Selection of a circuit-breaker: Difference between revisions

From Electrical Installation Guide
Home > LV switchgear: functions and selection > Circuit-breaker > Selection of a circuit-breaker
(Cleanup_2016)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(29 intermediate revisions by 4 users not shown)
Line 1: Line 1:
{{Menu_LV_switchgear_functions_and_selection}}
{{Menu_LV_switchgear_functions_and_selection}}__TOC__
 
__TOC__
 
{{Highlightbox|
{{Highlightbox|
The choice of a range of circuit-breakers is determined by: the electrical characteristics of the installation, the environment, the loads and a need for remote control, together with the type of telecommunications system envisaged}}
The choice of a range of circuit-breakers is determined by: the electrical characteristics of the installation, the environment, the loads and a need for remote control, together with the type of telecommunications system envisaged}}
Line 8: Line 5:
== Choice of a circuit-breaker ==
== Choice of a circuit-breaker ==


The choice of a CB is made in terms of:  
The choice of a CB is made in terms of:
*Electrical characteristics of the installation for which the CB is intended  
* Electrical characteristics (AC or DC, Voltage...) of the installation for which the CB is intended
*Its eventual environment: ambient temperature, in a kiosk or switchboard enclosure, climatic conditions, etc.  
* Its environment: ambient temperature, in a kiosk or switchboard enclosure, climatic conditions, etc.
*Short-circuit current breaking and making requirements
* Presumed short-circuit current at the point of installation
*Operational specifications: discriminative tripping, requirements (or not) for remote control and indication and related auxiliary contacts, auxiliary tripping coils, connection  
* Characteristics of the protected cables, busbars, busbar trunking system and application (distribution, motor...)
*Installation regulations; in particular: protection of persons
* [[Coordination between circuit-breakers|Co-ordination with upstream and/or downstream device]]: selectivity, cascading, coordination with switch disconnector, contactor...
*Load characteristics, such as motors, fluorescent lighting, LED ligthing, LV/LV transformers
* Operational specifications: requirements (or not) for remote control and indication and related auxiliary contacts, auxiliary tripping coils, connection  
* Installation regulations; in particular: protection against electric shock and thermal effect (See [[Protection against electric shocks and electric fires]])
* Load characteristics, such as motors, fluorescent lighting, LED ligthing, LV/LV transformers


The following notes relate to the choice LV circuit-breaker for use in distribution systems.  
The following notes relate to the choice LV circuit breaker for use in distribution systems.


== Choice of rated current in terms of ambient temperature  ==
== Choice of rated current in terms of ambient temperature  ==


The rated current of a circuit-breaker is defined for operation at a given ambient temperature, in general:  
The rated current of a circuit breaker is defined for operation at a given ambient temperature, in general:
*30°C for domestic-type CBs  
* 30°C for domestic-type CBs according to IEC 60898 series
*40°C for industrial-type CBs
* 40°C by default for industrial-type CBs, according to IEC 60947 series. Different value may be proposed however.


Performance of these CBs in a different ambient temperature depends mainly on the technology of their tripping units (see {{FigRef|H40}}).  
Performance of these CBs in a different ambient temperature depends mainly on the technology of their tripping units (see {{FigRef|H37}}).  


{{FigImage|DB422415_EN|svg|H40|Ambient temperature}}
{{FigImage|DB422415_EN|svg|H37|Ambient temperature}}


== Uncompensated thermal magnetic tripping units  ==
== Uncompensated thermal magnetic tripping units  ==
Line 33: Line 32:
Circuit-breakers with uncompensated thermal tripping units have a trip current level that depends on the surrounding temperature}}
Circuit-breakers with uncompensated thermal tripping units have a trip current level that depends on the surrounding temperature}}


