Photovoltaic system: electrical equipments selection: Difference between revisions
CleanUp2016 (talk | contribs) (Cleanup_2016) |
CleanUp2016 (talk | contribs) (Cleanup_2016) |
||
Line 23: | Line 23: | ||
| colspan="5" | '''Switchgears and control (Q)''' | | colspan="5" | '''Switchgears and control (Q)''' | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Isolation || • || •{{TabRef|Tab1405|d}} || {{TabRef|Tab1405|a}} || • {{TabRef|Tab1405|d}} | | - Isolation || • || •{{TabRef|Tab1405|d}} || {{TabRef|Tab1405|a}} || •{{TabRef|Tab1405|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Switching | | - Switching | ||
(Making & breaking rated current | (Making & breaking rated current | ||
| •<br>DC21B || • {{TabRef|Tab1405|d}}<br>DC21B || {{TabRef|Tab1405|a}} || • {{TabRef|Tab1405|d}} | | •<br>DC21B || •{{TabRef|Tab1405|d}}<br>DC21B || {{TabRef|Tab1405|a}} || •{{TabRef|Tab1405|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Control || • {{TabRef|Tab1405|b}} || •{{TabRef|Tab1405|d}} || {{TabRef|Tab1405|e}} || •{{TabRef|Tab1405|d}} | | - Control || •{{TabRef|Tab1405|b}} || •{{TabRef|Tab1405|d}} || {{TabRef|Tab1405|e}} || •{{TabRef|Tab1405|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Over-current protection || {{TabRef|Tab1405|c}} || || || • {{TabRef|Tab1405|f}} | | - Over-current protection || {{TabRef|Tab1405|c}} || || || •{{TabRef|Tab1405|f}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Protection against<br>Insulation fault || || || {{TabRef|Tab1405|g}} || {{TabRef|Tab1405|g}} <br>RCD type B or A SI | | - Protection against<br>Insulation fault || || || {{TabRef|Tab1405|g}} || {{TabRef|Tab1405|g}} <br>RCD type B or A SI | ||
Line 71: | Line 71: | ||
| colspan="5" | '''Switchgears and control (Q)''' | | colspan="5" | '''Switchgears and control (Q)''' | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Isolation || • || • {{TabRef|Tab1406|d}} || {{TabRef|Tab1406|a}} || • {{TabRef|Tab1406|d}} | | - Isolation || • || •{{TabRef|Tab1406|d}} || {{TabRef|Tab1406|a}} || •{{TabRef|Tab1406|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Switching<br>(Making & breaking rated current || •<br>DC21B || • {{TabRef|Tab1406|d}}<br>DC21B || {{TabRef|Tab1406|a}} || • {{TabRef|Tab1406|d}} | | - Switching<br>(Making & breaking rated current || •<br>DC21B || • {{TabRef|Tab1406|d}}<br>DC21B || {{TabRef|Tab1406|a}} || •{{TabRef|Tab1406|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Control || • {{TabRef|Tab1406|b}} || • {{TabRef|Tab1406|d}} || {{TabRef|Tab1406|e}} || • {{TabRef|Tab1406|d}} | | - Control || •{{TabRef|Tab1406|b}} || •{{TabRef|Tab1406|d}} || {{TabRef|Tab1406|e}} || •{{TabRef|Tab1406|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Over-current protection || {{TabRef|Tab1406|c}} || || || • {{TabRef|Tab1406|f}} | | - Over-current protection || {{TabRef|Tab1406|c}} || || || •{{TabRef|Tab1406|f}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Protection against<br>Insulation fault || || || {{TabRef|Tab1406|h}} || {{TabRef|Tab1406|h}}<br>RCD type B or A SI | | - Protection against<br>Insulation fault || || || {{TabRef|Tab1406|h}} || {{TabRef|Tab1406|h}}<br>RCD type B or A SI | ||
Line 96: | Line 96: | ||
|g| If there is no SPD in the inverter or if the distance between String junction box and inverter exceeds 10m a SPD is necessary in this box. | |g| If there is no SPD in the inverter or if the distance between String junction box and inverter exceeds 10m a SPD is necessary in this box. | ||
|h| | |h| | ||
|| | || If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI | ||
|| | || If the inverter provides at least simple separation | ||
|| | || - Without functional earthing: insulation monitoring is necessary, it's usually done by the inverter in this range of power. | ||
|| | || - With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}} | ||
=== One three phase inverter with One Array box === | === One three phase inverter with One Array box === | ||
Line 120: | Line 120: | ||
