Possible solutions for power-system harmonics: Difference between revisions

From Electrical Installation Guide
Home > Power Factor Correction > The effects of harmonics > Possible solutions for power-system harmonics
(updated according to guide 2013)
Line 1: Line 1:
{{Menu_Power_factor_correction_and_harmonic_filtering}}
{{Menu_Power_Factor_Correction}}  
__TOC__


{| style="width: 793px; height: 14px" cellspacing="1" cellpadding="1" width="793" border="1"
__TOC__
|-
 
| bgcolor="#0099cc" | Harmonics are taken into account mainly by oversizing capacitors and including harmonic-suppression reactors in series with them
== Standard capacitors  ==
|}
 
The presence of harmonics in the supply voltage results in abnormally high current levels through the capacitors. An allowance is made for this by designing capacitors for an r.m.s. value of current equal to 1.3 times the nominal rated current. All series elements, such as connections, fuses, switches, etc., associated with the capacitors are similarly oversized, between 1.3 to 1.5 times the nominal ratings.
 
Standard capacitors can be used if the percentage of non-linear loads is lower than 10% (N<sub>LL</sub> ≤ 10%).
 
 
== Capacitors with increased current rating  ==
 
Capacitors with improved current capability ("heavy duty") can be used in order to increase the safety margin. The technology of these capacitors allows a higher overcurrent compared to what is strictly requested by the standards.
 
Another possibility is to use capacitors with increased rated current and voltage.
 
As the same reactive power must be generated, the capacitors must have the same capacitance.
 
With a rated voltage U<sub>N</sub> (higher than the system voltage U), the rated current I<sub>N</sub> and the rated power
 
Q<sub>N</sub> will be given by the formulas:
 
<math>\frac{I_N}{I}=\frac{U_N}{U}</math> and <math>\frac{Q_N}{Q}= \left ( \frac{U_N}{U} \right )^2</math>
 
Capacitors with improved current rating can be used if the percentage of non-linear loads is lower than 20% (N<sub>LL</sub> ≤ 20%).
 
 
== Connection of Power Factor Correction capacitors with detuned reactors  ==
 
In order to attenuate the effects of harmonics (significant increase of capacitor current as well as high current and voltage distortion ), reactors should be associated to capacitors. Reactors and capacitors are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system.
 
The use of detuned reactors thus prevents harmonic resonance problems, avoids the risk of overloading the capacitors and helps reduce voltage harmonic distortion in the network.


===== Passive filter  =====


(see '''Fig. L28''')<br>'''Countering the effects of harmonics<br>'''The presence of harmonics in the supply voltage results in abnormally high current levels through the capacitors. An allowance is made for this by designing for an r.m.s. value of current equal to 1.3 times the nominal rated current. All series elements, such as connections, fuses, switches, etc., associated with the capacitors are similarly oversized, between 1.3 to 1.5 times nominal rating.<br>Harmonic distortion of the voltage wave frequently produces a “peaky” wave form, in which the peak value of the normal sinusoidal wave is increased. This possibility, together with other overvoltage conditions likely to occur when countering the effects of resonance, as described below, are taken into account by increasing the insulation level above that of “standard” capacitors. In many instances, these two counter measures are all that is necessary to achieve satisfactory operation.  
[[Image:Fig_L30.jpg|none]]


----


<br>[[Image:FigL28.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. L28:''' Operation principle of passive filter''  
'''''Fig. L30 :''''' ''Simplified circuit diagram''


----


'''Countering the effects of resonance<br>'''Capacitors are linear reactive devices, and consequently do not generate harmonics. The installation of capacitors in a power system (in which the impedances are predominantly inductive) can, however, result in total or partial resonance occurring at one of the harmonic frequencies.<br>The harmonic order ho of the natural resonant frequency between the system inductance and the capacitor bank is given by <br><math>h_o=\sqrt{\frac{Ssc}{Q}}</math><br>where<br>Ssc = the level of system short-circuit kVA at the point of connection of the capacitor<br>Q = capacitor bank rating in kvar; and ho = the harmonic order of the natural frequency f<sub>o</sub> i.e.<br><math>\frac{f_o}{50}</math>&nbsp; for a 50 Hz system, or&nbsp;&nbsp;<math>\frac{f_o}{60}</math>&nbsp;&nbsp; for a 60 Hz system.<br><br>For example:&nbsp;<math>h_o=\sqrt{\frac{Ssc}{Q}}</math>&nbsp; may give a value for h<sub>o</sub>of 2.93 which shows that the natural frequency of the capacitor/system-inductance combination is close to the 3<sup>rd</sup> harmonic frequency of the system. From <math>h_o=\frac{f_o}{50}</math>&nbsp; it can be seen that f<sub>o</sub> = 50 h<sub>o</sub> = 50 x 2.93 = 146.5 Hz
The tuning frequency can be expressed by the relative impedance of the reactor (in&nbsp;%, relative to the capacitor impedance), or by the tuning order, or directly in Hz.  


