Photovoltaic system: electrical equipments selection: Difference between revisions

From Electrical Installation Guide
Home > PhotoVoltaic (PV) installation > Photovoltaic installation architectures > Photovoltaic system: electrical equipments selection
(added content related to Fig P25 (guide 2013))
m (1 revision imported: Migrated pages - removed CN links)
 
(39 intermediate revisions by 6 users not shown)
Line 1: Line 1:
{{Menu_Photovoltaic_installations}}
{{Menu_Photovoltaic_installations}}__TOC__
 
== Grid connected PV system 10kW (Residential)  ==
'''''(page to be completed)'''''
 
__TOC__
 
== Grid connected PV system <= 10kW (Residential)  ==


=== One single phase inverter ===
=== One single phase inverter ===


*Typically, a 5kW grid-connected single-phase inverter. with UOC MAX ≤ 600V.  
* Typically, a 5kW grid-connected single-phase inverter. with UOC MAX &le; 600V. One or two strings – Isctc < 25A, IAC < 32A. In this design there is no string protection.  
*One or two strings – Isctc < 25A, IAC < 32A.  
* A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
*In this design there is no string protection.  
*A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
 
[[Image:Fig P22.png|none]]
 
{| width="800px" valign="top" border="1"
|-
! align="left"  width="180px" | Needs
! align="center" width="110px" | String junction box
! align="center" width="180px" | PV array main switch
! align="center" width="160px" | Inverter
! align="center" width="170px" | AC box (400V)
|- bgcolor="#79C68C" align="center"
| align="left" colspan="5" | '''Switchgears and control (Q)'''
|- bgcolor="#79C68C" align="center"
| align="left" | - Isolation || • || • (d) || (a) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Control || • (b) || • (d) || (e) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Over-current protection || (c) ||  ||  || • (f)
|- bgcolor="#79C68C" align="center"
| align="left" | - Protection against<br>Insulation fault ||  ||  || (h) || (h)<br>RCD type B or A SI
|- bgcolor="#A6D6AE" align="center"
| align="left" | '''Surge protection (SPD)''' ||  || • type 2 ||  || • type 1 or 2
|- bgcolor="#D1D3D4" align="center"
| align="left" | '''Enclosure (E)''' || Outdoor<br>Double insulation || Indoor<br>Double insulation || || Standard AC requirement +<br>grid code requirement
|- bgcolor="#FFFFFF" align="center"
| align="left" | '''Metering''' || ||  || Inverter relevant parameters || Energy
|}
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.<br>
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.<br>
(c) No protection is required when the number of string does not exceed 2.<br>
(d) Service and emergency switching<br>
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
(f) Overload and short-circuit protection B curve recommended.<br>
(g) This SPD could be unnecessary if there is another SPD in the AC installation at a distance of less than 10 metres.<br>
(h) If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI<br>
 
'''''Fig. P22 :''''' ''10-100kW single multi MPPT inverter''


{{FigImage|DB422723_EN|svg|P22|Grid connected <{{=}} 10kW}}


== 10 to 100kW grid connected PV system (Small building) ==


== 10 to 100kW grid connected PV system (Small building)==
=== One three phase inverter with one string combiner box ===


=== One three phase multi input inverter without array box ===
* Typically, 30kW to 60kW grid-connected inverters. U<sub>OC max</sub> is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A.  
 
* Typically, 10kW to 36kW grid-connected inverters, UOC MAX probably higher than 600V (i.e. 800V or 1000V), Isctc < 125A, Iac < 63A.
* In this range of power, inverters usually have between 2 and 4 maximum power point tracking (MPPT) inputs, so the number of strings in the same DC sub-network is equal to one or two.
* There is no need for string protection.
* A PV main switch for each MPPT input is necessary.
* When an inverter is indoors, additional remote-controlled switches at DC cable entry point are recommended for emergencies services.
 
[[Image:Fig P23.png|none]]
 
{| width="800px" valign="top" border="1"
|-
! align="left"  width="170px" | Needs
! align="center" width="145px" | String junction box
! align="center" width="165px" | PV array main switch
! align="center" width="135px" | Inverter
! align="center" width="185px" | AC box (400V)
|- bgcolor="#79C68C" align="center"
| align="left" colspan="5" | '''Switchgears and control (Q)'''
|- bgcolor="#79C68C" align="center"
| align="left" | - Isolation || • || • (d) || (a) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Control || • (b) || • (d) || (e) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Over-current protection || (c) ||  ||  || • (f)
|- bgcolor="#79C68C" align="center"
| align="left" | - Protection against<br>Insulation fault ||  ||  || (h) || (h)<br>RCD type B or A SI
|- bgcolor="#A6D6AE" align="center"
| align="left" | '''Surge protection (SPD)''' ||  || • type 2 ||  || • type 1 or 2
|- bgcolor="#D1D3D4" align="center"
| align="left" | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || Indoor IP5x<br>Double insulation || || Standard AC requirement +<br>grid code requirement
|- bgcolor="#FFFFFF" align="center"
| align="left" | '''Metering''' || ||  ||  || Energy
|}
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.<br>
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.<br>
(c) No protection is required when the number of string does not exceed 2.<br>
(d) Service and emergency switching<br>
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
(f) Overload and short-circuit protection (B curve recommended).<br>
(g) If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.<br>
(h)
*If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
*If the inverter provides at least simple separation
** Without functional earthing: insulation monitoring is necessary, it's usually done by the inverter in this range of power.
** With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.
 