Circuit-breakers with uncompensated thermal tripping elements have a tripping-current level that depends on the surrounding temperature. If the CB is installed in an enclosure, or in a hot location (boiler room, etc.), the current required to trip the CB on overload will be sensibly reduced. When the temperature in which the CB is located exceeds its reference temperature, it will therefore be “derated”. For this reason, CB manufacturers provide tables which indicate factors to apply at temperatures different to the CB reference temperature. It may be noted from typical examples of such tables (see {{FigRef|H41}}) that a lower temperature than the reference value produces an up-rating of the CB. Moreover, small modular-type CBs mounted in juxtaposition, as shown typically in {{FigureRef|H27}}, are usually mounted in a small closed metal case. In this situation, mutual heating, when passing normal load currents, generally requires them to be derated by a factor of 0.8.
Circuit-breakers with uncompensated thermal tripping elements have a tripping-current level that depends on the surrounding temperature. If the CB is installed in an enclosure, or in a hot location (boiler room, etc.), the current required to trip the CB on overload will be sensibly reduced. When the temperature in which the CB is located exceeds its reference temperature, it will therefore be “derated”. For this reason, CB manufacturers provide tables which indicate factors to apply at temperatures different to the CB reference temperature. It may be noted from typical examples of such tables (see {{FigRef|H39}}) that a lower temperature than the reference value produces an up-rating of the CB. Moreover, small modular-type CBs mounted in juxtaposition, as shown typically in {{FigureRef|H24}}, are usually mounted in a small closed metal case. In this situation, mutual heating, when passing normal load currents, generally requires them to be derated by a factor of 0.8.


=== Example ===
'''Example'''


What rating (In) should be selected for a iC60 N?  
What rating (In) should be selected for a iC60 N?  
Line 41: Line 40:
*Protecting a circuit, the maximum load current of which is estimated to be 34 A  
*Protecting a circuit, the maximum load current of which is estimated to be 34 A  
*Installed side-by-side with other CBs in a closed distribution box  
*Installed side-by-side with other CBs in a closed distribution box  
*In an ambient temperature of 50 °C
*In an ambient temperature of 60 °C


A iC60N circuit-breaker rated at 40 A would be derated to 35.6 A in ambient air at 50°C (see {{FigRef|H41}}). To allow for mutual heating in the enclosed space, however, the 0.8 factor noted above must be employed, so that, 35.6 x 0.8 = 28.5 A, which is not suitable for the 34 A load.
A iC60N circuit breaker rated at 40 A would be derated to 38.2 A in ambient air at 60°C (see {{FigureRef|H39}}). To allow for mutual heating in the enclosed space, however, the 0.8 factor noted above must be employed, so that, 38.2 x 0.8 = 30.5 A, which is not suitable for the 34 A load.


A 50 A circuit-breaker would therefore be selected, giving a (derated) current rating of 44 x 0.8 = 35.2 A.  
A 50 A circuit breaker would therefore be selected, giving a (derated) current rating of 47.6 x 0.8 = 38 A.


== Compensated thermal-magnetic tripping units  ==
== Compensated thermal-magnetic tripping units  ==
Line 55: Line 54:
*LV circuit-breakers at ratings ≤ 630 A are commonly equipped with compensated tripping units for this range (- 5 °C to + 40 °C)
*LV circuit-breakers at ratings ≤ 630 A are commonly equipped with compensated tripping units for this range (- 5 °C to + 40 °C)


=== Examples of tables for the determination of derating/uprating factors to apply to CBs with uncompensated thermal tripping units, according to temperature ===
== Examples of tables giving the derated/uprated current values according to temperature, for circuit-breakers with uncompensated thermal tripping units ==


{{TableStart|Tab1270|3col}}
{{Highlightbox|
Circuit breaker thermal characteristics are given considering the section and type of conductor (Cu or Al) according to IEC60947-1 Table 9 & 10 and IEC60898-1 & 2 Table 10 }}
 
