Chapter G

Sizing and protection of conductors


Calculation of minimum levels of short-circuit current

From Electrical Installation Guide
Revision as of 08:31, 28 November 2016 by CleanUp2016 (talk | contribs) (Cleanup_2016_2)

Home > Sizing and protection of conductors > Particular cases of short-circuit current > Calculation of minimum levels of short-circuit current


If a protective device in a circuit is intended only to protect against short-circuit faults, it is essential that it will operate with certainty at the lowest possible level of short-circuit current that can occur on the circuit

In general, on LV circuits, a single protective device protects against all levels of current, from the overload threshold through the maximum rated short-circuit current breaking capability of the device. The protection device should be able to operate in a maximum time to ensure people and circuit safety, for all short-circuit current or fault current that may occur. To check that behavior, calculation of minimal short-circuit current or fault current is mandatory.

In addition, in certain cases overload protective devices and separate short-circuit protective devices are used.

Examples of such arrangements

Figures G40 to G42 show some common arrangements where overload and short-circuit protections are achieved by separate devices.

Fig. G40 – Circuit protected by aM fuses
Fig. G41 – Circuit protected by circuit breaker without thermal overload relay
Fig. G42a – Circuit breaker D provides protection against short-circuit faults as far as and including the load

As shown in Figures G40 and G41, the most common circuits using separate devices control and protect motors.

Figure G42a constitutes a derogation in the basic protection rules, and is generally used on circuits of prefabricated bustrunking, lighting rails, etc.

Variable speed drive

Figure G42b shows the functions provided by the variable speed drive, and if necessary some additional functions provided by devices such as circuit-breaker, thermal relay, RCD.

Protection to be provided Protection generally provided by the variable speed drive Additional protection if not provided by the variable speed drive
Cable overload Yes CB / Thermal relay
Motor overload Yes CB / Thermal relay
Downstream short-circuit Yes
Variable speed drive overload Yes
Overvoltage Yes
Undervoltage Yes
Loss of phase Yes
Upstream short-circuit Circuit-breaker

(short-circuit tripping)

Internal fault Circuit-breaker

(short-circuit and overload tripping)

Downstream earth fault (indirect contact) (self protection) RCD ≥ 300 mA or CB in TN earthing system
Direct contact fault RCD ≤ 30 mA
Fig. G42b – Protection to be provided for variable speeed drive applications

Conditions to be fulfilled

The protective device must fulfill:

  • instantaneous trip setting Im < Iscmin for a circuit-breaker
  • fusion current Ia < Iscmin for a fuse

The protective device must therefore satisfy the two following conditions:

  • Its breaking capacity must be greater than Isc, the 3-phase short-circuit current at its point of installation
  • Elimination of the minimum short-circuit current possible in the circuit, in a time tc compatible with the thermal constraints of the circuit conductors, where:

[math]\displaystyle{ tc \le \frac{k^2S^2}{Isc_{min}\, ^2} }[/math]   (valid for tc < 5 seconds)

where S is the cross section area of the cable, k is a factor depending of the cable conductor material, the insulation material and initial temperature.

Example: for copper XLPE, initial temperature 90 °C, k = 143 (see IEC60364-4-43 §434.3.2 table 43A).

Comparison of the tripping or fusing performance curve of protective devices, with the limit curves of thermal constraint for a conductor shows that this condition is satisfied if:

  • Isc (min) > Im (instantaneous or short timedelay circuit-breaker trip setting current level), (see Fig. G43)
  • Isc (min) > Ia for protection by fuses. The value of the current Ia corresponds to the crossing point of the fuse curve and the cable thermal withstand curve (see Fig. G44 and G45)
FigG43.jpg

Fig. G43: Protection by circuit-breaker

FigG44.jpg

Fig. G44: Protection by aM-type fuses

FigG45.jpg

Fig. G45: Protection by gG-type fuses

Practical method of calculating Lmax

In practice this means that the length of circuit downstream of the protective device must not exceed a calculated maximum length: [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}L_{max}=\frac{0.8\ U\ S_{ph} }{2 \rho I_{m} } }[/math]

The limiting effect of the impedance of long circuit conductors on the value of short-circuit currents must be checked and the length of a circuit must be restricted accordingly.

The method of calculating the maximum permitted length has already been demonstrated in TN- and IT- earthed schemes for single and double earth faults, respectively. Two cases are considered below:

1 - Calculation of Lmax for a 3-phase 3-wire circuit

The minimum short-circuit current will occur when two phase wires are short-circuited at the remote end of the circuit (see Fig. G46).

FigG46.jpg

Fig G46: Definition of L for a 3-phase 3-wire circuit

Using the “conventional method”, the voltage at the point of protection P is assumed to be 80% of the nominal voltage during a short-circuit fault, so that 0.8 U = Isc Zd, where:

  • Zd = impedance of the fault loop
  • Isc = short-circuit current (ph/ph)
  • U = phase-to-phase nominal voltage

For cables ≤ 120 mm2, reactance may be neglected, so that  [math]\displaystyle{ Zd=\rho \frac{2L}{Sph} }[/math] [1]

where:

  • ρ = resistivity of conductor material at the average temperature during a short-circuit,
  • Sph = c.s.a. of a phase conductor in mm2
  • L = length in metres

The condition for the cable protection is Im ≤ Isc with Im = magnetic trip current setting of the CB.

