Transformer-energizing inrush current

From Electrical Installation Guide
Revision as of 09:57, 4 February 2011 by Wikiadmin (talk | contribs) (Created page with '{{Menu_Characteristics_of_particular_sources_and_loads}} <br> __TOC__ At the moment of energizing a transformer, high values of transient current (which includes a significant D…')
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)


At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N31).



FigN31.jpg















Fig N31: Transformer-energizing inrush current


The magnitude of the current peak depends on:

  • The value of voltage at the instant of energization
  • The magnitude and polarity of the residual flux existing in the core of the transformer
  • Characteristics of the load connected to the transformer

The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.