Fig. G45: Protection by gG-type fuses
Practical method of calculating Lmax
In practice this means that the length of circuit downstream of the protective device must not exceed a calculated maximum length: [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}L_{max}=\frac{0.8\ U\ Sph}{2 \rho Im} }[/math]
The limiting effect of the impedance of long circuit conductors on the value of short-circuit currents must be checked and the length of a circuit must be restricted accordingly.
The method of calculating the maximum permitted length has already been demonstrated in TN- and IT- earthed schemes for single and double earth faults, respectively. Two cases are considered below:
1 - Calculation of Lmax for a 3-phase 3-wire circuit
The minimum short-circuit current will occur when two phase wires are short-circuited at the remote end of the circuit (see Fig. G46).
Fig G46: Definition of L for a 3-phase 3-wire circuit
Using the “conventional method”, the voltage at the point of protection P is assumed to be 80% of the nominal voltage during a short-circuit fault, so that 0.8 U = Isc Zd, where:
Zd = impedance of the fault loop
Isc = short-circuit current (ph/ph)
U = phase-to-phase nominal voltage
For cables ≤ 120 mm2, reactance may be neglected, so that [math]\displaystyle{ Zd=\rho \frac{2L}{Sph}\ ^{(1)} }[/math]
where:
ρ = resistivity of conductor material at the average temperature during a short-circuit,
Sph = c.s.a. of a phase conductor in mm2
L = length in metres
The condition for the cable protection is Im ≤ Isc with Im = magnetic trip current setting of the CB.
This leads to [math]\displaystyle{ Im \ge \frac{0.8 U}{Zd} }[/math] which gives with U = 400 V
ρ = 1.25 x 0.018 = 0.023 Ω.mm2/m(2) (Cu)
Lmax = maximum circuit length in metres [math]\displaystyle{ L_{max}=\frac {k\ Sph}{Im} }[/math]
2 - Calculation of Lmax for a 3-phase 4-wire 230/400 V circuit
The minimum Isc will occur when the short-circuit is between a phase conductor and the neutral.
A calculation similar to that of example 1 above is required, but using the following formulae (for cable ≤ 120 mm2 (1) ).
- Where Sn for the neutral conductor = Sph for the phase conductor [math]\displaystyle{ L_{max}=\frac {3,333 Sph}{Im} }[/math]
- If Sn for the neutral conductor < Sph, then [math]\displaystyle{ L_{max}= 6,666 \frac{Sph}{Im}\frac{1}{1+m} }[/math] where [math]\displaystyle{ m=\frac{Sph}{Sn} }[/math]
For larger c.s.a.’s than those listed, reactance values must be combined with those of resistance to give an impedance. Reactance may be taken as 0.08 mΩ/m for cables (at 50 Hz). At 60 Hz the value is 0.096 mΩ/m.
(1) For larger c.s.a.’s, the resistance calculated for the conductors must be increased to account for the non-uniform current density in the conductor (due to “skin” and “proximity” effects) Suitable values are as follows: 150 mm2: R + 15% 185 mm2: R + 20% 240 mm2: R + 25% 300 mm2: R + 30% (2) The factor 1.25 applied to the copper resistivity is due to the elevated temperature of the conductor when passing short-circuit current. This value of 1.25 corresponds to the max temperature of EPR or XLPE cables. |
Tabulated values for Lmax
Figure G47 below gives maximum circuit lengths (Lmax) in metres, for:
- 3-phase 4-wire 400 V circuits (i.e. with neutral) and
- 1-phase 2-wire 230 V circuits
protected by general-purpose circuit-breakers. In other cases, apply correction factors (given in Figure G53) to the lengths obtained. The calculations are based on the above methods, and a short-circuit trip level within ± 20% of the adjusted value Im. For the 50 mm2 c.s.a., calculation are based on a 47.5 mm2 real c.s.a.