The closer a natural frequency approaches one of the harmonics present on the system, the greater will be the (undesirable) effect. In the above example, strong resonant conditions with the 3rd harmonic component of a distorted wave would certainly occur.  
The most common values of relative impedance are 5.7, 7 and 14&nbsp;% (14&nbsp;% is used with high level of 3rd harmonic voltages).  


In such cases, steps are taken to change the natural frequency to a value which will not resonate with any of the harmonics known to be present. This is achieved by the addition of a harmonic-suppression inductor connected in series with the capacitor bank.  
{| style="width: 769px; height: 107px" border="1" cellspacing="1" cellpadding="1" width="769"
|-
| bgcolor="#0099cc" | '''Relative impedance(%)'''
| bgcolor="#0099cc" | '''Tuning order'''
| bgcolor="#0099cc" | '''Tuning frequency @50Hz (Hz)'''
| bgcolor="#0099cc" | '''Tuning frequency @60Hz (Hz)'''
|-
| 5.7
| 4.2
| 210
| 250
|-
| 7
| 3.8
| 190
| 230
|-
| 14
| 2.7
| 135
| 160
|}


On 50 Hz systems, these reactors are often adjusted to bring the resonant frequency of the combination, i.e. the capacitor bank + reactors to 190 Hz. The reactors are adjusted to 228 Hz for a 60 Hz system. These frequencies correspond to a value for h<sub>o</sub> of 3.8 for a 50 Hz system, i.e. approximately mid-way between the 3<sup>rd</sup> and 5<sup>th </sup>harmonics.
'''''Fig. L31&nbsp;:''''' ''Correspondance between relative impedance, tuning order and tuning frequency''


In this arrangement, the presence of the reactor increases the fundamental frequency (50 Hz or 60 Hz) current by a small amount (7-8%) and therefore the voltage across the capacitor in the same proportion.<br>This feature is taken into account, for example, by using capacitors which are designed for 440 V operation on 400 V systems.<br>
In this arrangement, the presence of the reactor increases the fundamental frequency voltage (50 or 60Hz) across the capacitor.  


===== Active filter  =====
This feature is taken into account by using capacitors which are designed with a rated voltage U<sub>N</sub> higher than the network service voltage U<sub>S</sub>, as shown on the following table.


(see '''Fig. L29''')  
{| style="width: 756px; height: 135px" border="1" cellspacing="1" cellpadding="1" width="756"
|-
| colspan="2" rowspan="3"|'''Capacitor Rated Voltage U<sub>N</sub> (V) '''
| colspan="5"|'''Network Service Voltage U<sub>S </sub>(V)'''
|-
| colspan="2"|'''50 Hz'''
| colspan="3"|'''60 Hz'''
|-
| '''400'''
| '''690'''  
| '''400'''
| '''480'''
| '''600'''
|-
| bgcolor="#0099cc" rowspan="3"|Relative Impedance (%)  
| bgcolor="#0099cc" |5.7
| 480
| 830
| 480
| 575
| 690
|-
| bgcolor="#0099cc" |7
| &nbsp;
| &nbsp;
| &nbsp;
| &nbsp;
| &nbsp;
|-
| bgcolor="#0099cc" |14
| 480
|  &nbsp;
| 480
|  &nbsp;
| &nbsp;
|}


Active filters are based on power electronic technology. They are generally installed in parallel with the non linear load.  
'''''Fig. L32 :''''' ''Typical values of capacitor rated voltage''


