LED lamps - choice of circuit breaker

From Electrical Installation Guide
Revision as of 16:01, 25 July 2016 by LMischler (talk | contribs) (creation (guide 2015))
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Home > Characteristics of particular sources and loads > Lighting circuits > LED lamps - choice of circuit breaker


Choice of circuit-breaker for discharge and fluorescent lamps

Protection of lamp circuits: Maximum number of lamps and MCB rating versus lamp type, unit power and MCB tripping curve

During start up of discharge lamps (with their ballast), the inrush current drawn by each lamp may be in the order of:

  • 25 x circuit start current for the first 3 ms
  • 7 x circuit start current for the following 2 s

For fluorescent lamps with High Frequency Electronic control ballast, the protective device ratings must cope with 25 x inrush for 250 to 350 µs.

However due to the circuit resistance the total inrush current seen by the MCB is lower than the summation of all individual lamp inrush current if directly connected to the MCB.

The tables below (see Fig. N53 to N58) take into account:

  • Circuits cables have a length of 20 meters from distribution board to the first lamp and 7 meters between each additional fittings.
  • MCB rating is given to protect the lamp circuit in accordance with the cable cross section, and without unwanted tripping upon lamp starting.
  • MCB tripping curve (C = instantaneous trip setting 5 to 10 In, D = instantaneous trip setting 10 to 14 In).


Lamp
power (W)
Number of lamps per circuit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
MCB rating C & D tripping curve    
14/18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
14x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
14x3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10
14x4 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10
18x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
18x4 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10
21/24 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
21/24 x 2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
28 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
28x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10
35/36/39 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
35/36 x 2 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10
38/39 x 2 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10
40/42 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
40/42 x2 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10 16
49/50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
49/50 x2 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16
54/55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10  10
54/55 x2 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16
60 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10

Fig. N52: Fluorescent tubes with electronic ballast - Vac = 230 V



Lamp
power (W)
Number of lamps per circuit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
MCB rating C & D tripping curve    
6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
11 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
13 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
14 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
15 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
16 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
17 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
20 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
21 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
23 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10

Fig. N53: Compact fluorescent lamps - Vac = 230 V



Lamp
power (W)
Number of lamps per circuit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
MCB rating C tripping curve    
50 6 6 6
6 6 6 6 6 6 6 6 6 6 6 10 10 10 10
80 6
6 6  6 6 10 10 10 10 10 10 10 16 16 16
125 6 6 6 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20 20
250 6 10 10 16 16 16 16 16 16 20 20 25 25 25 32 32 32 32 40 40
400 6 16 20 25 25 32 32 32 32 32 32 40 40 40 50 50 50 50 63 63
1000 16 32 40 50 50 50 50 50 63 - - - - - - - - - - -
MCB rating D tripping curve
50 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 
80 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16
125 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16 20 20
250 6 6 10 10 10 10 16 16 16 20 20 25 25 25 32 32 32 32 40 40
400 6 10 16 16 20 20 25 25 25 32 32 40 40 40 50 50 50 50 63 63
1000 10 20 25 32 40 40 50 63 63 - - - - - - - - - - -

Fig. N54: High pressure mercury vapour (with ferromagnetic ballast and PF correction) - Vac = 230 V



Lamp
power (W)
                                            Number of lamps per circuit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
MCB rating C tripping curve
Ferromagnetic ballast
18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
26 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
35/36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
55 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10
91 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16 16
131 6 6 6 10 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20
135 6 6 6 10 10 10 10 10 10 10 10 16 16 16 16 16 16 20 20 20
180 6 6 10 10 10 10 10 10 16 16 16 16 20 20 20 20 25 25 25 25
Electronic ballast
36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
66 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10
91 6 6 6 6 6 6 10 10 10 10 10 10 10 10 10 10 16 16 16 16
MCB rating D tripping curve
Ferromagnetic ballast
18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
26 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
35/36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10
91 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16
131 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16 16 20
135 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 20 20 20
180 6 6 6 6 10 10 10 10 16 16 16 16 20 20 20 20 25 25 25 25
Electronic ballast
36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
66 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10
91 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16

Fig. N55: 'Low pressure sodium (with PF correction) - Vac = 230 V


 

Lamp power (W)                                  Number of lamps per circuit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
MCB rating C tripping curve
Ferromagnetic ballast
50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10
70 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16
100 6 6 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16
150 6 6 10 10 10 10 10 10 6 16 16 16 16 16 16 20 20 20 25 25
250 6 10 16 16 16 20 20 20 20 20 20 25 25 25 32 32 32 32 40 40
400 10 16 20 25 32 32 32 32 32 32 32 40 40 40 50 50 50 50 63 63
1000 16 32 40 50 50 50 50 63 63 -
Electronic ballast
35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
50 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10
100 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16
MCB rating D tripping curve
Ferromagnetic ballast
50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10
70 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16
100 6 6 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16
150 6 6 6 6 6 10 10 10 10 16 16 16 16 16 16 20 20 20 25 25
250 6 6 10 10 16 16 16 16 16 20 20 25 25 25 32 32 32 32 40 40
400 6 10 16 16 20 20 25 25 25 32 32 40 40 40 50 50 50 50 63 63
1000 10 20 32 32 40 40 50 63 63 - - - - - - - - - - -
Electronic ballast
35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
50 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10
100 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16

Fig. N56: High pressure sodium (with PF correction) - Vac = 230 V



Lamp power (W)                                   Number of lamps per circuit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
MCB rating C tripping curve
Ferromagnetic ballast
35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
70 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16
150 6 6 10 10 10 10 10 10 10 16 16 16 16 16 16 20 20 20 25 25
250 6 10 16 16 16 20 20 20 20 20 20 25 25 25 32 32 32 32 40 40
400 6 16 20 25 25 32 32 32 32 32 32 40 40 40 50 50 50 50 63 63
1000 16 32 40 50 50 50 50 63 63 63 63 63 63 63 63 63 63 63 63 63
1800/2000 25 50 63 63 63 - - - - - - - - - - - - - - -
Electronic ballast
35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
70 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10
150 6 6 6 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20 20 20
MCB rating D tripping curve
Electronic ballast
35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
70 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16
150 6 6 6 6 6 10 10 10 10 16 16 16 16 16 16 20 20 20 25 25
250 6 6 10 10 16 16 16 16 16 20 20 25 25 25 32 32 32 32 40 40
400 6 10 16 16 20 20 25 25 25 32 32 40 40 40 50 50 50 50 63 63
1000 16 20 32 32 40 50 50 63 63 - - - - - - - - - - -
1800 16 32 40 50 63 63 - - - - - - - - - - - - - -
2000 20 32 40 50 63 - - - - - - - - - - - - - - -
Electronic ballast
35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
70 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10
150 6 6 6 6 6 6 6 10 10 10 16 16 16 16 16 16 16 20 20 20

Fig. N57: <Metal halide (with PF correction) - Vac = 230 V


 

Lamp
power (W)
Number of lamps per circuit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
                                  MCB rating C tripping curve    
1800 16 32 40 50 50 50  50 63 63 - - - - - - - - - -
2000 16 32 40 50 50 50 50 63 63 - - - - - - - - - - -
                             MCB rating D tripping curve
1800 16 20 32 32 32 32 50 63 63 - - - - - - - - - - -
2000 16 25 32 32 32 32 50 63 - - - - - - - - - - - -

Fig. N58: <Metal halide (with ferromagnetic ballast and PF correction) - Vac = 400 V


ru:Ограничения, связанные с осветительными устройствами, и рекомендации

Share