| colspan="5" | '''Switchgears and control (Q)''' | | colspan="5" | '''Switchgears and control (Q)''' | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Isolation || • || • {{TabRef|Tab1407|d}} || {{TabRef|Tab1407|a}} || • {{TabRef|Tab1407|d}} | | - Isolation || • || •{{TabRef|Tab1407|d}} || {{TabRef|Tab1407|a}} || •{{TabRef|Tab1407|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Switching<br>(Making & breaking rated current || •<br>DC21B || • {{TabRef|Tab1407|d}}<br>DC21B || {{TabRef|Tab1407|a}} || • {{TabRef|Tab1407|d}} | | - Switching<br>(Making & breaking rated current || •<br>DC21B || •{{TabRef|Tab1407|d}}<br>DC21B || {{TabRef|Tab1407|a}} || •{{TabRef|Tab1407|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Control || • {{TabRef|Tab1407|b}} || • {{TabRef|Tab1407|d}} || {{TabRef|Tab1407|e}} || • {{TabRef|Tab1407|d}} | | - Control || •{{TabRef|Tab1407|b}} || •{{TabRef|Tab1407|d}} || {{TabRef|Tab1407|e}} || •{{TabRef|Tab1407|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Over-current protection || • || || || • {{TabRef|Tab1407|f}} | | - Over-current protection || • || || || •{{TabRef|Tab1407|f}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Protection against<br>Insulation fault || || || {{TabRef|Tab1407|h}} || {{TabRef|Tab1407|h}}<br>RCD type B or A SI | | - Protection against<br>Insulation fault || || || {{TabRef|Tab1407|h}} || {{TabRef|Tab1407|h}}<br>RCD type B or A SI | ||
Line 144: | Line 144: | ||
|f| If there is no SPD in the inverter or if the distance between String / Array junction box and inverter exceeds 10m a SPD is necessary in this box. | |f| If there is no SPD in the inverter or if the distance between String / Array junction box and inverter exceeds 10m a SPD is necessary in this box. | ||
|g| | |g| | ||
|| | || If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI. | ||
|| | || If the inverter provides at least simple separation | ||
|| | || - Without functional earthing: insulation monitoring is necessary | ||
|| | || - With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}} | ||
=== Multi single phase inverters design === | === Multi single phase inverters design === | ||
Line 193: | Line 193: | ||
| colspan="5" | '''Switchgears and control (Q)''' | | colspan="5" | '''Switchgears and control (Q)''' | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Isolation || • || • {{TabRef|Tab1409|d}} || {{TabRef|Tab1409|a}} || • {{TabRef|Tab1409|d}} | | - Isolation || • || •{{TabRef|Tab1409|d}} || {{TabRef|Tab1409|a}} || •{{TabRef|Tab1409|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • {{TabRef|Tab1409|d}}<br>DC21B || {{TabRef|Tab1409|a}} || • {{TabRef|Tab1409|d}} | | - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || •{{TabRef|Tab1409|d}}<br>DC21B || {{TabRef|Tab1409|a}} || •{{TabRef|Tab1409|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Control || • {{TabRef|Tab1409|b}} || • {{TabRef|Tab1409|d}} || {{TabRef|Tab1409|e}} || •{{TabRef|Tab1409|d}} | | - Control || • {{TabRef|Tab1409|b}} || •{{TabRef|Tab1409|d}} || {{TabRef|Tab1409|e}} || •{{TabRef|Tab1409|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Over-current protection || • || {{TabRef|Tab1409|c}}|| || •{{TabRef|Tab1409|f}} | | - Over-current protection || • || {{TabRef|Tab1409|c}}|| || •{{TabRef|Tab1409|f}} | ||
Line 218: | Line 218: | ||
|g| If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box. | |g| If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box. | ||
|h| | |h| | ||
|| | || If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI | ||
|| | || If the inverter provides at least simple separation | ||
|| | || - Without functional earthing: insulation monitoring is necessary | ||
|| | || - With functional earthing: the earthing shall be done with a DC MCB breaker (iC60PV 4P series 2 – 10A) or a fuse.}} | ||
== 150kW to 500kW Grid connected PV system (Large building and farm) == | == 150kW to 500kW Grid connected PV system (Large building and farm) == | ||
Line 244: | Line 244: | ||
