Photovoltaic system: electrical equipments selection: Difference between revisions

From Electrical Installation Guide
Home > PhotoVoltaic (PV) installation > Photovoltaic installation architectures > Photovoltaic system: electrical equipments selection
m (1 revision: no page modification, previous revision = imported ch.P pages cleaned-up)
(Cleanup_2016)
Line 6: Line 6:
=== One single phase inverter ===
=== One single phase inverter ===


*Typically, a 5kW grid-connected single-phase inverter. with UOC MAX ≤ 600V.  
Typically, a 5kW grid-connected single-phase inverter. with UOC MAX &le; 600V. One or two strings – Isctc < 25A, IAC < 32A. In this design there is no string protection.  
*One or two strings – Isctc < 25A, IAC < 32A.  
*In this design there is no string protection.
*A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.


[[File:Fig P22.png|none]]
A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.


{| class="wikitable"
{{TableStart|Tab1405|5col}}
|-
|colspan="5" | [[File:DB422723_EN.svg|830px]]
|-
|-
!  width="180px" | Needs
!  width="180px" | Needs
Line 25: Line 24:
| - Isolation || • || • (d) || (a) || • (d)  
| - Isolation || • || • (d) || (a) || • (d)  
|- {{PV_HC1}} align="center"
|- {{PV_HC1}} align="center"
| - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
| - Switching
(Making & breaking rated current  
| •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
|- {{PV_HC1}} align="center"
|- {{PV_HC1}} align="center"
| - Control || • (b) || • (d) || (e) || • (d)
| - Control || • (b) || • (d) || (e) || • (d)
Line 38: Line 39:
|- {{PV_HC4}} align="center"
|- {{PV_HC4}} align="center"
| '''Metering''' || ||  || Inverter relevant parameters || Energy
| '''Metering''' || ||  || Inverter relevant parameters || Energy
|}
|-
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.<br>
{{TableEnd|Tab1405|P22|Grid connected <{{=}} 10kW
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.<br>
|a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
(c) No protection is required when the number of string does not exceed 2.<br>
|b| Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
(d) Service and emergency switching<br>
|c| No protection is required when the number of string does not exceed 2.
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
|d| Service and emergency switching
(f) Overload and short-circuit protection B curve recommended.<br>
|e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
(g) If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI<br>
|f| Overload and short-circuit protection B curve recommended.
 
|g| If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI}}
'''''Fig. P22 :''''' ''Grid connected ≤ 10kW''


== 10 to 100kW grid connected PV system (Small building)==
== 10 to 100kW grid connected PV system (Small building)==
Line 53: Line 53:
=== One three phase multi input inverter without array box ===
=== One three phase multi input inverter without array box ===


* Typically, 10kW to 36kW grid-connected inverters, U<sub>OC MAX</sub> probably higher than 600V (i.e. 800V or 1000V), Isctc < 125A, Iac < 63A.
* Typically, 10kW to 36kW grid-connected inverters, U<sub>OC MAX</sub> probably higher than 600V (i.e. 800V or 1000V), Isctc < 125A, Iac < 63A.  
* In this range of power, inverters usually have between 2 and 4 maximum power point tracking (MPPT) inputs, so the number of strings in the same DC sub-network is equal to one or two.  
* In this range of power, inverters usually have between 2 and 4 maximum power point tracking (MPPT) inputs, so the number of strings in the same DC sub-network is equal to one or two.  
* There is no need for string protection.  
* There is no need for string protection. A PV main switch for each MPPT input is necessary.
* A PV main switch for each MPPT input is necessary.  
* When an inverter is indoors, additional remote-controlled switches at DC cable entry point are recommended for emergencies services.
* When an inverter is indoors, additional remote-controlled switches at DC cable entry point are recommended for emergencies services.


