Inductive coupling: Difference between revisions
From Electrical Installation Guide
m (r2.7.2) (robot Adding: zh:电感耦合) |
(updated according to guide 2013) |
||
Line 1: | Line 1: | ||
{{Menu_EMC_guidelines}} | {{Menu_EMC_guidelines}} | ||
__TOC__ | __TOC__ | ||
== Definition == | == Definition == | ||
Line 12: | Line 13: | ||
== Examples == | == Examples == | ||
(see '''Fig. | (see '''Fig. R38''') | ||
*Nearby cables subjected to rapid current variations (di/dt) | *Nearby cables subjected to rapid current variations (di/dt) | ||
Line 22: | Line 23: | ||
*Inductors | *Inductors | ||
<br>[[Image:Fig_R28.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br> | <br>[[Image:Fig_R28.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br> | ||
'''''Fig. | '''''Fig. R38:''' Example of inductive coupling'' | ||
== Counter-measures == | == Counter-measures == | ||
Line 39: | Line 38: | ||
*Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable) | *Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable) | ||
[[ru:Индуктивная связь]] | [[ru:Индуктивная связь]] | ||
[[zh:电感耦合]] | [[zh:电感耦合]] |
Revision as of 14:29, 19 October 2013
Definition
The disturber and the victim are coupled by a magnetic field. The level of disturbance depends on the current variations (di/dt) and the mutual coupling inductance.
Inductive coupling increases with:
- The frequency
- The proximity of the disturber to the victim and the length of the parallel cables,
- The height of the cables with respect to a ground referencing plane,
- The load impedance of the disturbing circuit.
Examples
(see Fig. R38)
- Nearby cables subjected to rapid current variations (di/dt)
- Short-circuits
- Fault currents
- Lightning strikes
- Stator control systems
- Welding machines
- Inductors
Fig. R38: Example of inductive coupling
Counter-measures
- Limit the length of parallel runs of disturbers and victims to the strict minimum
- Increase the distance between the disturber and the victim
- For two-wire connections, run the two wires as close together as possible
- Use multi-core or touching single-core cables, preferably in a triangular layout
- Position a PEC bonded at both ends and between the disturber and the victim
- Use symmetrical transmission systems on correctly implemented, symmetrical wiring systems
- Shield the disturbing cables, the victim cables or both (the shielding must be bonded)
- Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable)