Presence of an Uninterruptible Power Supply (UPS): Difference between revisions

From Electrical Installation Guide
Home > MV and LV architecture selection guide for buildings > Choice of architecture details > Presence of an Uninterruptible Power Supply (UPS)
m (1 revision)
(Text modified (guide 2015))
Line 1: Line 1:
{{Menu_MV_and_LV_architecture_selection_guide}}
{{Menu_MV_and_LV_architecture_selection_guide}}
<br>
The electrical power from a UPS is supplied from a storage unit: batteries or inertia wheel. This system allows us to avoid any power failure. The back-up time of the system is limited: from several minutes to several hours.<br>The simultaneous presence of a back-up generator and a UPS unit is used for permanently supply loads for which no failure is acceptable ('''Fig. D17'''). The back-up time of the battery or the inertia wheel must be compatible with the maximum time for the generator to start up and be brought on-line.<br>A UPS unit is also used for supply power to loads that are sensitive to disturbances (generating a “clean” voltage that is independent of the network).<br>Main characteristics to be considered for implementing a UPS:


*Sensitivity of loads to power interruptions,
The electrical power from a UPS is supplied from a storage unit: batteries or inertia wheel. This system prevent any power failure. The back-up time of the system is limited: from several minutes to several hours.
*Sensitivity of loads to disturbances.


The presence of a UPS unit is essential if and only if no failure is acceptable.<br>
The simultaneous presence of a back-up generator and a UPS unit is used for permanently supply loads for which no failure is acceptable '''(Fig. D19)'''. The back-up time of the battery must be compatible with the maximum time for the generator to start up and take over the load supply.
 
A UPS unit is also used to supply loads that are sensitive to power quality (generating a “clean” voltage that is independent of the network).
 
Main characteristics to be considered for implementing a UPS:
 
* Sensitivity of loads to power interruptions (see § 3.9 for definition),
* Sensitivity of loads to disturbances (see § 3.10 for definition).
 
The presence of a UPS unit is essential if and only if no failure is acceptable.


----
----


[[File:FigD17.jpg|none]]
[[File:FigD17.jpg|none]]
'''''Fig. D17:'''&nbsp;Example of connection for a UPS''
'''Fig. D19:''' Example of connection for a UPS


[[ru:Использование источников бесперебойного питания (ИБП)]]
[[ru:Использование источников бесперебойного питания (ИБП)]]
[[zh:不间断电源 (UPS) 的设置]]
[[zh:不间断电源 (UPS) 的设置]]

Revision as of 05:09, 8 December 2014


The electrical power from a UPS is supplied from a storage unit: batteries or inertia wheel. This system prevent any power failure. The back-up time of the system is limited: from several minutes to several hours.

The simultaneous presence of a back-up generator and a UPS unit is used for permanently supply loads for which no failure is acceptable (Fig. D19). The back-up time of the battery must be compatible with the maximum time for the generator to start up and take over the load supply.

A UPS unit is also used to supply loads that are sensitive to power quality (generating a “clean” voltage that is independent of the network).

Main characteristics to be considered for implementing a UPS:

  • Sensitivity of loads to power interruptions (see § 3.9 for definition),
  • Sensitivity of loads to disturbances (see § 3.10 for definition).

The presence of a UPS unit is essential if and only if no failure is acceptable.


FigD17.jpg

Fig. D19: Example of connection for a UPS

ru:Использование источников бесперебойного питания (ИБП) zh:不间断电源 (UPS) 的设置

Share