Selectivity MV/LV in a consumer’s substation: Difference between revisions

From Electrical Installation Guide
Home > LV switchgear: functions and selection > Circuit-breaker > Selectivity MV/LV in a consumer’s substation
m (1 revision: no page modification, previous revision = imported ch.H pages cleaned-up)
(Cleanup_2016)
Line 1: Line 1:
{{Menu_LV_switchgear_functions_and_selection}}
{{Menu_LV_switchgear_functions_and_selection}}


In general the transformer in a consumer’s substation is protected by MV fuses, suitably rated to match the transformer, in accordance with the principles laid down in IEC 60787 and IEC 60420, by following the advice of the fuse manufacturer.<br>The basic requirement is that a MV fuse will not operate for LV faults occurring downstream of the transformer LV circuit-breaker, so that the tripping characteristic curve of the latter must be to the left of that of the MV fuse pre-arcing curve.<br>This requirement generally fixes the maximum settings for the LV circuit-breaker protection:
In general the transformer in a consumer’s substation is protected by MV fuses, suitably rated to match the transformer, in accordance with the principles laid down in IEC 60787 and IEC 60420, by following the advice of the fuse manufacturer.


The basic requirement is that a MV fuse will not operate for LV faults occurring downstream of the transformer LV circuit-breaker, so that the tripping characteristic curve of the latter must be to the left of that of the MV fuse pre-arcing curve.
This requirement generally fixes the maximum settings for the LV circuit-breaker protection:
*Maximum short-circuit current-level setting of the magnetic tripping element  
*Maximum short-circuit current-level setting of the magnetic tripping element  
*Maximum time-delay allowable for the short-circuit current tripping element
*Maximum time-delay allowable for the short-circuit current tripping element
Line 8: Line 11:
(see {{FigRef|H57}})  
(see {{FigRef|H57}})  


 
{{FigImage|DB422435_EN|svg|H57|Example}}
[[File:FigH57.jpg|none]]
 
 
'''''Fig. H57:''' Example''
 
 


'''Example:'''  
'''Example:'''  
*Short-circuit level at MV terminals of transformer: 250 MVA  
*Short-circuit level at MV terminals of transformer: 250 MVA  
*Transformer MV/LV: 1,250 kVA 20/0.4 kV  
*Transformer MV/LV: 1,250 kVA 20/0.4 kV  
Line 24: Line 20:
*LV circuit-breaker: Compact NS 2000 set at 1,800 A (Ir)
*LV circuit-breaker: Compact NS 2000 set at 1,800 A (Ir)


What is the maximum short-circuit trip current setting and its maximum time delay allowable?<br>The curves of {{FigureRef|H58}} show that discrimination is assured if the short-time delay tripping unit of the CB is set at:
What is the maximum short-circuit trip current setting and its maximum time delay allowable?


The curves of {{FigureRef|H58}} show that discrimination is assured if the short-time delay tripping unit of the CB is set at:
*A level ≤ 6 Ir = 10.8 kA  
*A level ≤ 6 Ir = 10.8 kA  
*A time-delay setting of step 1 or 2
*A time-delay setting of step 1 or 2


 
{{FigImage|DB422436_EN|svg|H58|Curves of MV fuses and LV circuit-breaker}}
[[File:FigH58.jpg|none]]
 
'''''Fig. H58:''' Curves of MV fuses and LV circuit-breaker''


[[ru:Селективное отключение трансформатора на подстанции потребителя]]
[[ru:Селективное отключение трансформатора на подстанции потребителя]]
[[zh:高速断路器]]
[[zh:高速断路器]]

Revision as of 04:03, 3 December 2016


In general the transformer in a consumer’s substation is protected by MV fuses, suitably rated to match the transformer, in accordance with the principles laid down in IEC 60787 and IEC 60420, by following the advice of the fuse manufacturer.

The basic requirement is that a MV fuse will not operate for LV faults occurring downstream of the transformer LV circuit-breaker, so that the tripping characteristic curve of the latter must be to the left of that of the MV fuse pre-arcing curve.

This requirement generally fixes the maximum settings for the LV circuit-breaker protection:

  • Maximum short-circuit current-level setting of the magnetic tripping element
  • Maximum time-delay allowable for the short-circuit current tripping element

(see Fig. H57)

Fig. H57 – Example

Example:

  • Short-circuit level at MV terminals of transformer: 250 MVA
  • Transformer MV/LV: 1,250 kVA 20/0.4 kV
  • MV fuses: 63 A
  • Cabling, transformer - LV circuit-breaker: 10 metres single-core cables
  • LV circuit-breaker: Compact NS 2000 set at 1,800 A (Ir)

What is the maximum short-circuit trip current setting and its maximum time delay allowable?

The curves of Figure H58 show that discrimination is assured if the short-time delay tripping unit of the CB is set at:

  • A level ≤ 6 Ir = 10.8 kA
  • A time-delay setting of step 1 or 2
Fig. H58 – Curves of MV fuses and LV circuit-breaker

ru:Селективное отключение трансформатора на подстанции потребителя zh:高速断路器

Share