[[File:Fig P23.png|none]]
{{TableStart|Tab1406|5col}}
 
|-
{| class="wikitable"
| colspan="5" | [[File:DB422724_EN.svg|900px]]
|-
|-
!  width="170px" | Needs
!  width="170px" | Needs
Line 73: Line 72:
| - Isolation || • || • (d) || (a) || • (d)  
| - Isolation || • || • (d) || (a) || • (d)  
|- {{PV_HC1}} align="center"
|- {{PV_HC1}} align="center"
| - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
| - Switching<br>(Making & breaking rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
|- {{PV_HC1}} align="center"
|- {{PV_HC1}} align="center"
| - Control || • (b) || • (d) || (e) || • (d)
| - Control || • (b) || • (d) || (e) || • (d)
Line 86: Line 85:
|- {{PV_HC4}} align="center"
|- {{PV_HC4}} align="center"
| '''Metering''' || ||  ||  || Energy
| '''Metering''' || ||  ||  || Energy
|}
|-
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.<br>
{{TableEnd|Tab1406|P23|10-100kW single multi MPPT inverter
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.<br>
|a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
(c) No protection is required when the number of string does not exceed 2.<br>
|b| Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
(d) Service and emergency switching<br>
|c| No protection is required when the number of string does not exceed 2.
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
|d| Service and emergency switching
(f) Overload and short-circuit protection (B curve recommended).<br>
|e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
(g) If there is no SPD in the inverter or if the distance between String junction box and inverter exceeds 10m a SPD is necessary in this box.<br>
|f| Overload and short-circuit protection (B curve recommended).
(h)
|g| If there is no SPD in the inverter or if the distance between String junction box and inverter exceeds 10m a SPD is necessary in this box.
|h|
*If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
*If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
*If the inverter provides at least simple separation
*If the inverter provides at least simple separation
** Without functional earthing: insulation monitoring is necessary, it's usually done by the inverter in this range of power.
** Without functional earthing: insulation monitoring is necessary, it's usually done by the inverter in this range of power.
** With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.
** With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}}
 
'''''Fig. P23 :''''' ''10-100kW single multi MPPT inverter''
 


=== One three phase inverter with One Array box ===
=== One three phase inverter with One Array box ===
Line 110: Line 107:
* A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.
* A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.


[[File:Fig P24.png|none]]
{{TableStart|Tab1407|5col}}
 
|-
{| class="wikitable"
| colspan="5" | [[File:DB422725_EN.svg|830px]]
|-
|-
!  width="160px" | Needs
!  width="160px" | Needs
Line 124: Line 121:
| - Isolation || • || • (d) || (a) || • (d)  
| - Isolation || • || • (d) || (a) || • (d)  
|- {{PV_HC1}} align="center"
|- {{PV_HC1}} align="center"
| - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
| - Switching<br>(Making & breaking rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
|- {{PV_HC1}} align="center"
|- {{PV_HC1}} align="center"
| - Control || • (b) || • (d) || (e) || • (d)
| - Control || • (b) || • (d) || (e) || • (d)
Line 137: Line 134:
|- {{PV_HC4}} align="center"
|- {{PV_HC4}} align="center"
| '''Metering''' || ||  ||  || P, Q, PF, Energy
| '''Metering''' || ||  ||  || P, Q, PF, Energy
|}
|-
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.<br>
{{TableEnd|Tab1407|P24|10-100kW single MPPT inverter
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building. The main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing for that purpose.<br>
|a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
(d) Service and emergency switching<br>
|b| Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building. The main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing for that purpose.
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
|c| Service and emergency switching
(f) Overload and short-circuit protection (B curve recommended).<br>
|d| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
(g) If there is no SPD in the inverter or if the distance between String / Array junction box and inverter exceeds 10m a SPD is necessary in this box.<br>
|e| Overload and short-circuit protection (B curve recommended).
(h)
|f| If there is no SPD in the inverter or if the distance between String / Array junction box and inverter exceeds 10m a SPD is necessary in this box.
|g|
* If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI.
* If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI.
* If the inverter provides at least simple separation
* If the inverter provides at least simple separation
** Without functional earthing: insulation monitoring is necessary
** Without functional earthing: insulation monitoring is necessary
** With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.
** With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}}
 
'''''Fig. P24 :''''' ''10-100kW single MPPT inverter''


=== Multi single phase inverters design ===
=== Multi single phase inverters design ===
Line 158: Line 154:
* In that case, the DC system is very simple and the AC system is very similar to usual AC systems.
* In that case, the DC system is very simple and the AC system is very similar to usual AC systems.


[[File:Fig P25.png|none]]
{{TableStart|Tab1408|5col}}
 
|-
{| class="wikitable"
| colspan="5" | [[File:DB422726_EN.svg|820px]]
|-
|-
!  width="170px" | Needs
!  width="170px" | Needs
! align="center" width="120px" | PV array<br>main switch
! align="center" width="120px" | PV arraymain switch
! align="center" width="140px" | Inverter
! align="center" width="140px" | Inverter
! align="center" width="180px" |  
! align="center" width="180px" |  
Line 175: Line 171:
|- {{PV_HC4}} align="center"
|- {{PV_HC4}} align="center"
| '''Metering''' || ||  || Energy || P,Q, PF, Energy, unbalance
| '''Metering''' || ||  || Energy || P,Q, PF, Energy, unbalance
|}
|-
 
{{TableEnd|Tab1408|P25|10-100kW multi single MPPT inverter}}
'''''Fig. P25 :''''' ''10-100kW multi single MPPT inverter''


=== Three phase inverter with two Array boxes (Na ≤ 2) ===
=== Three phase inverter with two Array boxes (Na ≤ 2) ===


Typically, 60kW to 100kW grid-connected inverters with 2 arrays. Array cable protection is not necessary for 2 or 3 arrays.
Typically, 60kW to 100kW grid-connected inverters with 2 arrays. Array cable protection is not necessary for 2 or 3 arrays.
The I<sub>sctc</sub> array &le; 200A, I<sub>sctc</sub> ≤ 400A, and I<sub>max</sub> AC &le; 200A. A PV main switch is required close to the inverter. Remotely operated switches in array boxes allow disconnects to be located close to the PV modules in the event of emergencies.
The I<sub>sctc</sub> array &le; 200A, I<sub>sctc</sub> ≤ 400A, and I<sub>max</sub> AC &le; 200A. A PV main switch is required close to the inverter. Remotely operated switches in array boxes allow disconnects to be located close to the PV modules in the event of emergencies.


[[File:Fig P26.png|none]]
{{TableStart|Tab1409|5col}}
 
|-
{| class="wikitable"
| colspan="5" | [[File:DB422727_EN.svg|810px]]
|-
|-
!  width="160px" | Needs
!  width="160px" | Needs
Line 211: Line 207:
|- {{PV_HC4}} align="center"
|- {{PV_HC4}} align="center"
| '''Metering''' || ||  ||  || P, Q, PF, Energy
| '''Metering''' || ||  ||  || P, Q, PF, Energy
|}
|-
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.<br>
{{TableEnd|Tab1409|P26|10-100kW single MPPT inverter with 2 arrays
(b) If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.<br>
|a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
(c) No protection is required when the number of arrays ≤ 3 (No cable sizing benefit)<br>
|b| If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
(d) Service and emergency switching<br>
|c| No protection is required when the number of arrays ≤ 3 (No cable sizing benefit)
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
|d| Service and emergency switching
(f) Overload and short-circuit protection.<br>
|e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
(g) If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.<br>
|f| Overload and short-circuit protection.
(h)
|g| If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.
|h|
* If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
* If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
* If the inverter provides at least simple separation
* If the inverter provides at least simple separation
** Without functional earthing: insulation monitoring is necessary
** Without functional earthing: insulation monitoring is necessary
** With functional earthing: the earthing shall be done with a DC MCB breaker (iC60PV 4P series 2 – 10A) or a fuse.
** With functional earthing: the earthing shall be done with a DC MCB breaker (iC60PV 4P series 2 – 10A) or a fuse.}}
 
'''''Fig. P26 :''''' ''10-100kW single MPPT inverter with 2 arrays''


== 150kW to 500kW Grid connected PV system (Large building and farm)  ==
== 150kW to 500kW Grid connected PV system (Large building and farm)  ==

Revision as of 01:00, 12 December 2016

Grid connected PV system ≤ 10kW (Residential)

One single phase inverter

Typically, a 5kW grid-connected single-phase inverter. with UOC MAX ≤ 600V. One or two strings – Isctc < 25A, IAC < 32A. In this design there is no string protection.

A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.

DB422723 EN.svg
Needs String junction box PV array main switch Inverter AC box (400V)
Switchgears and control (Q)
- Isolation • (d) (a) • (d)
- Switching

(Making & breaking rated current


DC21B
• (d)
DC21B
(a) • (d)
- Control • (b) • (d) (e) • (d)
- Over-current protection (c) • (f)
- Protection against
Insulation fault
(g) (g)
RCD type B or A SI
Surge protection (SPD) • type 2 • type 1 or 2
Enclosure (E) Outdoor
Double insulation
Indoor
Double insulation
Standard AC requirement +
grid code requirement
Metering Inverter relevant parameters Energy

[a]  PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
[b]  Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
[c]  No protection is required when the number of string does not exceed 2.
[d]  Service and emergency switching
[e]  Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[f]  Overload and short-circuit protection B curve recommended.
[g]  If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI

