At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N31}}).
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N31}}).


[[File:FigN31.jpg|none]]
{{FigImage|DB422663_EN|svg|N31|Transformer-energizing inrush current}}
'''''Fig N31:''' Transformer-energizing inrush current''


The magnitude of the current peak depends on:  
The magnitude of the current peak depends on:  
*The value of voltage at the instant of energization  
*The value of voltage at the instant of energization  
*The magnitude and polarity of the residual flux existing in the core of the transformer  
*The magnitude and polarity of the residual flux existing in the core of the transformer  
*Characteristics of the load connected to the transformer
*Characteristics of the load connected to the transformer


The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (&lt; 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.
The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.


[[ru:Ток намагничивания трансформатора при включении]]
[[ru:Ток намагничивания трансформатора при включении]]
[[zh:变压器励磁涌流]]
[[zh:变压器励磁涌流]]

Revision as of 01:23, 9 December 2016


At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N31).

Fig. N31 – Transformer-energizing inrush current

The magnitude of the current peak depends on:

  • The value of voltage at the instant of energization
  • The magnitude and polarity of the residual flux existing in the core of the transformer
  • Characteristics of the load connected to the transformer

The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.