Protection of LV/LV transformers: Difference between revisions
m (1 revision imported: Migrated pages - removed CN links) |
(content update 2021 - copied from PPR-EN - also uploaded 2 modified images) |
||
(One intermediate revision by the same user not shown) | |||
Line 1: | Line 1: | ||
{{Menu_Characteristics_of_particular_sources_and_loads}} | {{Menu_Characteristics_of_particular_sources_and_loads}} | ||
LV/LV transformers are generally in the range of several hundreds of VA to some hundreds of kVA and are frequently used for: | |||
* Changing the low voltage level for: | * Changing the low voltage level for: | ||
** Auxiliary supplies to control and indication circuits | ** Auxiliary supplies to control and indication circuits | ||
** Lighting circuits (230 V created when the primary system is 400 V 3-phase 3-wires) | ** Lighting circuits (230 V created when the primary system is 400 V 3-phase 3-wires) | ||
* Changing the | * Changing the earthing system for certain application such as safety services, medical IT, or certain loads having a relatively high capacitive current to earth (computer equipment) or resistive leakage current (electric ovens, industrial-heating processes, mass-cooking installations, etc.) | ||
LV/LV | LV/LV transformer shall be protected against short-circuit and overloads. | ||
{{Highlightbox|text= | |||
When energized, a LV/LV transformer draws [[#Transformer-energizing inrush current|a very high inrush current]]. This very high inrush current (and its time/current characteristics) should be taken into account when [[#Protection for the supply circuit of a LV/LV transformer|selecting the overcurrent protection]], to avoid nuisance tripping.}} | |||
'''Notes''': | |||
*LV/LV transformers may be supplied with embedded protective systems, such as over-temperature sensors. Refer to transformer manufacturer documentation. | |||
*In the particular cases of LV/LV safety isolating transformers at extra-low voltage, an earthed metal screen between the primary and secondary windings is frequently required, according to circumstances, as recommended in European Standard EN 60742. | |||
[[ | ==Transformer-energizing inrush current== | ||
When energized, LV/LV transformers draw very high inrush currents which must be taken into account when choosing overcurrent protection devices. (see {{FigRef|N33}}) | |||
The peak value of the first current wave often reaches 10 to 15 times the rated rms current of the transformer, and may even reach values of 20 to 25 times the rated current for transformers < 50 kVA. This transient current decreases rapidly, with a time constant 𝜏 of the order of several ms to severals tens of ms. | |||
This can be compared to the maximum short-circuit current, which is the nominal current divided by the short circuit impedance voltage of the transformer in %. For example, when the short circuit impedance voltage is 5%, the short circuit current is In / 5% = 20 In, e.g. the same order of magnitude as the transformer energizing inrush current. The main difference is that the inrush current when energizing decreases very fast. | |||
{{FigImage|DB422663_EN|svg|N33|Transformer-energizing inrush current}} | |||
Note: the actual magnitude of the current peak can vary a lot, and depends on: | |||
*The value of voltage at the instant of energization | |||
*The magnitude and polarity of the residual flux existing in the core of the transformer | |||
*The characteristics of the load connected to the transformer | |||
==Protection for the supply circuit of a LV/LV transformer== | |||
The [[#Protection of LV/LV transformers, using Schneider Electric circuit-breakers|selection of the protective device for the supply circuit of a LV/LV transformer]] must avoid the possibility of incorrect operation due to the inrush current when enegizing the transformer, described above. It is therefore necessary to use: | |||
===Selective (i.e. slighly time-delayed) circuit-breakers, such as Compact NSX with electronic trip-unit=== | |||
(see {{FigRef|N34}}) | |||
{{FigImage|DB422664_EN|svg|N34|Tripping characteristic of a Compact NSX with electronic trip-unit}} | |||
Where: | |||
* I<sub>n</sub> = nominal current of the transformer, | |||
* I<sub>r</sub> = Long Time Protection (overload) setting of the circuit breaker | |||
* I<sub>sd</sub>, t<sub>sd</sub> = Short-Time Protection (short-circuit) setting of the circuit breaker, which should be selected according to the time/current characteristics of the transformer energizing inrush current, | |||
* I<sub>i</sub> = Instantaneous Protection (short-circuit) setting of the circuit-breaker | |||