This leads to [math]\displaystyle{ Im \le \frac{0.8 U}{Zd} }[/math]  which gives [math]\displaystyle{ L \le \frac{0.8\ U\ S_{ph}}{2 \rho I_{m}} }[/math]

with U = 400 V
ρ = 0.023 Ω.mm2/m[2] (Cu)

therefore

[math]\displaystyle{ L_{max}=\frac {k\ S_{ph}}{I_{m}} }[/math]

with Lmax = maximum circuit length in metres

In general, the value of Im is given with +/- 20% tolerance, so Lmax should be calculated for Im+20% (worst case).

k factor values are provided in the following table, taking into account these 20%, and as a function of cross-section for Sph > 120 mm2 [1]

Cross-section (mm2) ≤ 120 150 185 240 300
k (for 400 V) 5800 5040 4830 4640 4460

2 - Calculation of Lmax for a 3-phase 4-wire 230/400 V circuit

The minimum Isc will occur when the short-circuit is between a phase conductor and the neutral at the end of the circuit.

A calculation similar to that of example 1 above is required, but for a single-phase fault (230V).

  • If Sn (neutral cross-section) = Sph

Lmax = k Sph / Im with k calculated for 230V, as shown in the table below

Cross-section (mm2) ≤ 120 150 185 240 300
k (for 400 V) 3333 2898 2777 2668 2565
  • If Sn (neutral cross-section) < Sph, then (for cable cross-section ≤ 120mm2)

[math]\displaystyle{ L_{max}= 6666 \frac{Sph}{Im}\frac{1}{1+m} }[/math]  where [math]\displaystyle{ m=\frac{Sph}{Sn} }[/math]


Tabulated values for Lmax

Figure G47 below gives maximum circuit lengths (Lmax) in metres, for:

  • 3-phase 4-wire 400 V circuits (i.e. with neutral) and
  • 1-phase 2-wire 230 V circuits

protected by general-purpose circuit-breakers.

In other cases, apply correction factors (given in Figure G51) to the lengths obtained.

In general, the value of Im is given with +/- 20% tolerance.

Lmax values below are therefore calculated for Im+20% (worst case).

For the 50 mm2 c.s.a., calculation are based on a 47.5 mm2 real c.s.a.

Operating current level Im of the instantaneous magnetic tripping
element (in A)
c.s.a. (nominal cross-sectional-area) of conductors (in mm2)
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240
50 100 167 267 400
63 79 133 212 317
80 63 104 167 250 417
100 50 83 133 200 333
125 40 67 107 160 267 427
160 31 52 83 125 208 333
200 25 42 67 100 167 267 417
250 20 33 53 80 133 213 333 467
320 16 26 42 63 104 167 260 365 495
400 13 21 33 50 83 133 208 292 396
500 10 17 27 40 67 107 167 233 317
560 9 15 24 36 60 95 149 208 283 417
630 8 13 21 32 53 85 132 185 251 370
700 7 12 19 29 48 76 119 167 226 333 452
800 6 10 17 25 42 67 104 146 198 292 396
875 6 10 15 23 38 61 95 133 181 267 362 457
1000 5 8 13 20 33 53 83 117 158 233 317 400 435
1120 4 7 12 18 30 48 74 104 141 208 283 357 388 459
1250 4 7 11 16 27 43 67 93 127 187 253 320 348 411
1600 5 8 13 21 33 52 73 99 146 198 250 272 321 400
2000 4 7 10 17 27 42 58 79 117 158 200 217 257 320
2500 5 8 13 21 33 47 63 93 127 160 174 206 256
3200 4 6 10 17 26 36 49 73 99 125 136 161 200
4000 5 8 13 21 29 40 58 79 100 109 128 160
5000 4 7 11 17 23 32 47 63 80 87 103 128
6300 5 8 13 19 25 37 50 63 69 82 102
8000 4 7 10 15 20 29 40 50 54 64 80
10000 5 8 12 16 23 32 40 43 51 64
12500 4 7 9 13 19 25 32 35 41 51

Fig. G47: Maximum circuit lengths in metres for copper conductors (for aluminium, the lengths must be multiplied by 0.62)

Figures G48 to G50 give maximum circuit length (Lmax) in metres for:

  • 3-phase 4-wire 400 V circuits (i.e. with neutral) and
  • 1-phase 2-wire 230 V circuits

protected in both cases by domestic-type circuit-breakers or with circuit-breakers having similar tripping/current characteristics. In other cases, apply correction factors to the lengths indicated. These factors are given in Figure G51.