Fig. P22 – Grid connected <= 10kW

10 to 100kW grid connected PV system (Small building)

One three phase multi input inverter without array box

  • Typically, 10kW to 36kW grid-connected inverters, UOC MAX probably higher than 600V (i.e. 800V or 1000V), Isctc < 125A, Iac < 63A.
  • In this range of power, inverters usually have between 2 and 4 maximum power point tracking (MPPT) inputs, so the number of strings in the same DC sub-network is equal to one or two.
  • There is no need for string protection. A PV main switch for each MPPT input is necessary.
  • When an inverter is indoors, additional remote-controlled switches at DC cable entry point are recommended for emergencies services.
DB422724 EN.svg
Needs String junction box PV array main switch Inverter AC box (400V)
Switchgears and control (Q)
- Isolation • (d) (a) • (d)
- Switching
(Making & breaking rated current

DC21B
• (d)
DC21B
(a) • (d)
- Control • (b) • (d) (e) • (d)
- Over-current protection (c) • (f)
- Protection against
Insulation fault
(h) (h)
RCD type B or A SI
Surge protection (SPD) (g) • type 2 • type 1 or 2
Enclosure (E) Outdoor IP5x
Double insulation
Indoor IP5x
Double insulation
Standard AC requirement +
grid code requirement
Metering Energy

[a]  PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
[b]  Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
[c]  No protection is required when the number of string does not exceed 2.
[d]  Service and emergency switching
[e]  Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[f]  Overload and short-circuit protection (B curve recommended).
[g]  If there is no SPD in the inverter or if the distance between String junction box and inverter exceeds 10m a SPD is necessary in this box.
[h] 

  • If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
  • If the inverter provides at least simple separation
    • Without functional earthing: insulation monitoring is necessary, it's usually done by the inverter in this range of power.
    • With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.

Fig. P23 – 10-100kW single multi MPPT inverter

One three phase inverter with One Array box

  • Typically, 30kW to 60kW grid-connected inverters. UOC max is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A.
  • This design has more than 2 strings.
  • Reverse current protection is therefore necessary.
  • A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.
DB422725 EN.svg
Needs String / Array junction box PV array main switch Inverter AC box (400V)
Switchgears and control (Q)
- Isolation • (d) (a) • (d)
- Switching
(Making & breaking rated current

DC21B
• (d)
DC21B
(a) • (d)
- Control • (b) • (d) (e) • (d)
- Over-current protection • (f)
- Protection against
Insulation fault
(h) (h)
RCD type B or A SI
Surge protection (SPD) (g) • type 2 • type 1 or 2
Enclosure (E) Outdoor IP5x
Double insulation
Indoor IP5x
Double insulation
Standard AC requirement +
grid code requirement
Metering P, Q, PF, Energy

[a]  PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
[b]  Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building. The main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing for that purpose.
[c]  Service and emergency switching
[d]  Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[e]  Overload and short-circuit protection (B curve recommended).
[f]  If there is no SPD in the inverter or if the distance between String / Array junction box and inverter exceeds 10m a SPD is necessary in this box.
[g] 

  • If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI.
  • If the inverter provides at least simple separation
    • Without functional earthing: insulation monitoring is necessary
    • With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.

Fig. P24 – 10-100kW single MPPT inverter

Multi single phase inverters design

  • Typically, 6x5 to 20x5kW grid-connected inverters.
  • The design used for residential building can be duplicated as often as necessary.
  • In that case, the DC system is very simple and the AC system is very similar to usual AC systems.
DB422726 EN.svg
Needs PV arraymain switch Inverter AC box (400V)
Switchgears and control (Q) See ≤10kW design
Surge protection (SPD) • type 2 • type 1 or 2
Enclosure (E) Outdoor IP5x
Double insulation
Standard AC requirement +
grid code requirement
Metering Energy P,Q, PF, Energy, unbalance
Fig. P25 – 10-100kW multi single MPPT inverter

Three phase inverter with two Array boxes (Na ≤ 2)

Typically, 60kW to 100kW grid-connected inverters with 2 arrays. Array cable protection is not necessary for 2 or 3 arrays.

The Isctc array ≤ 200A, Isctc ≤ 400A, and Imax AC ≤ 200A. A PV main switch is required close to the inverter. Remotely operated switches in array boxes allow disconnects to be located close to the PV modules in the event of emergencies.

