Example of lightning current in TT system: Difference between revisions

From Electrical Installation Guide
Home > Overvoltage protection > Surge protection technical supplements > Example of lightning current in TT system
m (r2.7.2) (robot Adding: zh:TT 系统中的雷电流举例)
m (1 revision imported: Migrated pages - removed CN links)
 
(10 intermediate revisions by 5 users not shown)
Line 1: Line 1:
{{Menu_Protection_against_voltage_surges_in_LV}}
{{Menu_Overvoltage_protection}}__TOC__
<br>
Common mode SPD between phase and PE or phase and PEN is installed whatever type of system earthing arrangement (see {{FigRef|J61}}).
__TOC__


The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation.


Common mode SPD between phase and PE or phase and PEN is installed whatever type of system earthing arrangement (see '''Fig. J55''').<br>The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation. <br>The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the Up voltage of the SPD (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases.  
The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the Up voltage of the SPD (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases.


----
{{FigImage|DB422526_EN|svg|J61|Common protection only}}


<br>[[Image:Fig J55 EN.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br>
To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced.


'''''Fig. J55:''' Common protection only''
Another SPD architecture is therefore used (see {{FigRef|J62}})


----
The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the SPD (Up2).


To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced.<br>Another SPD architecture is therefore used (see '''Fig. J56''')<br>The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the SPD (Up2).
{{FigImage|DB422527_EN|svg|J62|Common and differential protection}}
 
----
 
<br>[[Image:Fig J56 EN.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br>
 
'''''Fig. J56:''' Common and differential protection''
 
[[zh:TT 系统中的雷电流举例]]

Latest revision as of 17:50, 20 December 2019

Common mode SPD between phase and PE or phase and PEN is installed whatever type of system earthing arrangement (see Fig. J61).

The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation.

The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the Up voltage of the SPD (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases.

Fig. J61 – Common protection only

To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced.

Another SPD architecture is therefore used (see Fig. J62)

The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the SPD (Up2).

Fig. J62 – Common and differential protection
Share