Protection provided for enclosed equipment: codes IP and IK

From Electrical Installation Guide

Home > LV Distribution > External influences (IEC 60364-5-51) > Protection provided for enclosed equipment: codes IP and IK

Protection provided for enclosed equipment: codes IP and IK

IP code definition

(see Fig. E47)
The degree of protection provided by an enclosure is indicated in the IP code, recommended in IEC 60529.
Protection is afforded against the following external influences:

  • Penetration by solid bodies
  • Protection of persons against access to live parts
  • Protection against the ingress of dust
  • Protection against the ingress of liquids

Note: the IP code applies to electrical equipment for voltages up to and including 72.5 kV.



FigE47.jpg




















Fig. E47: IP Code arrangement


Elements of the IP Code and their meanings

A brief description of the IP Code elements is given in the following chart (see Fig. E48).



FigE48.jpg






























Fig. E48: Elements of the IP Code


IK Code definition

Standard IEC 62262 defines an IK code that characterises the aptitude of equipment to resist mechanical impacts on all sides (see Fig. E49).



IK code Impact energy (In joules) AG Code
00 0  
01 ≤ 0.14  
02 ≤ 0.20 AG1
03 ≤ 0.35  
04 ≤ 0.50  
05 ≤ 0.70  
06 ≤ 1  
07 ≤ 2 AG2
08 ≤ 5 AG3
09 ≤ 10  
10 ≤ 20 AG4

Fig. E49: Elements of the IK Code


IP and IK code specifications for distribution switchboards

The degrees of protection IP and IK of an enclosure must be specified as a function of the different external influences defined by standard IEC 60364-5-51, in particular:

  • Presence of solid bodies (code AE)
  • Presence of water (code AD)
  • Mechanical stresses (no code)
  • Capability of persons (code BA)

Prisma Plus switchboards are designed for indoor installation.
Unless the rules, standards and regulations of a specific country stipulate otherwise, Schneider Electric recommends the following IP and IK values (see Fig. E50 and Fig. E51 )

IP recommendations



IP codes according to conditions
Normal without risk of vertically falling water Technical rooms 30
Normal with risk of vertically falling water Hallways 31
Very severe with risk of splashing water from all directions Workshops 54/55

Fig. E50: IP recommendations


IK recommendations



IK codes according to conditions
No risk of major impact Technical rooms 07
Significant risk of major impact that could damage devices Hallways 08 (enclosure with door) 
Maximum risk of impact that could damage the enclosure Workshops 10

Fig. E51: IK recommendations