Example of lightning current in TT system: Difference between revisions

From Electrical Installation Guide
Home > Overvoltage protection > Surge protection technical supplements > Example of lightning current in TT system
m (1 revision: no page modification, previous revision = imported ch.J pages cleaned-up)
(Cleanup_2016)
Line 1: Line 1:
{{Menu_Overvoltage_protection}}
{{Menu_Overvoltage_protection}}
<br>
 
__TOC__
__TOC__


Common mode SPD between phase and PE or phase and PEN is installed whatever type of system earthing arrangement (see {{FigRef|J58}}).
The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation.
The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the Up voltage of the SPD (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases.
{{FigImage|DB422526_EN|svg|J58|Common protection only}}


Common mode SPD between phase and PE or phase and PEN is installed whatever type of system earthing arrangement (see {{FigRef|J58}}).<br>The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation. <br>The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the Up voltage of the SPD (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases.
To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced.


[[File:Fig J55 EN.jpg|none]]
Another SPD architecture is therefore used (see {{FigRef|J59}})
'''''Fig. J58:''' Common protection only''


To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced.<br>Another SPD architecture is therefore used (see {{FigRef|J59}})<br>The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the SPD (Up2).
The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the SPD (Up2).


[[File:Fig J56 EN.jpg|none]]
{{FigImage|DB422527_EN|svg|J59|Common and differential protection}}
'''''Fig. J59:''' Common and differential protection''


[[zh:TT 系统中的雷电流举例]]
[[zh:TT 系统中的雷电流举例]]

Revision as of 01:01, 5 December 2016


Common mode SPD between phase and PE or phase and PEN is installed whatever type of system earthing arrangement (see Fig. J58).

The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation.

The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the Up voltage of the SPD (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases.

Fig. J58 – Common protection only

To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced.

Another SPD architecture is therefore used (see Fig. J59)

The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the SPD (Up2).

Fig. J59 – Common and differential protection

zh:TT 系统中的雷电流举例

Share