Protection against electrical fire risks - synthesis

From Electrical Installation Guide
Revision as of 03:35, 18 April 2018 by LMischler (talk | contribs) (update_2018)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Home > Protection against electric shocks and electrical fires > Protection against electrical fire risks > Protection against electrical fire risks - synthesis


Conclusion

In addition to protection against electric shock, protection against fire is another main target of a proper design of electrical installation. The minimum requirement is the coordination between overcurrent protective device and conductor permanent and short-time withstand. (See Chapter Sizing and protection of conductors ). But other protective measures are recommended to reduce the risk of fire due to electrical installation.

  • For main circuits and distribution circuits, more sensitive earth fault detection than the one necessary for protection against electric shock is recommended.
  • For terminal circuits where mechanical withstand of conductor is lower, where the number of connection is higher, where portable equipment can be supplied, in addition to RCD, Arc fault detection device is recommended.

The table below tries to position the different types of current-based protections required or recommended for low voltage installations.

Protection against electric shock Protection against thermal effect / Fire Protection against overcurrent

(IEC 60364-4-43)

BE2 location[a] Other location
Earthing system Basic protection Automatic disconnection Additional protection Terminal Circuit Distribution Circuit
TNC Insulation of live part / Barriers enclosure OCPD NA NA NA RS GFP[c] OCPD (overload and short-circuit)
TNS OCPD/RCD RCD 30mA 300mA RCD
AFDD
AFDD[b] RCD[b]
TT RCD RCD 30mA AFDD[b] RCD[b]
IT OCPD/RCD RCD 30mA AFDD[b] RCD[b]