Characterization of the lightning wave: Difference between revisions
m (1 revision imported: Migrated pages - Remove empty lines begin pages) |
Migrate2019 (talk | contribs) (removed links to Chinese wiki) |
||
Line 20: | Line 20: | ||
{{FigImage|DB422471|svg|J11|1.2/50 µs voltage wave}} | {{FigImage|DB422471|svg|J11|1.2/50 µs voltage wave}} | ||
Revision as of 17:50, 20 December 2019
Analysis of the phenomena allows definition of the types of lightning current and voltage waves.
- 2 types of current wave are considered by the IEC standards:
- 10/350 µs wave: to characterize the current waves from a direct lightning stroke (see Fig. J9);
- 8/20 µs wave: to characterize the current waves from an indirect lightning stroke (see Fig. J10).
These two types of lightning current wave are used to define tests on SPDs (IEC standard 61643-11) and equipment immunity to lightning currents.
The peak value of the current wave characterizes the intensity of the lightning stroke.
- The overvoltages created by lightning strokes are characterized by a 1.2/50 µs voltage wave (see Fig. J11).
This type of voltage wave is used to verify equipment's withstand to overvoltages of atmospheric origin (impulse voltage as per IEC 61000-4-5).