===Circuit-breakers having a very high magnetic-trip setting, such as Compact NSX with TMD thermal-magnetic trip unit or Acti 9 curve D=== | |||
(see {{FigRef|N35}}) | |||
{{FigImage|DB422665_EN|svg|N35|Tripping characteristic of a Acti 9 curve D}} | |||
=== Example === | |||
(see {{FigRef|N36}}) | |||
A 400 V 3-phase circuit is supplying a 125 kVA 400/230 V transformer (In = 180 A) for which the first inrush current peak can reach 12 In (value provided by the transformer manufacturer), i.e. 12 x 180 = 2160 A. | |||
This current peak value corresponds to a thermal equivalent rms value of 2160 / √2 = 1530 A. | |||
A Compact NSX250N circuit-breaker with I<sub>r</sub> setting of 200 A and I<sub>sd</sub> setting at 8 x I<sub>r</sub> (= 1600 A) would therefore be a suitable protective device. | |||
{{FigImage|DB422666_EN|svg|N36|Example}} | |||
==Typical electrical characteristics of LV/LV 50 Hz transformers== | |||
These values are given as an example, always refer to the manufacturer's technical data. | |||
{{tb-start|id=Tab1366a|num=|title=|cols=4}} | |||
{| class="wikitable" | |||
|- | |||
! colspan="24" | 3-phase (≤ 80A) | |||
|- | |||
| style= "width: 110px;" | kVA rating|| 5 || 6.3 || 8 || 10 || 12.5 || 16 || 20 || 25 || 31.5 || 40 || 50 || 63 || 80 | |||
|- | |||
| No-load losses (W) || 100 || 110 || 130 || 150 || 160 || 170 || 270 || 310 || 350 || 350 || 410 || 460 || 520 | |||
|- | |||
| Load loss at rated power (W) || 250 || 320 || 390 || 500 || 600 || 840 || 800 || 1180 || 1240 || 1530 || 1650 || 2150 || 2540 | |||
|- | |||
| Short-circuit voltage (%) || 4.5 || 4.5 || 4.5 || 5.5 || 5.5 || 5.5 || 5.5 || 5.5 || 5 || 5 || 4.5 || 5 || 5 | |||
|} | |||
{{tb-start|id=Tab1366b|num=|title=|cols=4}} | |||
{| class="wikitable" | |||
|- | |||
! colspan="24" | 3-phase (≥ 100A) | |||
|- | |||
| style= "width: 110px;" | kVA rating|| 100 || 125 || 160 || 200 || 250 || 315 || 400 || 500 || 630 || 800 | |||
|- | |||
| No-load losses (W) || 570 || 680 || 680 || 790 || 950 || 1160 || 1240 || 1485 || 1855 || 2160 | |||
|- | |||
| Load loss at rated power (W) || 3700 || 3700 || 5900 || 5900 || 6500 || 7400 || 9300 || 9400 || 11400 || 13400 | |||
|- | |||
| Short-circuit voltage (%) || 5.5 || 4.5 || 5.5 || 5 || 5 || 4.5 || 6 || 6 || 5.5 || 5.5 | |||
|} | |||
{{tb-start|id=Tab1367|num=|title=|cols=4}} | |||
{| class="wikitable" | |||
|- | |||
! colspan="15" | 1-phase | |||
|- | |||
| style= "width: 110px;" | kVA rating | |||
| 8 | |||
| 10 | |||
| 12.5 | |||
| 16 | |||
| 20 | |||
| 25 | |||
| 31.5 | |||
| 40 | |||
| 50 | |||
| 63 | |||
| 80 | |||
| 100 | |||
| 125 | |||
| 160 | |||
|- | |||
| No-load losses (W) | |||
| 105 | |||
| 115 | |||
| 120 | |||
| 140 | |||
| 150 | |||
| 175 | |||
| 200 | |||
| 215 | |||
| 265 | |||
| 305 | |||
| 450 | |||
| 450 | |||
| 525 | |||
| 635 | |||
|- | |||
| Load loss at rated power (W) | |||
| 400 | |||
| 530 | |||
| 635 | |||
| 730 | |||
| 865 | |||
| 1065 | |||
| 1200 | |||
| 1400 | |||
| 1900 | |||
| 2000 | |||
| 2450 | |||
| 3950 | |||
| 3950 | |||
| 4335 | |||
|- | |||
| Short-circuit voltage (%) | |||
| 5 | |||
| 5 | |||
| 5 | |||
| 4.5 | |||
| 4.5 | |||
| 4.5 | |||
| 4 | |||
| 4 | |||
| 5 | |||
| 5 | |||
| 4.5 | |||
| 5.5 | |||
| 5 | |||
| 5 | |||
|} | |||
==Protection of LV/LV transformers, using Schneider Electric circuit-breakers== | |||
For up-to-date tables to choose the appropriate circuit breaker for protection of LV/LV transformers, refer to the latest [https://www.se.com/ww/en/download/document/LVPED318033EN/ Complementary Technical Information - Selectivity, Cascading and Coordination Guide]. |
Latest revision as of 16:51, 29 October 2021
LV/LV transformers are generally in the range of several hundreds of VA to some hundreds of kVA and are frequently used for:
- Changing the low voltage level for:
- Auxiliary supplies to control and indication circuits
- Lighting circuits (230 V created when the primary system is 400 V 3-phase 3-wires)
- Changing the earthing system for certain application such as safety services, medical IT, or certain loads having a relatively high capacitive current to earth (computer equipment) or resistive leakage current (electric ovens, industrial-heating processes, mass-cooking installations, etc.)
LV/LV transformer shall be protected against short-circuit and overloads.
When energized, a LV/LV transformer draws a very high inrush current. This very high inrush current (and its time/current characteristics) should be taken into account when selecting the overcurrent protection, to avoid nuisance tripping.