| colspan="6" | '''Switchgears and control (Q)''' | | colspan="6" | '''Switchgears and control (Q)''' | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Isolation || • || • || • || | | - Isolation || • || • || • || {{TabRef|Tab1410|a}} || •{{TabRef|Tab1410|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Switching<br>(Making & breaking<br>rated current || || •<br>DC22A || • <br>DC22A || • | | - Switching<br>(Making & breaking<br>rated current || || •<br>DC22A || • <br>DC22A || •{{TabRef|Tab1410|a}} || •{{TabRef|Tab1410|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Control || || • | | - Control || || •{{TabRef|Tab1410|b}} || || •{{TabRef|Tab1410|a}}{{TabRef|Tab1410|e}} || •{{TabRef|Tab1410|d}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Over-current protection || • || || • | | - Over-current protection || • || || •{{TabRef|Tab1410|c}} || || •{{TabRef|Tab1410|f}} | ||
|- {{PV_HC1}} align="center" | |- {{PV_HC1}} align="center" | ||
| - Protection against<br>Insulation fault || || || || • | | - Protection against<br>Insulation fault || || || || •{{TabRef|Tab1410|h}} || •{{TabRef|Tab1410|h}} | ||
|- {{PV_HC2}} align="center" | |- {{PV_HC2}} align="center" | ||
| '''Surge protection (SPD)''' || || | | '''Surge protection (SPD)''' || || {{TabRef|Tab1410|g}} || • type 2 || || • type 1 or 2 | ||
|- {{PV_HC3}} align="center" | |- {{PV_HC3}} align="center" | ||
| '''Enclosure (E)''' || || Outdoor IP5x<br>Double insulation || Indoor<br>Double insulation || || Standard AC requirement +<br>grid code requirement | | '''Enclosure (E)''' || || Outdoor IP5x<br>Double insulation || Indoor<br>Double insulation || || Standard AC requirement +<br>grid code requirement | ||
Line 269: | Line 269: | ||
|g| If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box. | |g| If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box. | ||
|h| Galvanic insulation is provided by LV/MV transformer, | |h| Galvanic insulation is provided by LV/MV transformer, | ||
|| - PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700 | |||
|| - PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}} | |||
=== Multi three phases inverters design without array box === | === Multi three phases inverters design without array box === | ||
Line 320: | Line 320: | ||
| • | | • | ||
| • | | • | ||
| • | | •{{TabRef|Tab1412|a}} | ||
|• | |• | ||
|• | |• | ||
Line 331: | Line 331: | ||
| •<br> | | •<br> | ||
DC22A | DC22A | ||
| • | | •{{TabRef|Tab1412|a}} | ||
|• | |• | ||
DC22A or | DC22A or | ||
Line 341: | Line 341: | ||
| - Control | | - Control | ||
| | | | ||
| • | | •{{TabRef|Tab1412|b}} | ||
| | | | ||
|• | |• | ||
Line 350: | Line 350: | ||
| • | | • | ||
| | | | ||
| • | | •{{TabRef|Tab1412|c}} | ||
|No | |No | ||
|• | |• | ||
| • | | •{{TabRef|Tab1412|f}} | ||
|- align="center" | |- align="center" | ||
| - Protection against | | - Protection against | ||
Line 359: | Line 359: | ||
| | | | ||
| | | | ||
|• | |•{{TabRef|Tab1412|h}} | ||
|• | |• | ||
| | | | ||
| • | | •{{TabRef|Tab1412|h}} | ||
|- align="center" | |- align="center" | ||
| '''Surge protection (SPD)''' | | '''Surge protection (SPD)''' | ||
| | | | ||
| | | {{TabRef|Tab1412|g}} | ||
| • type 2 | | • type 2 | ||
| colspan="2" | | | colspan="2" | {{TabRef|Tab1412|g}} | ||
| • type 1 or 2 | | • type 1 or 2 | ||
|- align="center" | |- align="center" | ||
Line 394: | Line 394: | ||
|e| If there is no SPD in the inverter or if the between DC box and inverter >10m a SPD is necessary in this box. | |e| If there is no SPD in the inverter or if the between DC box and inverter >10m a SPD is necessary in this box. | ||
|f| Galvanic insulation is provided by LV/MV transformer, | |f| Galvanic insulation is provided by LV/MV transformer, | ||
|| - PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700 | |||
|| - PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}} |
Revision as of 08:36, 12 December 2016
Grid connected PV system ≤ 10kW (Residential)
One single phase inverter
Typically, a 5kW grid-connected single-phase inverter. with UOC MAX ≤ 600V. One or two strings – Isctc < 25A, IAC < 32A. In this design there is no string protection.
