Requirements applicable to special installations and locations
Figure Q20 below summarizes the main requirements prescribed in many national and international standards.
Note: Section in brackets refer to sections of IEC 60364-7 (example: "section 701" means IEC60364-7-701)
Locations | Protection principles | IP level | Wiring and cables | Switchgear | Socket-outlets | Installation materials |
---|---|---|---|---|---|---|
Domestic dwellings and other habitations |
|
20 | Switch operating handles and similar devices on distribution panels, to be mounted between 1 metre and 1.80 metre above the floor | Protection by 30 mA RCDs | ||
Bathrooms or shower rooms (section 701) | Supplementary equipotential bonding in zones 0, 1, 2 and 3 | |||||
Zone 0 | SELV 12 V only | 27 | Class II limited to strict minimum | Special appliances | ||
Zone 1 | SELV 12 V | 25 | Class II limited to strict minimum | Special appliances
Water heater | ||
Zone 2 | SELV 12 V or 30 mA RCD | 24 | Class II limited to strict minimum | Special appliances
Water heater | ||
Zone 3 | 21 | Only socket-outlets protected by:
|
||||
Swimming baths
(section 702) |
Supplementary equipotential bonding in zones 0, 1, and 2 | |||||
Zone 0 | SELV 12 V | 28 | Class II
limited to strict minimum |
Special appliances | ||
Zone 1 | 25 | Class II
limited to strict minimum |
Special appliances | |||
Zone 2 | 22(indoor)
24(outdoor) |
Only socket-outlets protected by:
|
||||
Saunas
(section 703) |
24 | Class II | Adapted to temperature | |||
Work sites
(section 704) |
Conventional voltage limit UL reduced to 25 V | 44 | Mechanically protected | Protection by 30 mA RCDs | ||
Agricultural and horticultural establishments
(section 705) |
Conventional voltage limit UL reduced to 25 V
Protection against fire risks by 500 mA RCDs |
35 | Protection by 30 mA RCDs | |||
Restricted
conductive |
2x | Protection of
| ||||
Fountains
(section 702) |
Protection by 30 mA RCDs and equipotential bonding of all exposed and extraneous conductive parts | |||||
Caravan park
(section 708) |
55 | Flexible cable of 25 metres length | Socket-outlets shall be placed at a height of 0.80 m to 1.50 m from the ground.
Protection of circuits by 30 mA RCDs (one per 6 socket-outlets) |
|||
Marinas and pleasure craft
(section 709) |
The cable length for connection to pleasure craft must not exceeded 25 m | Protection of circuits by 30 mA RCDs (one per 6 socket-outlets) | ||||
Medical locations
Group 2: Operating theatres and similar |
IT medical system equipotential grouding, limited to one operating theatre and not exceeding 10 kVA | Only magnetic protection for the primary of LV/LV transformer. Monitoring of secondary loads and transformer temperature | Protection of circuits by thermal-magnetic protection only. One to three per circuit. | |||
Medical locations
Group 1: Hospitalization and similar |
TT or TNS | Protection by
30 mA RCDs |
||||
Exhibitions, shows and stands
(section 711) |
TT or TN-S systems | 4x | Protection by 30 mA RCDs | |||
Balneotherapy (cure-centre baths) | Individual: see section 701 (volumes 0 and 1)
Collective: see section 702 (volumes 0 and 1) |
|||||
Motor-fuel filling stations | Explosion risks in security zones | Limited to the necessary minimum | ||||
Motor vehicules | Protection by RCDs or by electrical separation | |||||
External lighting installations
(section 714) |
23 | Protection by
30 mA RCDs |
||||
Mobile or transportable units
(section 717) |
The use of TN-C system is not permitted inside any unit | 30 mA RCDs must be used for all socket-outlets supplying equipment outside the unit |