When an installation is to be supplied directly from a MV/LV transformer and the maximum apparent-power loading of the installation has been determined, a suitable rating for the transformer can be decided, taking into account the following considerations '''(see&nbsp;Fig. A15):'''
When an installation is to be supplied directly from a MV/LV transformer and the maximum apparent-power loading of the installation has been determined, a suitable rating for the transformer can be decided, taking into account the following considerations (see {{FigRef|A15}}):  


*The possibility of improving the power factor of the installation (see chapter L)  
*The possibility of improving the power factor of the installation (see [[Power Factor Correction}})  
*Anticipated extensions to the installation  
*Anticipated extensions to the installation  
*Installation constraints (e.g. temperature)  
*Installation constraints (e.g. temperature)  
*Standard transformer ratings
*Standard transformer ratings
<br>


{| class="wikitable"
{| class="wikitable"
Line 16: Line 12:
! rowspan="2" |  
! rowspan="2" |  
'''Apparent power kVA'''
'''Apparent power kVA'''
! colspan="2" | In (A)
! colspan="2" | In (A)
|-
|-
Line 87: Line 82:
where
where
*Pa = kVA rating of the transformer  
*Pa = kVA rating of the transformer  
*U = phase-to-phase voltage at no-load in volts (237&nbsp;V or 410&nbsp;V)  
*U = phase-to-phase voltage at no-load in volts (237 V or 410 V)  
*In is in amperes.
*In is in amperes.


For a single-phase transformer:


For a single-phase transformer:
<math>\mbox{In}=\frac{\mbox{Pa}\times10^3}{\mbox{V} }</math>


<math>\mbox{In}=\frac{\mbox{Pa}\times10^3}{\mbox{V} }</math> <br>where  
where  


*V = voltage between LV terminals at no-load (in volts)
*V = voltage between LV terminals at no-load (in volts)
Line 100: Line 96:


*In = kVA x 1.4  
*In = kVA x 1.4  
*The IEC standard for power transformers is IEC&nbsp;60076.
*The IEC standard for power transformers is IEC 60076.
 


<br>


[[ru:Выбор номинальной мощности трансформатора]]
[[ru:Выбор номинальной мощности трансформатора]]
[[zh:变压器额定容量的选择]]
[[zh:变压器额定容量的选择]]

Revision as of 01:50, 16 November 2016


When an installation is to be supplied directly from a MV/LV transformer and the maximum apparent-power loading of the installation has been determined, a suitable rating for the transformer can be decided, taking into account the following considerations (see Fig. A15):

  • The possibility of improving the power factor of the installation (see [[Power Factor Correction}})
  • Anticipated extensions to the installation
  • Installation constraints (e.g. temperature)
  • Standard transformer ratings

Apparent power kVA

In (A)
237 V 410 V
100 244 141
160 390 225
250 609 352
315 767 444
400 974 563
500 1218 704
630 1535 887
800 1939 1127
1000 2436 1408
1250 3045 1760
1600 3898 2253
2000 4872 2816
2500 6090 3520
3150 7673 4436
Fig. A15 – Standard apparent powers for MV/LV transformers and related nominal output currents


The nominal full-load current In on the LV side of a 3-phase transformer is given by:

[math]\displaystyle{ \mbox{In}=\frac{\mbox{Pa}\times10^3}{\mbox{U}\sqrt3} }[/math]

where

  • Pa = kVA rating of the transformer
  • U = phase-to-phase voltage at no-load in volts (237 V or 410 V)
  • In is in amperes.

For a single-phase transformer:

[math]\displaystyle{ \mbox{In}=\frac{\mbox{Pa}\times10^3}{\mbox{V} } }[/math]

where

  • V = voltage between LV terminals at no-load (in volts)

Simplified equation for 400 V (3-phase load)

  • In = kVA x 1.4
  • The IEC standard for power transformers is IEC 60076.