Operating current level Im of the instantaneous magnetic tripping element (in A) |
c.s.a. (nominal cross-sectional-area) of conductors (in mm2) | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | |
50 | 100 | 167 | 267 | 400 | |||||||||||
63 | 79 | 133 | 212 | 317 | |||||||||||
80 | 63 | 104 | 167 | 250 | 417 | ||||||||||
100 | 50 | 83 | 133 | 200 | 333 | ||||||||||
125 | 40 | 67 | 107 | 160 | 267 | 427 | |||||||||
160 | 31 | 52 | 83 | 125 | 208 | 333 | |||||||||
200 | 25 | 42 | 67 | 100 | 167 | 267 | 417 | ||||||||
250 | 20 | 33 | 53 | 80 | 133 | 213 | 333 | 467 | |||||||
320 | 16 | 26 | 42 | 63 | 104 | 167 | 260 | 365 | 495 | ||||||
400 | 13 | 21 | 33 | 50 | 83 | 133 | 208 | 292 | 396 | ||||||
500 | 10 | 17 | 27 | 40 | 67 | 107 | 167 | 233 | 317 | ||||||
560 | 9 | 15 | 24 | 36 | 60 | 95 | 149 | 208 | 283 | 417 | |||||
630 | 8 | 13 | 21 | 32 | 63 | 85 | 132 | 185 | 251 | 370 | |||||
700 | 7 | 12 | 19 | 29 | 48 | 76 | 119 | 167 | 226 | 333 | 452 | ||||
800 | 6 | 10 | 17 | 25 | 42 | 67 | 104 | 146 | 198 | 292 | 396 | ||||
875 | 6 | 10 | 15 | 23 | 38 | 61 | 95 | 133 | 181 | 267 | 362 | 457 | |||
1000 | 5 | 8 | 13 | 20 | 33 | 53 | 83 | 117 | 158 | 233 | 317 | 400 | 435 | ||
1120 | 4 | 7 | 12 | 18 | 30 | 48 | 74 | 104 | 141 | 208 | 283 | 357 | 388 | 459 | |
1250 | 4 | 7 | 11 | 16 | 27 | 43 | 67 | 93 | 127 | 187 | 253 | 320 | 348 | 411 | |
1600 | 5 | 8 | 13 | 21 | 33 | 52 | 73 | 99 | 146 | 198 | 250 | 272 | 321 | 400 | |
2000 | 4 | 7 | 10 | 17 | 27 | 42 | 58 | 79 | 117 | 158 | 200 | 217 | 257 | 320 | |
2500 | 5 | 8 | 13 | 21 | 33 | 47 | 63 | 93 | 127 | 160 | 174 | 206 | 256 | ||
3200 | 4 | 6 | 10 | 17 | 26 | 36 | 49 | 73 | 99 | 125 | 136 | 161 | 200 | ||
4000 | 5 | 8 | 13 | 21 | 29 | 40 | 58 | 79 | 100 | 109 | 128 | 160 | |||
5000 | 4 | 7 | 11 | 17 | 23 | 32 | 47 | 63 | 80 | 87 | 103 | 128 | |||
6300 | 5 | 8 | 13 | 19 | 25 | 37 | 50 | 63 | 69 | 82 | 102 | ||||
8000 | 4 | 7 | 10 | 15 | 20 | 29 | 40 | 50 | 54 | 64 | 80 | ||||
10000 | 5 | 8 | 12 | 16 | 23 | 32 | 40 | 43 | 51 | 64 | |||||
12500 | 4 | 7 | 9 | 13 | 19 | 25 | 32 | 35 | 41 | 51 |
Fig. G47: Maximum circuit lengths in metres for copper conductors (for aluminium, the lengths must be multiplied by 0.62)
Figures G48 to G50 give maximum circuit length (Lmax) in metres for:
- 3-phase 4-wire 400 V circuits (i.e. with neutral) and
- 1-phase 2-wire 230 V circuits
protected in both cases by domestic-type circuit-breakers or with circuit-breakers having similar tripping/current characteristics. In other cases, apply correction factors to the lengths indicated. These factors are given in Figure G51.
Circuit-breaker rating (A) | c.s.a. (nominal cross-sectional-area) of conductors (in mm2) | ||||||||
---|---|---|---|---|---|---|---|---|---|
1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | |
6 | 200 | 333 | 533 | 800 | |||||
10 | 120 | 200 | 320 | 480 | 800 | ||||
16 | 75 | 125 | 200 | 300 | 500 | 800 | |||
20 | 60 | 100 | 160 | 240 | 400 | 640 | |||
25 | 48 | 80 | 128 | 192 | 320 | 512 | 800 | ||
32 | 37 | 62 | 100 | 150 | 250 | 400 | 625 | 875 | |
40 | 30 | 50 | 80 | 120 | 200 | 320 | 500 | 700 | |
50 | 24 | 40 | 64 | 96 | 160 | 256 | 400 | 560 | 760 |
63 | 19 | 32 | 51 | 76 | 127 | 203 | 317 | 444 | 603 |
80 | 15 | 25 | 40 | 60 | 100 | 160 | 250 | 350 | 475 |
100 | 12 | 20 | 32 | 48 | 80 | 128 | 200 | 280 | 380 |
125 | 10 | 16 | 26 | 38 | 64 | 102 | 160 | 224 | 304 |
Fig. G48: Maximum length of copper-conductor circuits in metres protected by B-type circuit-breakers
Circuit-breaker rating (A) |
c.s.a. (nominal cross-sectional-area) of conductors (in mm2) | ||||||||
---|---|---|---|---|---|---|---|---|---|
1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | |
6 | 100 | 167 | 267 | 400 | 667 | ||||
10 | 60 | 100 | 160 | 240 | 400 | 640 | |||