Circuit-breaker rating (A) c.s.a. (nominal cross-sectional-area) of conductors (in mm2)
1.5 2.5 4 6 10 16 25 35 50
6 200 333 533 800
10 120 200 320 480 800
16 75 125 200 300 500 800
20 60 100 160 240 400 640
25 48 80 128 192 320 512 800
32 37 62 100 150 250 400 625 875
40 30 50 80 120 200 320 500 700
50 24 40 64 96 160 256 400 560 760
63 19 32 51 76 127 203 317 444 603
80 15 25 40 60 100 160 250 350 475
100 12 20 32 48 80 128 200 280 380
125 10 16 26 38 64 102 160 224 304

Fig. G48: Maximum length of copper-conductor circuits in metres protected by B-type circuit-breakers

Circuit-breaker rating (A)
c.s.a. (nominal cross-sectional-area) of conductors (in mm2)
1.5 2.5 4 6 10 16 25 35 50
6 100 167 267 400 667
10 60 100 160 240 400 640
16 37 62 100 150 250 400 625 875
20 30 50 80 120 200 320 500 700
25 24 40 64 96 160 256 400 560 760
32 18.0 31 50 75 125 200 313 438 594
40 15.0 25 40 60 100 160 250 350 475
50 12.0 20 32 48 80 128 200 280 380
63 9.5 16.0 26 38 64 102 159 222 302
80 7.5 12.5 20 30 50 80 125 175 238
100 6.0 10.0 16.0 24 40 64 100 140 190
125 5.0 8.0 13.0 19.0 32 51 80 112 152

Fig. G49: Maximum length of copper-conductor circuits in metres protected by C-type circuit-breakers

Circuit-breaker rating (A)
c.s.a. (nominal cross-sectional-area) of conductors (in mm2)
1.5 2.5 4 6 10 16 25 35 50
1 429 714
2 214 357 571 857
3 143 238 381 571 952
4 107 179 286 429 714
6 71 119 190 286 476 762
10 43 71 114 171 286 457 714
16 27 45 71 107 179 286 446 625 848
20 21 36 57 86 143 229 357 500 679
25 17.0 29 46 69 114 183 286 400 543
32 13.0 22 36 54 89 143 223 313 424
40 11.0 18.0 29 43 71 114 179 250 339
50 9.0 14.0 23 34 57 91 143 200 271
63 7.0 11.0 18.0 27 45 73 113 159 215
80 5.0 9.0 14.0 21 36 57 89 125 170
100 4.0 7.0 11.0 17.0 29 46 71 100 136
125 3.0 6.0 9.0 14.0 23 37 57 80 109

Fig. G50: Maximum length of copper-conductor circuits in metres protected by D-type circuit-breakers

Circuit detail
3-phase 3-wire 400 V circuit or 1-phase 2-wire 400 V circuit (no neutral) 1.73
1-phase 2-wire (phase and neutral) 230 V circuit 1
3-phase 4-wire 230/400 V circuit or 2-phase 3-wire 230/400 V circuit (i.e with neutral) Sph / S neutral = 1 1
Sph / S neutral = 2 0.67

Fig. G51: Correction factor to apply to lengths obtained from Figures G47 to G50

Note: IEC 60898 accepts an upper short-circuit-current tripping range of 10-50 In for type D circuit-breakers. European standards, and Figure G50 however, are based on a range of 10-20 In, a range which covers the vast majority of domestic and similar installations.

Examples

Example 1

In a 3-phase 3-wire 400 V installation the protection is provided by a 50 A circuit-breaker type NS80HMA, the instantaneous short-circuit current trip, is set at 500 A (accuracy of ± 20%), i.e. in the worst case would require 500 x 1,2 = 600 A to trip. The cable c.s.a. = 10 mm2 and the conductor material is copper.
In Figure G47, the row Im = 500 A crosses the column c.s.a. = 10 mm2 at the value for Lmax of 67 m. The circuit-breaker protects the cable against short-circuit faults, therefore, provided that its length does not exceed 67 metres.
Example 2
In a 3-phase 3-wire 400 V circuit (without neutral), the protection is provided by a 220 A circuit-breaker type NSX250N with an instantaneous short-circuit current trip unit type MA set at 2,000 A (± 20%), i.e. a worst case of 2,400 A to be certain of tripping. The cable c.s.a. = 120 mm2 and the conductor material is copper.
In Figure G47 the row Im = 2,000 A crosses the column c.s.a. = 120 mm2 at the value for Lmax of 200 m. Being a 3-phase 3-wire 400 V circuit (without neutral), a correction factor from Figure G51 must be applied. This factor is seen to be 1.73.
The circuit-breaker will therefore protect the cable against short-circuit current, provided that its length does not exceed 200 x 1.73= 346 metres.


References

  1. ^ 1 2 For larger c.s.a.’s, the resistance calculated for the conductors must be increased to account for the non-uniform current density in the conductor (due to “skin” and “proximity” effects)
    Suitable values are as follows:
    150 mm2: R + 15 %
    185 mm2: R + 20 %
    240 mm2: R + 25 %
    300 mm2: R + 30 %
  2. ^ Resistivity for copper EPR/XLPE cables when passing short-circuit current, eg for the max temperature they can withstand = 90°C (cf Figure G35b).

ru:Расчет минимальных величин тока короткого замыкания zh:最小短路电流的计算

Share