=== iC60 (IEC 60947-2) ===
 
{{tb-start|id=Tab1270a|num=H38|title=iC60 (IEC 60947-2) - derated/uprated current values according to ambient temperature|cols=3}}
{| class="wikitable"
! Rating || colspan="13" | Ambient temperature (°C)
|-
!  (A) ||  10  || 15 ||  20 ||  25 ||  30 ||  35 ||  40 ||  45 ||  50  || 55 ||  60  || 65  || 70
|-
|-
! Rating (A)
| 0.5  || 0.58  || 0.57 ||  0.56 ||  0.55 ||  0.54 ||  0.53  || 0.52  || 0.51  || {{tb-HC1}} | 0.5  || 0.49 ||  0.48  || 0.47 ||  0.45
! 20 °C
! 25 °C
! 30 °C
! 35 °C
! 40 °C
! 45 °C
! 50 °C
! 55 °C
! 60 °C
|-
|-
| 1  
| 1 || 1.16 ||  1.14 ||  1.12 || 1.1  || 1.08  || 1.06 || 1.04 || 1.02 || {{tb-HC1}} | 1  || 0.98 || 0.96 || 0.93  || 0.91
| 1.05
| 1.02
| 1.00
| 0.98
| 0.95
| 0.93
| 0.90
| 0.88
| 0.85
|-
|-
| 2  
| 2 ||  2.4 ||  2.36 || 2.31 || 2.26  || 2.21 ||  2.16  || 2.11  || 2.05  || {{tb-HC1}} |2  || 1.94  || 1.89 |1.83  || 1.76
| 2.08
| 2.04
| 2.00
| 1.96
| 1.92
| 1.88
| 1.84
| 1.80
| 1.74
|-
|-
| 3  
| 3 || 3.62 |3.55 |3.48 ||  3.4 ||  3.32 ||  3.25 ||  3.17  || 3.08  || {{tb-HC1}} |3 ||  2.91 |2.82 || 2.73 || 2.64
| 3.18
| 3.09
| 3.00
| 2.91  
| 2.82  
| 2.70
| 2.61
| 2.49
| 2.37
|-
|-
| 4  
| 4 || 4.83 ||  4.74  || 4.64  || 4.54 ||  4.44 || 4.33 |4.22 ||  4.11 ||  {{tb-HC1}} |4 |3.88 |3.76 || 3.64 || 3.51
| 4.24
| 4.12
| 4.00
| 3.88  
| 3.76  
| 3.64  
| 3.52
| 3.36
| 3.24
|-
|-
| 6  
| 6 || 7.31 ||  7.16  || 7.01 ||  6.85  || 6.69  || 6.52 || 6.35 || 6.18 || {{tb-HC1}} | 6 || 5.81 |5.62 || 5.43 || 5.22
| 6.24
| 6.12
| 6.00
| 5.88
| 5.76
| 5.64
| 5.52
| 5.40
| 5.30
|-
|-
| 10  
| 10 ||  11.7  || 11.5 ||  11.3 ||  11.1 ||  10.9 |10.7 || 10.5 ||  10.2 || {{tb-HC1}} | 10 |9.8 |9.5 ||  9.3 || 9
| 10.6
| 10.3
| 10.0
| 9.70
| 9.30
| 9.00
| 8.60
| 8.20
| 7.80
|-
|-
| 16
| 13 ||  15.1  || 14.8 || 14.6 || 14.3 || 14.1 |13.8 ||  13.6 ||  13.3 || {{tb-HC1}} | 13 ||  12.7 ||  12.4  || 12.1 ||  11.8
| 16.8
| 16.5
| 16.0
| 15.5
| 15.2
| 14.7
| 14.2
| 13.8  
| 13.5
|-
|-
| 20
| 16 || 18.6 || 18.|| 18 ||  17.7 || 17.3 || 17 ||  16.7 || 16.3 || {{tb-HC1}} | 16 ||  15.7 ||  15.3  || 14.9 ||  14.5
| 21.0
| 20.6  
| 20.0
| 19.4
| 19.0
| 18.4
| 17.8
| 17.4
| 16.8
|-
|-
| 25
| 20 ||  23 ||  22.7 ||  22.3  || 21.9  || 21.6 ||  21.2 ||  20.8  || 20.4 || {{tb-HC1}} | 20 || 19.6 ||  19.2 ||  18.7 ||  18.
| 26.2
| 25.7
| 25.0
| 24.2  
| 23.7
| 23.0
| 22.2  
| 21.5
| 20.7
|-
|-
| 32
| 25 ||  28.5 ||  28.1  || 27.6 ||  27.2 || 26.8 ||  26.4 ||  25.9  || 25.5  || {{tb-HC1}} |25 || 24.5 || 24.1 ||  23.6  || 23.1
| 33.5  
| 32.9
| 32.0
| 31.4
| 30.4
| 29.8  
| 28.4  
| 28.2
| 27.5
|-
|-
| 40
| 32 ||  37.1 || 36.5 || 35.9  || 35.3  || 34.6  || 34 || 33.3 ||  32.7 || {{tb-HC1}} | 32  || 31.3 || 30.6 ||  29.9 ||  29.1
| 42.0
| 41.2
| 40.0
| 38.8
| 38.0
| 36.8
| 35.6  
| 34.4
| 33.2
|-
|-
| 50
| 40  || 46.4 || 45.6  || 44.|| 44.1  || 43.3 || 42.5 ||  41.7 || 40.9  || {{tb-HC1}} |40 || 39.1  || 38.2  || 37.3 ||  36.4
| 52.5
| 51.5
| 50.0
| 48.5
| 47.4
| 45.5  
| 44.0
| 42.5
| 40.5
|-
|-
| 63
| 50  || 58.7 ||  57.7  || 56.|| 55.|| 54.|| 53.4 || 52.3 || 51.2 ||  {{tb-HC1}} |50 ||  48.8 ||  47.6 || 46.3  || 45
| 66.2
| 64.9
| 63.0
| 61.1
| 58.0
| 56.7
| 54.2  
| 51.7
| 49.2
|-
|-
{{TableEnd|Tab1270|H38a|iC60a, iC60H: curve C. iC60N: curves B and C (reference temperature: 30 °C)}}
| 63  || 74.9 ||  73.5 ||  72.1  || 70.7 ||  69.2  || 67.7  || 66.2 ||  64.6 || {{tb-HC1}} | 63  || 61.4 ||  59.7  || 57.9  || 56.1
|}


