Bathroom electrical installation: Difference between revisions

From Electrical Installation Guide
Home > Residential premises and other special locations > Bathroom electrical installation
m (r2.7.2) (robot Adding: zh:浴室电气安装)
m (cleaned up source: table format, etc ...)
Line 8: Line 8:
*The strict adherence to the requirements prescribed for each particular zones.
*The strict adherence to the requirements prescribed for each particular zones.


==== <br>Classification of zones  ====
 
==== Classification of zones  ====


Sub-clause 701.32 of IEC 60364-7-701 defines the zones 0, 1, 2, 3 as shown in the following diagrams (see '''Fig. Q12 '''below&nbsp;to'''&nbsp;Fig. Q18''')  
Sub-clause 701.32 of IEC 60364-7-701 defines the zones 0, 1, 2, 3 as shown in the following diagrams (see '''Fig. Q12 '''below&nbsp;to'''&nbsp;Fig. Q18''')  
Line 14: Line 15:
----
----


<br>[[Image:FigQn12.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. Q12:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity to a bath-tub</i>  
[[File:FigQn12.jpg|none]]
'''''Fig. Q12:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity to a bath-tub</i>  


----
----


<br>[[Image:FigQn13.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. Q13:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity of a shower with basin</i>  
[[File:FigQn13.jpg|none]]
'''''Fig. Q13:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity of a shower with basin</i>  


----
----


<br>[[Image:FigQn14.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. Q14:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity of a shower without basin</i>  
[[File:FigQn14.jpg|none]]
'''''Fig. Q14:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity of a shower without basin</i>  


----
----


<br>[[Image:FigQn15.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. Q15:'''''<i>&nbsp;No switch or socket-outlet is permitted within 60 cm of the door opening of a shower cabinet</i>  
[[File:FigQn15.jpg|none]]
'''''Fig. Q15:'''''<i>&nbsp;No switch or socket-outlet is permitted within 60 cm of the door opening of a shower cabinet</i>  


----
----


<br>[[Image:FigQn16.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. QP16:'''''<i>&nbsp;Individual showers with dressing cubicles</i>  
[[File:FigQn16.jpg|none]]
'''''Fig. QP16:'''''<i>&nbsp;Individual showers with dressing cubicles</i>  


----
----


<br>[[Image:FigQn17.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. Q17:'''''<i>&nbsp;Individual showers with separate individual dressing cubicles</i>  
[[File:FigQn17.jpg|none]]
'''''Fig. Q17:'''''<i>&nbsp;Individual showers with separate individual dressing cubicles</i>  


----
----


<br>[[Image:FigQn18.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. Q18:'''''<i>&nbsp;Communal showers and common dressing room</i>  
[[File:FigQn18.jpg|none]]
'''''Fig. Q18:'''''<i>&nbsp;Communal showers and common dressing room</i>  


----
----
Line 44: Line 52:
Note: Classes of external influences (see Fig.Q46).  
Note: Classes of external influences (see Fig.Q46).  


==== <br>Equipotential bonding  ====
 
==== Equipotential bonding  ====


(see '''Fig. Q19''')  
(see '''Fig. Q19''')  
Line 50: Line 59:
----
----


<br>[[Image:FigQn19.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. Q19:'''''<i>&nbsp;Supplementary equipotential bonding in a bathroom</i>  
[[File:FigQn19.jpg|none]]
'''''Fig. Q19:'''''<i>&nbsp;Supplementary equipotential bonding in a bathroom</i>  


----
----


==== <br>Requirements prescribed for each zone  ====
 
==== Requirements prescribed for each zone  ====


The table&nbsp; describes the application of the principles mentioned in the foregoing text and in other similar or related cases
The table&nbsp; describes the application of the principles mentioned in the foregoing text and in other similar or related cases

Revision as of 13:10, 15 November 2013

Bathrooms and showers rooms are areas of high risk, because of the very low resistance of the human body when wet or immersed in water.
Precaution to be taken are therefore correspondingly rigorous, and the regulations are more severe than those for most other locations.
The relevant standard is IEC 60364-7-701.

Precautions to observe are based on three aspects:

  • The definition of zones, numbered 0,1, 2, 3 in which the placement (or exclusion) of any electrical device is strictly limited or forbidden and, where permitted, the electrical and mechanical protection is prescribed
  • The establishment of an equipotential bond between all exposed and extraneous metal parts in the zones concerned
  • The strict adherence to the requirements prescribed for each particular zones.


Classification of zones

Sub-clause 701.32 of IEC 60364-7-701 defines the zones 0, 1, 2, 3 as shown in the following diagrams (see Fig. Q12 below to Fig. Q18)


FigQn12.jpg

Fig. Q12: Zones 0, 1, 2 and 3 in proximity to a bath-tub


FigQn13.jpg

Fig. Q13: Zones 0, 1, 2 and 3 in proximity of a shower with basin


FigQn14.jpg

Fig. Q14: Zones 0, 1, 2 and 3 in proximity of a shower without basin


FigQn15.jpg

Fig. Q15: No switch or socket-outlet is permitted within 60 cm of the door opening of a shower cabinet


FigQn16.jpg

Fig. QP16: Individual showers with dressing cubicles


FigQn17.jpg

Fig. Q17: Individual showers with separate individual dressing cubicles


FigQn18.jpg

Fig. Q18: Communal showers and common dressing room


Note: Classes of external influences (see Fig.Q46).


Equipotential bonding

(see Fig. Q19)


FigQn19.jpg

Fig. Q19: Supplementary equipotential bonding in a bathroom



Requirements prescribed for each zone

The table  describes the application of the principles mentioned in the foregoing text and in other similar or related cases