16 | 37 | 62 | 100 | 150 | 250 | 400 | 625 | 875 | |
20 | 30 | 50 | 80 | 120 | 200 | 320 | 500 | 700 | |
25 | 24 | 40 | 64 | 96 | 160 | 256 | 400 | 560 | 760 |
32 | 18.0 | 31 | 50 | 75 | 125 | 200 | 313 | 438 | 594 |
40 | 15.0 | 25 | 40 | 60 | 100 | 160 | 250 | 350 | 475 |
50 | 12.0 | 20 | 32 | 48 | 80 | 128 | 200 | 280 | 380 |
63 | 9.5 | 16.0 | 26 | 38 | 64 | 102 | 159 | 222 | 302 |
80 | 7.5 | 12.5 | 20 | 30 | 50 | 80 | 125 | 175 | 238 |
100 | 6.0 | 10.0 | 16.0 | 24 | 40 | 64 | 100 | 140 | 190 |
125 | 5.0 | 8.0 | 13.0 | 19.0 | 32 | 51 | 80 | 112 | 152 |
Fig. G49: Maximum length of copper-conductor circuits in metres protected by C-type circuit-breakers
Circuit-breaker rating (A) |
c.s.a. (nominal cross-sectional-area) of conductors (in mm2) | ||||||||
---|---|---|---|---|---|---|---|---|---|
1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | |
1 | 429 | 714 | |||||||
2 | 214 | 357 | 571 | 857 | |||||
3 | 143 | 238 | 381 | 571 | 952 | ||||
4 | 107 | 179 | 286 | 429 | 714 | ||||
6 | 71 | 119 | 190 | 286 | 476 | 762 | |||
10 | 43 | 71 | 114 | 171 | 286 | 457 | 714 | ||
16 | 27 | 45 | 71 | 107 | 179 | 286 | 446 | 625 | 848 |
20 | 21 | 36 | 57 | 86 | 143 | 229 | 357 | 500 | 679 |
25 | 17.0 | 29 | 46 | 69 | 114 | 183 | 286 | 400 | 543 |
32 | 13.0 | 22 | 36 | 54 | 89 | 143 | 223 | 313 | 424 |
40 | 11.0 | 18.0 | 29 | 43 | 71 | 114 | 179 | 250 | 339 |
50 | 9.0 | 14.0 | 23 | 34 | 57 | 91 | 143 | 200 | 271 |
63 | 7.0 | 11.0 | 18.0 | 27 | 45 | 73 | 113 | 159 | 215 |
80 | 5.0 | 9.0 | 14.0 | 21 | 36 | 57 | 89 | 125 | 170 |
100 | 4.0 | 7.0 | 11.0 | 17.0 | 29 | 46 | 71 | 100 | 136 |
125 | 3.0 | 6.0 | 9.0 | 14.0 | 23 | 37 | 57 | 80 | 109 |
Fig. G50: Maximum length of copper-conductor circuits in metres protected by D-type circuit-breakers
Circuit detail | ||
---|---|---|
3-phase 3-wire 400 V circuit or 1-phase 2-wire 400 V circuit (no neutral) | 1.73 | |
1-phase 2-wire (phase and neutral) 230 V circuit | 1 | |
3-phase 4-wire 230/400 V circuit or 2-phase 3-wire 230/400 V circuit (i.e with neutral) | Sph / S neutral = 1 | 1 |
Sph / S neutral = 2 | 0.67 |
Fig. G51: Correction factor to apply to lengths obtained from Figures G47 to G50
Note: IEC 60898 accepts an upper short-circuit-current tripping range of 10-50 In for type D circuit-breakers. European standards, and Figure G50 however, are based on a range of 10-20 In, a range which covers the vast majority of domestic and similar installations.
Examples
Example 1
In a 3-phase 3-wire 400 V installation the protection is provided by a 50 A circuit-breaker type NS80HMA, the instantaneous short-circuit current trip, is set at 500 A (accuracy of ± 20%), i.e. in the worst case would require 500 x 1,2 = 600 A to trip. The cable c.s.a. = 10 mm2 and the conductor material is copper.
In Figure G47, the row Im = 500 A crosses the column c.s.a. = 10 mm2 at the value for Lmax of 67 m. The circuit-breaker protects the cable against short-circuit faults, therefore, provided that its length does not exceed 67 metres.
Example 2
In a 3-phase 3-wire 400 V circuit (without neutral), the protection is provided by a 220 A circuit-breaker type NSX250N with an instantaneous short-circuit current trip unit type MA set at 2,000 A (± 20%), i.e. a worst case of 2,400 A to be certain of tripping. The cable c.s.a. = 120 mm2 and the conductor material is copper.
In Figure G47 the row Im = 2,000 A crosses the column c.s.a. = 120 mm2 at the value for Lmax of 200 m. Being a 3-phase 3-wire 400 V circuit (without neutral), a correction factor from Figure G51 must be applied. This factor is seen to be 1.73.
The circuit-breaker will therefore protect the cable against short-circuit current, provided that its length does not exceed 200 x 1.73= 346 metres.
ru:Расчет минимальных величин тока короткого замыкания zh:最小短路电流的计算