{{TableStart|Tab1270b|4col}}
=== Compact NSX100-250 equipped with TM-D or TM-G trip units ===
{{tb-start|id=Tab1270b|num=H39|title=Compact NSX100-250 equipped with TM-D or TM-G trip units - derated/uprated current values according to ambient temperature|cols=4}}
{| class="wikitable"
|-
|-
! Rating  
! Rating  
! colspan="13" | Temperature (°C)
! colspan="13" | Ambient temperature (°C)
|-
|-
! (A)  
! (A)  
Line 347: Line 232:
| 105  
| 105  
| 103  
| 103  
! 100  
|{{tb-HC1}} | 100  
| 97.5  
| 97.5  
| 95  
| 95  
Line 414: Line 299:
| 219  
| 219  
| 213
| 213
|-
|}
{{TableEnd|Tab1270b|H38b|Compact NSX100-250 equippment with TM-D or TM-G trip units}}


== Electronic trip units  ==
== Electronic trip units  ==
Line 422: Line 306:
Electronic tripping units are highly stable in changing temperature levels }}
Electronic tripping units are highly stable in changing temperature levels }}


An important advantage with electronic tripping units is their stable performance in changing temperature conditions. However, the switchgear itself often imposes operational limits in elevated temperatures, so that manufacturers generally provide an operating chart relating the maximum values of permissible trip-current levels to the ambient temperature (see {{FigRef|H42}}).
An important advantage with electronic tripping units is their stable performance in changing temperature conditions. However, the switchgear itself often imposes operational limits in elevated temperatures, so that manufacturers generally provide an operating chart relating the maximum values of permissible trip-current levels to the ambient temperature (see {{FigRef|H40}}).


Moreover, electronic trip units can provide information that can be used for a better management of the electrical distribution, including energy efficiency and power quality.  
Moreover, electronic trip units can provide information that can be used for a better management of the electrical distribution, including energy efficiency and power quality.  


