Main characteristics to consider to determine the transformation substations:


*Surface area of building or site
The main criteria to consider for determination of the number and the location of the MV/LV substations are the following:
*Power demand, (to be compared with standardized transformer power),
*Load distribution


The preferred basic configuration comprises one single substation.Certain factors contribute to increasing the number of substations (&gt;1):
* Number of buildings
* Surface of each building
* Number of floors per building
* Repartition and power of the consumers
* Power demand per area, floor, building
* Sensitivity to interruption, need for redundancy


*A large surface area (&gt; 25000m²),  
To determine the number and the location of the MV/LV substations, we may however give the following basic indications:
*The site configuration: several buildings,
*Total power &gt; 2500kVA,
*Sensitivity to interruption: need for redundancy in the case of a fire.<br>


----
* Small and medium size building: One single MV/LV substation
 
* Large building: One or several MV/LV substations depending on the power and the repartition of the consumers
<br>
* Building with several floors: One or several MV/LV substations depending on the power and the repartition of the consumers. One MV/LV substation may be dedicated to each floor
 
* Large site with several buildings: One MV/LV substation may be dedicated to each building.
{| class="wikitable" style="width: 65%; height: 93px"
|-
| &nbsp;
! colspan="3" | Configuration
|-
! Characteristic to consider
! 1 substation with<br>N transformers
! N substations<br>N transformers (identical substations)
! N substations<br>M transformers (different powers)
|-
| Building configuration
| &lt; 25000m²
| ≥ 25000m²<br>1 building with several floors  
| ≥ 25000m²<br>several buildings
|-
| Power demand
| &lt; 2500kVA
| ≥ 2500kVA
| ≥ 2500kVA
|-
| Load distribution
| Localized loads
| Uniform distribution
| Medium density
|}
 
'''''Fig. D11:'''&nbsp;Typical characteristics of the different configurations'' <br>
 
----
 
<br>


[[ru:Число и расстановка трансформаторных подстанций высокого/низкого напряжения]]
[[ru:Число и расстановка трансформаторных подстанций высокого/низкого напряжения]]
[[zh:中压/低压变电站的数量和分布]]
[[zh:中压/低压变电站的数量和分布]]

Revision as of 03:29, 8 December 2014


The main criteria to consider for determination of the number and the location of the MV/LV substations are the following:

  • Number of buildings
  • Surface of each building
  • Number of floors per building
  • Repartition and power of the consumers
  • Power demand per area, floor, building
  • Sensitivity to interruption, need for redundancy

To determine the number and the location of the MV/LV substations, we may however give the following basic indications:

  • Small and medium size building: One single MV/LV substation
  • Large building: One or several MV/LV substations depending on the power and the repartition of the consumers
  • Building with several floors: One or several MV/LV substations depending on the power and the repartition of the consumers. One MV/LV substation may be dedicated to each floor
  • Large site with several buildings: One MV/LV substation may be dedicated to each building.

ru:Число и расстановка трансформаторных подстанций высокого/низкого напряжения zh:中压/低压变电站的数量和分布

Share