LED lamps and fixtures: Difference between revisions

From Electrical Installation Guide
m (added links to other languages)
(converted syntax for tables)
Line 11: Line 11:
'''Note:''' The power in Watts indicated on the LED module with a separated driver doesn’t include the power dissipated in the driver.
'''Note:''' The power in Watts indicated on the LED module with a separated driver doesn’t include the power dissipated in the driver.


{{TableStart|Tab1011|5col}}
{{tb-start|id=Tab1011|num=A9|title=Main characteristics of LED lamps & fixtures|cols=5}}
{| class="wikitable"
|-
|-
! rowspan="2" | Power demand (W) at 230 V  
! rowspan="2" | Power demand (W) at 230 V  
Line 33: Line 34:
|  
|  
* All lighting applications in all domains (housing,commercial and industrial building, infrastructure)
* All lighting applications in all domains (housing,commercial and industrial building, infrastructure)
|-
|}
{{TableEnd|Tab1011|A9|Main characteristics of LED lamps & fixtures}}


[[ru:Резистивные нагревательные приборы и лампы накаливания (традиционные и галогенные)]]
[[ru:Резистивные нагревательные приборы и лампы накаливания (традиционные и галогенные)]]
[[zh:电阻型加热设备和白炽灯 (普通灯或卤素灯)]]
[[zh:电阻型加热设备和白炽灯 (普通灯或卤素灯)]]

Revision as of 16:34, 20 December 2019


See also "Lighting circuits" for more details

A lamp or luminaire with LED technology is powered by a driver:

  • can be integrated into the bulb (tube or lamp for retrofit) : in this case refer to the power indicated on the lamp
  • if separated : in that case it is necessary to take into account the power dissipated in the driver and the power indicated for one or several associated LED modules.

This technology has a very short start-up time. On the other hand, the inrush current at the powering is generally much higher than for fluorescent lamp with electronic ballast.

Note: The power in Watts indicated on the LED module with a separated driver doesn’t include the power dissipated in the driver.

Fig. A9 – Main characteristics of LED lamps & fixtures
Power demand (W) at 230 V Power factor Starting Luminous efficiency (lumens/watt) Average timelife (h) Utilization
Inrush current Ip/In Inrush current time Full Time to start
3 to 400 W > 0.9 Up to 250 < 250 μs < 0.5 to 1 sec 100 to 140 20000 to 50000
  • All lighting applications in all domains (housing,commercial and industrial building, infrastructure)