Photovoltaic system: electrical equipments selection: Difference between revisions
From Electrical Installation Guide
m (1 revision imported: Migrated pages - Remove empty lines begin pages) |
Migrate2019 (talk | contribs) (removed links to Chinese wiki) |
(No difference)
|
Revision as of 17:52, 20 December 2019
Grid connected PV system ≤ 10kW (Residential)
One single phase inverter
- Typically, a 5kW grid-connected single-phase inverter. with UOC MAX ≤ 600V. One or two strings – Isctc < 25A, IAC < 32A. In this design there is no string protection.
- A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
10 to 100kW grid connected PV system (Small building)
One three phase inverter with one string combiner box
- Typically, 30kW to 60kW grid-connected inverters. UOC max is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A.
- This design has more than 2 strings.
- Reverse current protection is therefore necessary.
- A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.
Multi single phase inverters design
- Typically, 6x5 to 20x5kW grid-connected inverters.
- The design used for residential building can be duplicated as often as necessary.
- In that case, the DC system is very simple and the AC system is very similar to usual AC systems.
150kW to 500kW Grid connected PV system (Large building and farm)
Three phase inverter with more than two string combiner boxes
- Typically, 150kW to 500kW single inverter.
- This design is very similar to the three phase inverter with one string combiner box except that it has more arrays, which requires array cable protection.
- Istc <= 400A, IAC <= 600A.