Connection to the utility network: Difference between revisions

From Electrical Installation Guide
(Created page with '{{Menu_MV_&_LV_architecture_selection_guide}} <br> The main configurations for possible connection are as follows (see '''Fig. D8 '''for MV service): *LV service, *MV single-l…')
 
m (Review Format)
Line 13: Line 13:
----
----


<br>[[Image:FigD08.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. D8:'''&nbsp;MV connection to the utilities network''  
<br>[[Image:FigD08.jpg|left|500px]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. D8:'''&nbsp;MV connection to the utilities network''  


----
----
Line 23: Line 23:
<br>
<br>


{| style="width: 827px; height: 187px" cellspacing="1" cellpadding="1" width="827" border="1"
{| style="width: 65%; height: 187px" cellspacing="1" cellpadding="1" border="1"
|-
|-
| &nbsp;  
| &nbsp;  

Revision as of 09:29, 17 August 2012


The main configurations for possible connection are as follows (see Fig. D8 for MV service):

  • LV service,
  • MV single-line service,
  • MV ring-main service,
  • MV duplicate supply service,
  • MV duplicate supply service with double busbar.

Metering, protection, disconnection devices, located in the delivery substations are not represented on the following diagrams. They are often specific to each utilities company and do not have an influence on the choice of installation architecture.
For each connection, one single transformer is shown for simplification purposes, but in the practice, several transformers can be connected.(MLVS: Main Low Voltage Switchboard)



FigD08.jpg



































Fig. D8: MV connection to the utilities network


For the different possible configurations, the most probable and usual set of characteristics is given in the following table:



  Configuration
  LV MV
Characteristic to
consider
Simple-line Ring-main Duplicate supply Duplicate supply
with double
busbars
Activity Any Any Any Hi-tech, sensitive
office, health-care
Any
Site topology Single building Single building Single building Single building Several buildings
Service reliability Minimal Minimal Standard Enhanced Enhanced
Power demand < 630kVA ≤ 1250kVA ≤ 2500kVA > 2500kVA > 2500kVA
Other connection constraints Any Isolated site Low density urban area High density urban area Urban area with utility constraint




Share