Requirements applicable to special installations and locations
From Electrical Installation Guide
Figure Q20 below summarizes the main requirements prescribed in many national and international standards.
Note: Section in brackets refer to sections of IEC 60364-7
Locations | Protection principles |
IP level |
Wiring and cables |
Switchgear | Socket-outlets | Installation materials |
Domestic dwellings and other habitations |
- 300 mA if the earth electrode resistance is y 80 ohms instantaneous or short time delay (type S) - 30 mA if the earth electrode resistance is u 500 ohms
- supply is from overhead line with bare conductors, and if
|
20 | Switch operating handles and similar devices on distribution panels, to be mounted between 1 metre and 1.80 metre above the floor |
Protection by 30 mA RCDs |
||
Bathrooms or shower rooms (section 701) | Supplementary equipotential bonding in zones 0, 1, 2 and 3 | |||||
Zone 0 | SELV 12 V only | 27 | Class II limited to strict minimum | Special appliances | ||
Zone 1 | SELV 12 V | 25 | Class II limited to strict minimum | Special appliances Water heater | ||
Zone 2 | SELV 12 V or 30 mA RCD | 24 | Class II limited to strict minimum | Special appliances Water heater Class II luminaires | ||
Zone 3 | 21 | |||||