Active filters analyse the harmonics drawn by the load and then inject the same harmonic current to the load with the appropriate phase. As a result, the harmonic currents are totally neutralised at the point considered. This means they no longer flow upstream and are no longer supplied by the source.<br>A main advantage of active conditioners is that they continue to guarantee efficient harmonic compensation even when changes are made to the installation. They are also exceptionally easy to use as they feature:
Summary


*Auto-configuration to harmonic loads whatever their order of magnitude
Practical rules are given in the following table, for selection of the suitable configuration, depending on the system parameters:
*Elimination of overload risks
*Compatibility with electrical generator sets
*Connection to any point of the electrical network
*Several conditioners can be used in the same installation to increase depollution efficiency (for example when a new machine is installed)


Active filters may provide also power factor correction.  
*S<sub>SC</sub> = 3-phase short-circuit power in kVA at the busbar level
*S<sub>n</sub> = sum of the kVA ratings of all transformers supplying (i.e. directly connected to)the busbar
*G<sub>h</sub> = sum of the kVA ratings of all harmonic-generating devices (static converters,inverters, variable speed drives, etc.) connected to the busbar. If the ratings of some of these devices are quoted in kW only, assume an average power factor of 0.7 to obtain the kVA ratings


----
General rule (for any size of transformer):


<br>[[Image:FigL29.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. L29:''' Operation principle of active filter''
{| style="width: 769px; height: 100px" border="1" cellspacing="1" cellpadding="1" width="769"
|-
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}G_h\le \frac{S_{sc}}{120}</math>  
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}\frac{S_{sc}}{120} < G_h\le \frac{S_{sc}}{70}</math>
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}\frac{S_{sc}}{70} < G_h\le \frac{S_{sc}}{30}</math>
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}G_h{{>}}\frac{S_{sc}}{70}</math>
|-
| valign="top" | Standard capacitors
| valign="top" | Heavy Duty capacitors or capacitors with voltage rating increased by 10%
| valign="top" | Heavy Duty capacitors or capacitors with voltage rating increased by 20% + detuned reactor
| valign="top" | Harmonic filtering necessary See chapter [[Harmonic management|Harmonic management]]
|}


----


===== Hybrid filter  =====
Simplified rule (if transformer rating ≤ 2MVA):


(see '''Fig. L30''')<br>This type of filter combines advantages of passive and active filter. One frequency can be filtered by passive filter and all the other frequencies are filtered by active filter.
{| style="width: 769px; height: 100px" border="1" cellspacing="1" cellpadding="1" width="769"
|-
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} G_h \le 0.1 \times S_n </math>
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} 0.1 \times S_n < G_h \le 0.2 \times S_n </math>
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} 0.2 \times S_n < G_h \le 0.5 \times S_n </math>
| bgcolor="#0099cc" | <math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}G_h> 0.60S_n</math>
|-
| valign="top" | Standard capacitors
| valign="top" | Heavy Duty capacitors or capacitors with voltage rating increased by 10%
| valign="top" | Heavy Duty capacitors or capacitors with voltage rating increased by 20% + detuned reactor
| valign="top" | Harmonic filtering necessary See chapter [[Harmonic management|Harmonic management]]
|}


----
'''''Fig. L33:''''' ''Simplified rules''


<br>[[Image:FigL30.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>


'''''Fig. L30:''' Operation principle of hybrid filter''


----
[[Zh:电力系统谐波可能的解决方案]]


[[ru:Возможные решения, связанные с гармоническими составляющими напряжения]]
[[ru:Возможные решения, связанные с гармоническими составляющими напряжения|ru:Возможные решения, связанные с гармоническими составляющими напряжения]]
[[zh:电力系统谐波可能的解决方案]]

Revision as of 17:24, 23 August 2013


Standard capacitors

The presence of harmonics in the supply voltage results in abnormally high current levels through the capacitors. An allowance is made for this by designing capacitors for an r.m.s. value of current equal to 1.3 times the nominal rated current. All series elements, such as connections, fuses, switches, etc., associated with the capacitors are similarly oversized, between 1.3 to 1.5 times the nominal ratings.

Standard capacitors can be used if the percentage of non-linear loads is lower than 10% (NLL ≤ 10%).


