LED lamps - choice of circuit breaker
Choice of circuit-breaker for LED lamps and fixtures
Use of circuit breakers
The new lighting technologies with electronic interfaces (ballasts, drivers) cause a large transient inrush current at power up which could result in circuit breaker tripping.
These phenomena are especially significant with LED lighting.
Coordination curves between the number of LED luminaires and circuit breaker rating:
Maximum number of luminaires depending on the circuit breaker rating and curve
Unit power of the luminaire (W) | Circuit breaker rating | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
10 A | 16 A | 20 A | ||||||||||
Curve | Curve | Curve | ||||||||||
B | C | D | B, C, D with iCT+ or iTL+ | B | C | D | B, C, D with iCT+ or iTL+ | B | C | D | B, C, D with iCT+ | |
10 | 15 | 30 | 48 | - | 22 | 44 | 69 | - | 32 | 63 | 98 | - |
30 | 11 | 24 | 38 | 57 | 17 | 34 | 54 | 90 | 25 | 49 | 77 | 110 |
50 | 8 | 17 | 27 | 41 | 12 | 25 | 39 | 66 | 18 | 35 | 56 | 83 |
75 | 4 | 11 | 17 | 28 | 7 | 15 | 25 | 44 | 11 | 21 | 36 | 55 |
150 | - | 5 | 9 | 13 | 2 | 7 | 12 | 22 | 4 | 9 | 18 | 28 |
250 | - | 3 | 5 | 8 | - | 4 | 7 | 13 | - | 5 | 10 | 16 |
400 | - | 1 | 4 | 5 | - | 2 | 6 | 8 | - | 3 | 9 | 10 |
Depending on the control device used, the transient current surge may:
- require derating of the circuit breaker according to the coordination curves between the number of luminaires and the circuit breaker rating, when using conventional control devices: CT, TL (electromechanical control device),
- be reduced by using the following technologies:
- softStart: implemented by a control integrated in the driver or by variable speed controller,
- controlled-action control contactor (iTL+, iCT+) (closing on zero crossing by the voltage, only derating is linked to the lighting circuit's power factor.
These technologies make it possible to use the circuit breakers without derating due to the lamp technology.
Example:
Circuit rated power = 230 V AC x Circuit breaker rating x Cos φ.
Other lamp technologies
The figure N55 below indicates the maximum number of lamps according to the circuit breaker rating and curve , for C-curve circuit breakers
- for B-curve circuit breakers, the number of lamps should be reduced by 50%,
- for D-curve circuit breakers, the number of lamps should be increased by 50%.
Products | Circuit breaker (C curve) | ||||||
---|---|---|---|---|---|---|---|
Type of lamp | 10 A | 16 A | 25 A | 40 A | 63 A | ||
Standard incandescent lamps, LV halogen lamps, replacement mercury vapor lamps (without ballast) | |||||||
40 W | 28 | 46 | 70 | 140 | 207 | ||
60 W | 23 | 36 | 55 | 103 | 152 | ||
75 W | 29 | 31 | 46 | 80 | 121 | ||
100 W | 15 | 23 | 33 | 60 | 88 | ||
ELV 12 or 24 V halogen lamps | |||||||
Ferromagnetic transformer | 20 W | 11 | 19 | 27 | 50 | 75 | |
50 W | 8 | 12 | 19 | 33 | 51 | ||
75 W | 7 | 10 | 14 | 27 | 43 | ||
100 W | 5 | 8 | 10 | 22 | 33 | ||
Electronic transformer | 20 W | 47 | 74 | 108 | 220 | 333 | |
50 W | 19 | 31 | 47 | 92 | 137 | ||
75 W | 15 | 24 | 34 | 64 | 94 | ||
100 W | 12 | 20 | 26 | 51 | 73 | ||
Fluorescent tubes with starter and ferromagnetic ballast | |||||||
1 tube without compensation (1) | 15 W | 16 | 26 | 37 | 85 | 121 | |
18 W | 16 | 26 | 37 | 85 | 121 | ||
20 W | 16 | 26 | 37 | 85 | 121 | ||
36 W | 15 | 24 | 34 | 72 | 108 | ||
40 W | 15 | 24 | 34 | 72 | 108 | ||
58 W | 9 | 15 | 21 | 43 | 68 | ||
65 W | 9 | 15 | 21 | 43 | 68 | ||
80 W | 8 | 12 | 19 | 36 | 58 | ||
115 W | 6 | 9 | 12 | 24 | 38 | ||
1 tube with parallel compensation (2) | 15 W | 5 µF | 11 | 19 | 24 | 48 | 72 |