A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
Needs | String junction box | PV array main switch | Inverter | AC box (400V) |
---|---|---|---|---|
Switchgears and control (Q) | ||||
- Isolation | • | •[d] | [a] | •[d] |
- Switching
(Making & breaking rated current |
• DC21B |
•[d] DC21B |
[a] | •[d] |
- Control | •[b] | •[d] | [e] | •[d] |
- Over-current protection | [c] | •[f] | ||
- Protection against Insulation fault |
[g] | [g] RCD type B or A SI | ||
Surge protection (SPD) | • type 2 | • type 1 or 2 | ||
Enclosure (E) | Outdoor Double insulation |
Indoor Double insulation |
Standard AC requirement + grid code requirement | |
Metering | Inverter relevant parameters | Energy |
[a] PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
[b] Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
[c] No protection is required when the number of string does not exceed 2.
[d] Service and emergency switching
[e] Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[f] Overload and short-circuit protection B curve recommended.
[g] If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
10 to 100kW grid connected PV system (Small building)
One three phase multi input inverter without array box
- Typically, 10kW to 36kW grid-connected inverters, UOC MAX probably higher than 600V (i.e. 800V or 1000V), Isctc < 125A, Iac < 63A.
- In this range of power, inverters usually have between 2 and 4 maximum power point tracking (MPPT) inputs, so the number of strings in the same DC sub-network is equal to one or two.
- There is no need for string protection. A PV main switch for each MPPT input is necessary.
- When an inverter is indoors, additional remote-controlled switches at DC cable entry point are recommended for emergencies services.
Needs | String junction box | PV array main switch | Inverter | AC box (400V) |
---|---|---|---|---|
Switchgears and control (Q) | ||||
- Isolation | • | •[d] | [a] | •[d] |
- Switching (Making & breaking rated current |
• DC21B |
• [d] DC21B |
[a] | •[d] |
- Control | •[b] | •[d] | [e] | •[d] |
- Over-current protection | [c] | •[f] | ||
- Protection against Insulation fault |
[h] | [h] RCD type B or A SI | ||
Surge protection (SPD) | [g] | • type 2 | • type 1 or 2 | |
Enclosure (E) | Outdoor IP5x Double insulation |
Indoor IP5x Double insulation |
Standard AC requirement + grid code requirement | |
Metering | Energy |
[a] PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
[b] Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
[c] No protection is required when the number of string does not exceed 2.
[d] Service and emergency switching
[e] Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[f] Overload and short-circuit protection (B curve recommended).
[g] If there is no SPD in the inverter or if the distance between String junction box and inverter exceeds 10m a SPD is necessary in this box.
If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
If the inverter provides at least simple separation
- Without functional earthing: insulation monitoring is necessary, it's usually done by the inverter in this range of power.
- With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.
One three phase inverter with One Array box
- Typically, 30kW to 60kW grid-connected inverters. UOC max is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A.
- This design has more than 2 strings.
- Reverse current protection is therefore necessary.
- A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.
Needs | String / Array junction box | PV array main switch | Inverter | AC box (400V) |
---|---|---|---|---|
Switchgears and control (Q) | ||||
- Isolation | • | •[d] | [a] | •[d] |
- Switching (Making & breaking rated current |
• DC21B |
•[d] DC21B |
[a] | •[d] |
- Control | •[b] | •[d] | [e] | •[d] |
- Over-current protection | • | •[f] | ||
- Protection against Insulation fault |
[h] | [h] RCD type B or A SI | ||
Surge protection (SPD) | [g] | • type 2 | • type 1 or 2 | |
Enclosure (E) | Outdoor IP5x Double insulation |
Indoor IP5x Double insulation |
Standard AC requirement + grid code requirement | |
Metering | P, Q, PF, Energy |
[a] PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
[b] Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building. The main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing for that purpose.
[c] Service and emergency switching
[d] Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[e] Overload and short-circuit protection (B curve recommended).
[f] If there is no SPD in the inverter or if the distance between String / Array junction box and inverter exceeds 10m a SPD is necessary in this box.
If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI.
If the inverter provides at least simple separation
- Without functional earthing: insulation monitoring is necessary
- With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.
Multi single phase inverters design
- Typically, 6x5 to 20x5kW grid-connected inverters.
- The design used for residential building can be duplicated as often as necessary.
- In that case, the DC system is very simple and the AC system is very similar to usual AC systems.
Needs | PV arraymain switch | Inverter | AC box (400V) | |
---|---|---|---|---|
Switchgears and control (Q) | See ≤10kW design | |||
Surge protection (SPD) | • type 2 | • type 1 or 2 | ||
Enclosure (E) | Outdoor IP5x Double insulation |
Standard AC requirement + grid code requirement | ||
Metering | Energy | P,Q, PF, Energy, unbalance |
Three phase inverter with two Array boxes (Na ≤ 2)
Typically, 60kW to 100kW grid-connected inverters with 2 arrays. Array cable protection is not necessary for 2 or 3 arrays.