Capacitors with increased current rating

Capacitors with improved current capability ("heavy duty") can be used in order to increase the safety margin. The technology of these capacitors allows a higher overcurrent compared to what is strictly requested by the standards.

Another possibility is to use capacitors with increased rated current and voltage.

As the same reactive power must be generated, the capacitors must have the same capacitance.

With a rated voltage UN (higher than the system voltage U), the rated current IN and the rated power

QN will be given by the formulas:

[math]\displaystyle{ \frac{I_N}{I}=\frac{U_N}{U} }[/math] and [math]\displaystyle{ \frac{Q_N}{Q}= \left ( \frac{U_N}{U} \right )^2 }[/math]

Capacitors with improved current rating can be used if the percentage of non-linear loads is lower than 20% (NLL ≤ 20%).


Connection of Power Factor Correction capacitors with detuned reactors

In order to attenuate the effects of harmonics (significant increase of capacitor current as well as high current and voltage distortion ), reactors should be associated to capacitors. Reactors and capacitors are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system.

The use of detuned reactors thus prevents harmonic resonance problems, avoids the risk of overloading the capacitors and helps reduce voltage harmonic distortion in the network.


Fig L30.jpg


Fig. L30 : Simplified circuit diagram


The tuning frequency can be expressed by the relative impedance of the reactor (in %, relative to the capacitor impedance), or by the tuning order, or directly in Hz.

The most common values of relative impedance are 5.7, 7 and 14 % (14 % is used with high level of 3rd harmonic voltages).

Relative impedance(%) Tuning order Tuning frequency @50Hz (Hz) Tuning frequency @60Hz (Hz)
5.7 4.2 210 250
7 3.8 190 230
14 2.7 135 160

Fig. L31 : Correspondance between relative impedance, tuning order and tuning frequency

In this arrangement, the presence of the reactor increases the fundamental frequency voltage (50 or 60Hz) across the capacitor.

This feature is taken into account by using capacitors which are designed with a rated voltage UN higher than the network service voltage US, as shown on the following table.

Capacitor Rated Voltage UN (V) Network Service Voltage US (V)
50 Hz 60 Hz
400 690 400 480 600
Relative Impedance (%) 5.7 480 830 480 575 690
7          
14 480   480    

Fig. L32 : Typical values of capacitor rated voltage

Summary

Practical rules are given in the following table, for selection of the suitable configuration, depending on the system parameters:

  • SSC = 3-phase short-circuit power in kVA at the busbar level
  • Sn = sum of the kVA ratings of all transformers supplying (i.e. directly connected to)the busbar
  • Gh = sum of the kVA ratings of all harmonic-generating devices (static converters,inverters, variable speed drives, etc.) connected to the busbar. If the ratings of some of these devices are quoted in kW only, assume an average power factor of 0.7 to obtain the kVA ratings

General rule (for any size of transformer):

[math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}G_h\le \frac{S_{sc}}{120} }[/math] [math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}\frac{S_{sc}}{120} \lt G_h\le \frac{S_{sc}}{70} }[/math] [math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}\frac{S_{sc}}{70} \lt G_h\le \frac{S_{sc}}{30} }[/math] [math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}G_h{{\gt }}\frac{S_{sc}}{70} }[/math]
Standard capacitors Heavy Duty capacitors or capacitors with voltage rating increased by 10% Heavy Duty capacitors or capacitors with voltage rating increased by 20% + detuned reactor Harmonic filtering necessary See chapter Harmonic management


Simplified rule (if transformer rating ≤ 2MVA):

[math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} G_h \le 0.1 \times S_n }[/math] [math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} 0.1 \times S_n \lt G_h \le 0.2 \times S_n }[/math] [math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} 0.2 \times S_n \lt G_h \le 0.5 \times S_n }[/math] [math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue}G_h\gt 0.60S_n }[/math]
Standard capacitors Heavy Duty capacitors or capacitors with voltage rating increased by 10% Heavy Duty capacitors or capacitors with voltage rating increased by 20% + detuned reactor Harmonic filtering necessary See chapter Harmonic management

Fig. L33: Simplified rules


Zh:电力系统谐波可能的解决方案

ru:Возможные решения, связанные с гармоническими составляющими напряжения

Share