Notes:
- LV/LV transformers may be supplied with embedded protective systems, such as over-temperature sensors. Refer to transformer manufacturer documentation.
- In the particular cases of LV/LV safety isolating transformers at extra-low voltage, an earthed metal screen between the primary and secondary windings is frequently required, according to circumstances, as recommended in European Standard EN 60742.
Transformer-energizing inrush current
When energized, LV/LV transformers draw very high inrush currents which must be taken into account when choosing overcurrent protection devices. (see Fig. N33)
The peak value of the first current wave often reaches 10 to 15 times the rated rms current of the transformer, and may even reach values of 20 to 25 times the rated current for transformers < 50 kVA. This transient current decreases rapidly, with a time constant 𝜏 of the order of several ms to severals tens of ms.
This can be compared to the maximum short-circuit current, which is the nominal current divided by the short circuit impedance voltage of the transformer in %. For example, when the short circuit impedance voltage is 5%, the short circuit current is In / 5% = 20 In, e.g. the same order of magnitude as the transformer energizing inrush current. The main difference is that the inrush current when energizing decreases very fast.
Note: the actual magnitude of the current peak can vary a lot, and depends on:
- The value of voltage at the instant of energization
- The magnitude and polarity of the residual flux existing in the core of the transformer
- The characteristics of the load connected to the transformer
Protection for the supply circuit of a LV/LV transformer
The selection of the protective device for the supply circuit of a LV/LV transformer must avoid the possibility of incorrect operation due to the inrush current when enegizing the transformer, described above. It is therefore necessary to use:
Selective (i.e. slighly time-delayed) circuit-breakers, such as Compact NSX with electronic trip-unit
(see Fig. N34)
Where:
- In = nominal current of the transformer,
- Ir = Long Time Protection (overload) setting of the circuit breaker
- Isd, tsd = Short-Time Protection (short-circuit) setting of the circuit breaker, which should be selected according to the time/current characteristics of the transformer energizing inrush current,
- Ii = Instantaneous Protection (short-circuit) setting of the circuit-breaker
Circuit-breakers having a very high magnetic-trip setting, such as Compact NSX with TMD thermal-magnetic trip unit or Acti 9 curve D
(see Fig. N35)
Example
(see Fig. N36)
A 400 V 3-phase circuit is supplying a 125 kVA 400/230 V transformer (In = 180 A) for which the first inrush current peak can reach 12 In (value provided by the transformer manufacturer), i.e. 12 x 180 = 2160 A.
This current peak value corresponds to a thermal equivalent rms value of 2160 / √2 = 1530 A.
A Compact NSX250N circuit-breaker with Ir setting of 200 A and Isd setting at 8 x Ir (= 1600 A) would therefore be a suitable protective device.
Typical electrical characteristics of LV/LV 50 Hz transformers
These values are given as an example, always refer to the manufacturer's technical data.
3-phase (≤ 80A) | |||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
kVA rating | 5 | 6.3 | 8 | 10 | 12.5 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | ||||||||||
No-load losses (W) | 100 | 110 | 130 | 150 | 160 | 170 | 270 | 310 | 350 | 350 | 410 | 460 | 520 | ||||||||||
Load loss at rated power (W) | 250 | 320 | 390 | 500 | 600 | 840 | 800 | 1180 | 1240 | 1530 | 1650 | 2150 | 2540 | ||||||||||
Short-circuit voltage (%) | 4.5 | 4.5 | 4.5 | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 | 5 | 5 | 4.5 | 5 | 5 |
3-phase (≥ 100A) | |||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
kVA rating | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 800 | |||||||||||||
No-load losses (W) | 570 | 680 | 680 | 790 | 950 | 1160 | 1240 | 1485 | 1855 | 2160 | |||||||||||||
Load loss at rated power (W) | 3700 | 3700 | 5900 | 5900 | 6500 | 7400 | 9300 | 9400 | 11400 | 13400 | |||||||||||||
Short-circuit voltage (%) | 5.5 | 4.5 | 5.5 | 5 | 5 | 4.5 | 6 | 6 | 5.5 | 5.5 |
1-phase | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
kVA rating | 8 | 10 | 12.5 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 100 | 125 | 160 |
No-load losses (W) | 105 | 115 | 120 | 140 | 150 | 175 | 200 | 215 | 265 | 305 | 450 | 450 | 525 | 635 |
Load loss at rated power (W) | 400 | 530 | 635 | 730 | 865 | 1065 | 1200 | 1400 | 1900 | 2000 | 2450 | 3950 | 3950 | 4335 |
Short-circuit voltage (%) | 5 | 5 | 5 | 4.5 | 4.5 | 4.5 | 4 | 4 | 5 | 5 | 4.5 | 5.5 | 5 | 5 |
Protection of LV/LV transformers, using Schneider Electric circuit-breakers
For up-to-date tables to choose the appropriate circuit breaker for protection of LV/LV transformers, refer to the latest Complementary Technical Information - Selectivity, Cascading and Coordination Guide.