The Isctc array ≤ 200A, Isctc ≤ 400A, and Imax AC ≤ 200A. A PV main switch is required close to the inverter. Remotely operated switches in array boxes allow disconnects to be located close to the PV modules in the event of emergencies.
Needs | String / Array junction box | PV array main switch | Inverter | AC box (400V) |
---|---|---|---|---|
Switchgears and control (Q) | ||||
- Isolation | • | •[d] | [a] | •[d] |
- Switching (Making & breaking rated current |
• DC21B |
•[d] DC21B |
[a] | •[d] |
- Control | • [b] | •[d] | [e] | •[d] |
- Over-current protection | • | [c] | •[f] | |
- Protection against Insulation fault |
[h] | [h] RCD type B or A SI | ||
Surge protection (SPD) | [g] | • type 2 | • type 1 or 2 | |
Enclosure (E) | Outdoor IP5x Double insulation |
Indoor IP5x Double insulation |
Standard AC requirement + grid code requirement | |
Metering | P, Q, PF, Energy |
[a] PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
[b] If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
[c] No protection is required when the number of arrays ≤ 3 (No cable sizing benefit)
[d] Service and emergency switching
[e] Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[f] Overload and short-circuit protection.
[g] If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.
If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
If the inverter provides at least simple separation
- Without functional earthing: insulation monitoring is necessary
- With functional earthing: the earthing shall be done with a DC MCB breaker (iC60PV 4P series 2 – 10A) or a fuse.
150kW to 500kW Grid connected PV system (Large building and farm)
Three phase inverter with more than two Array boxes
- Typically, 150kW to 500kW single inverter.
- This design is very similar to the previous one except that it has more arrays, which requires array cable protection.
- Istc <= 400A, IAC <= 600A.
Needs | String | Array junction box | Generator junction box | Inverter | AC box 400V or other voltage (Transfoless inverter) |
---|---|---|---|---|---|
Switchgears and control (Q) | |||||
- Isolation | • | • | • | [a] | •[d] |
- Switching (Making & breaking rated current |
• DC22A |
• DC22A |
•[a] | •[d] | |
- Control | •[b] | •[a][e] | •[d] | ||
- Over-current protection | • | •[c] | •[f] | ||
- Protection against Insulation fault |
•[h] | •[h] | |||
Surge protection (SPD) | [g] | • type 2 | • type 1 or 2 | ||
Enclosure (E) | Outdoor IP5x Double insulation |
Indoor Double insulation |
Standard AC requirement + grid code requirement | ||
Metering | P, Q, PF, Energy, Alarm, THD, individual harmonics |
[a] PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
[b] If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
[c] Array cable protection is recommended to prevent cable oversizing. To ensure fast trip of protections 6 to 8 arrays are recommended.
[d] Service and emergency switching
[e] Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
[f] Overload and short-circuit protection.
[g] If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.
[h] Galvanic insulation is provided by LV/MV transformer,
- PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700
- PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.
Multi three phases inverters design without array box
Typically 10x20 to 20x30kW grid connected inverters
Uoc max ≤ 1000V one or two string per inverter. IAC max 50A for one inverter.
Multi MW Grid connected PV system (Large building and farm)
- Typically 500kW-630kW inverters with LV/MV transformers and MV substation.
Needs | String | Array junction box | Generator junction box | Inverter | AC box 400V or other voltage (Transfoless inverter) | |
---|---|---|---|---|---|---|
Switchgears and control (Q) | DC side | AC side | ||||
- Isolation | • | • | •[a] | • | • | • |
- Switching
(Making & breaking |
• DC22A |
•[a] | •
DC22A or 23A |
•
AC1 |
• | |
- Control | •[b] | • | • | • | ||
- Over-current protection | • | •[c] | No | • | •[f] | |
- Protection against
Insulation fault |
•[h] | • | •[h] | |||
Surge protection (SPD) | [g] | • type 2 | [g] | • type 1 or 2 | ||
Enclosure (E) | Outdoor IP5x
Double insulation |
Indoor
Double insulation |
||||
Metering | Energy | P, Q, PF, Energy, Alarm, Power quality |
[a] PV array main switch is usually included in the inverter panel.
[b] If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
[c] Array cable protection is recommended to prevent cable oversizing. To ensure fast trip of protections 6 to 8 arrays are recommended.
[d] Overload and short-circuit protection.
[e] If there is no SPD in the inverter or if the between DC box and inverter >10m a SPD is necessary in this box.
[f] Galvanic insulation is provided by LV/MV transformer,
- PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700
- PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.