DB422727 EN.svg
Needs String / Array junction box PV array main switch Inverter AC box (400V)
Switchgears and control (Q)
- Isolation • (d) (a) • (d)
- Switching
(Making & breaking
rated current

DC21B
• (d)
DC21B
(a) • (d)
- Control • (b) • (d) (e) • (d)
- Over-current protection (c) • (f)
- Protection against
Insulation fault
(h) (h)
RCD type B or A SI
Surge protection (SPD) (g) • type 2 • type 1 or 2
Enclosure (E) Outdoor IP5x
Double insulation
Indoor IP5x
Double insulation
Standard AC requirement +
grid code requirement
Metering P, Q, PF, Energy

[a]  PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
[b]  If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
[c]  No protection is required when the number of arrays ≤ 3 (No cable sizing benefit)
[d]  Service and emergency switching
[e]  Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[f]  Overload and short-circuit protection.
[g]  If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.
[h] 

  • If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
  • If the inverter provides at least simple separation
    • Without functional earthing: insulation monitoring is necessary
    • With functional earthing: the earthing shall be done with a DC MCB breaker (iC60PV 4P series 2 – 10A) or a fuse.

Fig. P26 – 10-100kW single MPPT inverter with 2 arrays

150kW to 500kW Grid connected PV system (Large building and farm)

Three phase inverter with more than two Array boxes

  • Typically, 150kW to 500kW single inverter.
  • This design is very similar to the previous one except that it has more arrays, which requires array cable protection.
  • Istc <= 400A, IAC <= 600A.
Fig P27 2015.jpg
Needs String Array junction box Generator junction box Inverter AC box 400V or other voltage (Transfoless inverter)
Switchgears and control (Q)
- Isolation (a) • (d)
- Switching
(Making & breaking
rated current

DC22A

DC22A
• (a) • (d)
- Control • (b) • (a)(e) • (d)
- Over-current protection • (c) • (f)
- Protection against
Insulation fault
• (h) • (h)
Surge protection (SPD) (g) • type 2 • type 1 or 2
Enclosure (E) Outdoor IP5x
Double insulation
Indoor
Double insulation
Standard AC requirement +
grid code requirement
Metering P, Q, PF, Energy, Alarm, THD, individual harmonics

(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
(b) If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
(c) Array cable protection is recommended to prevent cable oversizing. To ensure fast trip of protections 6 to 8 arrays are recommended.
(d) Service and emergency switching
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
(f) Overload and short-circuit protection.
(g) If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.
(h) Galvanic insulation is provided by LV/MV transformer,

  • PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700
  • PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.

Fig. P27 : 150-500kW single MPPT inverter with N arrays > 2

Multi three phases inverters design without array box

Typically 10x20 to 20x30kW grid connected inverters
Uoc max ≤ 1000V one or two string per inverter. IAC max 50A for one inverter.

Fig P28.png
Needs String junction box AC Combiner box
Switchgears and control (Q) See 10 to 36kW design
Surge protection (SPD) • type 2 • type 1 or 2
Enclosure (E) Outdoor IP5x
Double insulation
Standard AC requirement +
grid code requirement
Metering Energy P, Q, PF, Energy, Alarm

Fig. P28 : 150-500kW multi 3-phases inverters

Multi MW Grid connected PV system (Large building and farm)

  • Typically 500kW-630kW inverters with LV/MV transformers and MV substation.
Fig P29.png
Needs String Array junction box Generator junction box Inverter AC box 400V or other voltage (Transfoless inverter)
Switchgears and control (Q) DC side AC side
- Isolation • (a)
- Switching

(Making & breaking
rated current


DC22A

• (a)

DC22A or 23A

AC1

- Control • (b)
- Over-current protection • (c) No • (f)
- Protection against

Insulation fault

• (h) • (h)
Surge protection (SPD) (g) • type 2 (g) • type 1 or 2
Enclosure (E) Outdoor IP5x
Double insulation
Indoor
Double insulation
Metering Energy P, Q, PF, Energy, Alarm, Power quality

(a) PV array main switch is usually included in the inverter panel.
(b) If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
(c) Array cable protection is recommended to prevent cable oversizing. To ensure fast trip of protections 6 to 8 arrays are recommended.
(f) Overload and short-circuit protection.
(g) If there is no SPD in the inverter or if the between DC box and inverter >10m a SPD is necessary in this box.
(h) Galvanic insulation is provided by LV/MV transformer,

  • PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700
  • PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.

Fig. P29 : 500-630kW inverters with LV/MV transformers

Share