18 W | 5 µF | 11 | 19 | 24 | 48 | 72 | |
20 W | 5 µF | 11 | 19 | 24 | 48 | 72 | |
36 W | 5 µF | 11 | 19 | 24 | 48 | 72 | |
40 W | 5 µF | 11 | 19 | 24 | 48 | 72 | |
58 W | 7 µF | 8 | 12 | 19 | 36 | 51 | |
65 W | 7 µF | 8 | 12 | 19 | 36 | 51 | |
80 W | 7 µF | 8 | 12 | 19 | 36 | 51 | |
115 W | 16 µF | 4 | 7 | 9 | 17 | 24 | |
2 or 4 tubes with series compensation | 2 x 18 W | 23 | 36 | 56 | 96 | 148 | |
4 x 18 W | 12 | 20 | 29 | 52 | 82 | ||
2 x 36 W | 12 | 20 | 29 | 52 | 82 | ||
2 x 58 W | 8 | 12 | 20 | 33 | 51 | ||
2 x 65 W | 8 | 12 | 20 | 33 | 51 | ||
2 x 80 W | 7 | 11 | 15 | 26 | 41 | ||
2 x 115 W | 5 | 8 | 12 | 20 | 31 | ||
Fluorescent tubes with electronic ballast | |||||||
1 or 2 tubes | 18 W | 56 | 90 | 134 | 268 | 402 | |
36 W | 28 | 46 | 70 | 142 | 213 | ||
58 W | 19 | 31 | 45 | 90 | 134 | ||
2 x 18 W | 27 | 44 | 67 | 134 | 201 | ||
2 x 36 W | 16 | 24 | 37 | 72 | 108 | ||
2 x 58 W | 9 | 15 | 23 | 46 | 70 | ||
Compact fluorescent lamps | |||||||
External electronic ballast | 5 W | 158 | 251 | 399 | 810 | Infrequent use | |
7 W | 113 | 181 | 268 | 578 | |||
9 W | 92 | 147 | 234 | 463 | |||
11 W | 79 | 125 | 196 | 396 | |||
18 W | 49 | 80 | 127 | 261 | |||
26 W | 37 | 60 | 92 | 181 | |||
Integral electronic ballast (replacing incandescent lamps) | 5 W | 121 | 193 | 278 | 568 | 859 | |
7 W | 85 | 137 | 198 | 405 | 621 | ||
9 W | 71 | 113 | 160 | 322 | 497 | ||
11 W | 59 | 94 | 132 | 268 | 411 | ||
18 W | 36 | 58 | 83 | 167 | 257 | ||
26 W | 25 | 40 | 60 | 121 | 182 | ||
Low-pressure sodium vapor lamps with ferromagnetic ballast and external ignitor | |||||||
Without compensation (1) | 35 W | 4 | 7 | 11 | 17 | 29 | |
55 W | 4 | 7 | 11 | 17 | 29 | ||
90 W | 3 | 4 | 8 | 11 | 23 | ||
135 W | 2 | 3 | 5 | 8 | 12 | ||
180 W | 1 | 2 | 4 | 7 | 10 | ||
With parallel compensation (2) | 35 W | 20 µF | 3 | 4 | 7 | 12 | 19 |
55 W | 20 µF | 3 | 4 | 7 | 12 | 19 | |
90 W | 26 µF | 2 | 3 | 5 | 8 | 13 | |
135 W | 40 µF | 1 | 2 | 3 | 5 | 9 | |
180 W | 45 µF | 0 | 1 | 2 | 4 | 8 | |
High-pressure sodium vapor lamps
Metal-iodide lamps | |||||||
Ferromagnetic ballast with external ignitor, without compensation (1) | 35 W | 12 | 19 | 28 | 50 | 77 | |
70 W | 7 | 11 | 15 | 24 | 38 | ||
150 W | 3 | 5 | 9 | 15 | 22 | ||
250 W | 2 | 3 | 5 | 10 | 13 | ||
400 W | 0 | 1 | 3 | 6 | 10 | ||
1000 W | 0 | 0 | 1 | 2 | 3 | ||
Ferromagnetic ballast and external ignitor, with parallel compensation (2) | 35 W | 6 µF | 14 | 17 | 26 | 43 | 70 |
70 W | 12 µF | 8 | 9 | 13 | 23 | 35 | |
150 W | 20 µF | 5 | 6 | 9 | 14 | 21 | |
250 W | 32 µF | 3 | 4 | 5 | 10 | 14 | |
400 W | 45 µF | 2 | 3 | 4 | 7 | 9 | |
1000 W | 60 µF | 0 | 1 | 2 | 4 | 7 | |
2000 W | 85 µF | 0 | 0 | 1 | 2 | 3 | |
Electronic ballast | 35 W | 15 | 24 | 38 | 82 | 123 | |
70 W | 11 | 18 | 29 | 61 | 92 | ||
150 W | 6 | 9 | 14 | 31 | 48 |
(1) Circuits with non-compensated ferromagnetic ballasts consume twice as much current for a given power output. This explains the small number of lamps in this configuration.
(2) The total capacitance of the power factor capacitors in parallel on a circuit limits the number of lamps that can be controlled by a contactor. The total downstream capacitance of a modular contactor of rating 16, 25, 40 or 63 A should not exceed 75, 100, 200 or 300 μF respectively. Allow for these limits to calculate the maximum acceptable number of lamps if the capacitance values are different from those in the table.
High-pressure sodium vapor lamps: for the 10 A and 16 A B-curve ratings, the number of lamps should be reduced by 10% to limit unwanted magnetic tripping.