'''''Fig. P23 :''''' ''10-100kW single multi MPPT inverter''
 
 
=== One three phases inverter with One Array box ===
 
* Typically, 30kW to 60kW grid-connected inverters. UOC max is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A.  
* This design has more than 2 strings.
* This design has more than 2 strings.
* Reverse current protection is therefore necessary.  
* Reverse current protection is therefore necessary.  
* A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.
* A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.


[[Image:Fig P24.png|none]]
{{FigImage|DB422725_EN|svg|P23|10-100kW single MPPT inverter}}
 
{| width="800px" valign="top" border="1"
|-
! align="left"  width="160px" | Needs
! align="center" width="135px" | String / Array junction box
! align="center" width="160px" | PV array main switch
! align="center" width="145px" | Inverter
! align="center" width="200px" | AC box (400V)
|- bgcolor="#79C68C" align="center"
| align="left" colspan="5" | '''Switchgears and control (Q)'''
|- bgcolor="#79C68C" align="center"
| align="left" | - Isolation || • || • (d) || (a) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • (d)<br>DC21B || (a) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Control || • (b) || • (d) || (e) || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | - Over-current protection || • || (c) ||  || • (f)
|- bgcolor="#79C68C" align="center"
| align="left" | - Protection against<br>Insulation fault ||  ||  || (h) || (h)<br>RCD type B or A SI
|- bgcolor="#A6D6AE" align="center"
| align="left" | '''Surge protection (SPD)''' ||  || • type 2 ||  || • type 1 or 2
|- bgcolor="#D1D3D4" align="center"
| align="left" | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || Indoor IP5x<br>Double insulation || || Standard AC requirement +<br>grid code requirement
|- bgcolor="#FFFFFF" align="center"
| align="left" | '''Metering''' || ||  ||  || P, Q, PF, Energy
|}
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.<br>
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building. The main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing for that purpose.<br>
(d) Service and emergency switching<br>
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
(f) Overload and short-circuit protection (B curve recommended).<br>
(g) If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.<br>
(h)
* If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI.
* If the inverter provides at least simple separation
** Without functional earthing: insulation monitoring is necessary
** With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.
 
'''''Fig. P24 :''''' ''10-100kW single MPPT inverter''
 


=== Multi single phase inverters design ===
=== Multi single phase inverters design ===
Line 165: Line 26:
* In that case, the DC system is very simple and the AC system is very similar to usual AC systems.
* In that case, the DC system is very simple and the AC system is very similar to usual AC systems.


[[Image:Fig P25.png|none]]
{{FigImage|DB422726_EN|svg|P24|10-100kW multi single MPPT inverter}}
 
== 150kW to 500kW Grid connected PV system (Large building and farm)  ==
 
=== Three phase inverter with more than two string combiner boxes ===
 
* Typically, 150kW to 500kW single inverter.
* This design is very similar to the three phase inverter with one string combiner box except that it has more arrays, which requires array cable protection.
* Istc <= 400A, IAC <= 600A.


{| width="800px" valign="top" border="1"
{{FigImage|DB422728_EN|svg|P25|150-500kW single MPPT inverter with N arrays > 2}}
|-
! align="left"  width="170px" | Needs
! align="center" width="120px" | PV array<br>main switch
! align="center" width="140px" | Inverter
! align="center" width="180px" |
! align="center" width="190px" | AC box (400V)
|- bgcolor="#79C68C" align="center"
| align="left" | '''Switchgears and control (Q)''' || See 5kW<br>design || || (h)  || • (d)
|- bgcolor="#79C68C" align="center"
| align="left" | '''Surge protection (SPD)''' || • type 2 ||  ||  || • type 1 or 2
|- bgcolor="#D1D3D4" align="center"
| align="left" | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || || || Standard AC requirement +<br>grid code requirement
|- bgcolor="#FFFFFF" align="center"
| align="left" | '''Metering''' || ||  || Energy || P,Q, PF, Energy, unbalance
|}
(h) If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI<br>
'''''Fig. P25 :''''' ''10-100kW multi single MPPT inverter''

Latest revision as of 17:52, 20 December 2019

Grid connected PV system ≤ 10kW (Residential)

One single phase inverter

  • Typically, a 5kW grid-connected single-phase inverter. with UOC MAX ≤ 600V. One or two strings – Isctc < 25A, IAC < 32A. In this design there is no string protection.
  • A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
Fig. P22 – Grid connected <= 10kW

10 to 100kW grid connected PV system (Small building)

One three phase inverter with one string combiner box

  • Typically, 30kW to 60kW grid-connected inverters. UOC max is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A.
  • This design has more than 2 strings.
  • Reverse current protection is therefore necessary.
  • A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.
Fig. P23 – 10-100kW single MPPT inverter

Multi single phase inverters design

  • Typically, 6x5 to 20x5kW grid-connected inverters.
  • The design used for residential building can be duplicated as often as necessary.
  • In that case, the DC system is very simple and the AC system is very similar to usual AC systems.
Fig. P24 – 10-100kW multi single MPPT inverter

150kW to 500kW Grid connected PV system (Large building and farm)

Three phase inverter with more than two string combiner boxes

  • Typically, 150kW to 500kW single inverter.
  • This design is very similar to the three phase inverter with one string combiner box except that it has more arrays, which requires array cable protection.
  • Istc <= 400A, IAC <= 600A.
Fig. P25 – 150-500kW single MPPT inverter with N arrays > 2
Share