{{TableStart|Tab1271|4col}}
{{tb-start|id=Tab1271|num=H40|title=Derating of Masterpact MTZ2 circuit breaker, according to the temperature |cols=4}}
{| class="wikitable"
|-
! rowspan="2" colspan="2" | Type of Drawout Masterpact 
! colspan="6" | MTZ2 N1 - H1 - H2 - H3 -L1 -H10 
|-
! 08
! 10 
! 12 
! 16
! 20{{tn|A}}
! 20{{tn|B}}
|-
| colspan="2" | '''Ambient temperature (°C)'''
| colspan="6" |
|-
| rowspan="7" | In front or rear horizontal
|40
|800
|1000
|1250
|1600
|2000
|2000
|-
|45
| rowspan="6" |
| rowspan="6" |
| rowspan="6" |
| rowspan="5" |
| rowspan="3" |
| rowspan="3" |
|-
|50
|-
|55
|-
|60
|1900
|
|-
|65
|1830
|1950
|-
|-
! colspan="2" | Masterpact NW20 version
|70
!
|1520
! 40°C
|1750
! 45°C
|1900
! 50°C
! 55°C
! 60°C
|-
|-
| rowspan="2" | H1/H2/H3
| rowspan="7" | In rear vertical
| rowspan="2" | Withdrawable with horizontal plugs
|40
| In (A)
|800
| 2,000
|1000
| 2,000
|1250
| 2,000
|1600
| 1,980
|2000
| 1,890
|2000
|-
|-
| Maximum adjustment Ir
|45
| 1
| rowspan="6" |
| 1
| rowspan="6" |
| 1
| rowspan="6" |
| 0.99
| rowspan="6" |
| 0.95
| rowspan="6" |
| rowspan="6" |
|-
|-
| rowspan="2" | L1
|50
| rowspan="2" | Withdrawable with on-edge plugs
|-
| In (A)
|55
| 2,000
| 200
| 1,900
| 1,850
| 1,800
|-
|-
| Maximum adjustment Ir
|60
| 1
| 1
| 0.95
| 0.93
| 0.90
|-
|-
|colspan="8" | [[File:DB422416_EN.svg]]
|65
|-
|-
{{TableEnd|Tab1271|H42|Derating of Masterpact NW20 circuit-breaker, according to the temperature }}
|70
|}
{{tb-notes
|A= Type: H1/H2/H3
|B= Type: L1 }}


== Selection of an instantaneous, or short-time-delay, tripping threshold  ==
== Selection of an instantaneous, or short-time-delay, tripping threshold  ==


{{FigureRef|H43}} below summarizes the main characteristics of the instantaneous or short-time delay trip units.  
{{FigureRef|H41}} below summarizes the main characteristics of the instantaneous or short-time delay trip units.  


{{TableStart|Tab1272|4col}}
{{tb-start|id=Tab1272|num=H41|title=Different tripping units, instantaneous or short-time-delayed|cols=4}}
{| class="wikitable"
|-
|-
! Type  
! Type  
Line 482: Line 402:
! Applications
! Applications
|-
|-
| [[File:DB422417.svg]]  
| [[File:DB422417.png]]  
| Low setting  
| Low setting  
type B  
type B  
Line 489: Line 409:
*Long lengths of line or cable
*Long lengths of line or cable
|-
|-
| [[File:DB422418.svg]]
| [[File:DB422418.png]]
| Standard setting  
| Standard setting  
type C  
type C  
Line 496: Line 416:


|-
|-
| [[File:DB422419.svg]]
| [[File:DB422419.png]]
| High setting  
| High setting  
type D or K  
type D or K  
Line 502: Line 422:
*Protection of circuits having high initial transient current levels (e.g. motors, transformers, resistive loads)
*Protection of circuits having high initial transient current levels (e.g. motors, transformers, resistive loads)
|-
|-
| [[File:DB422420.svg]]
| [[File:DB422420.png]]
| 12 In  
| 12 In  
type MA  
type MA  
|  
|  
*Protection of motors in association with discontactors (contactors with overload protection)
*Protection of motors in association with contactors and overload protection
|-
|}
{{TableEnd|Tab1272|H43|Different tripping units, instantaneous or short-time-delayed}}


== Selection of a circuit-breaker according to the short-circuit breaking capacity requirements  ==
== Selection of a circuit breaker according to the presumed short-circuit current ==


{{Highlightbox|
{{Highlightbox|
Line 524: Line 443:
*Associations of current-limiting circuit-breakers and standard circuit-breakers.
*Associations of current-limiting circuit-breakers and standard circuit-breakers.


The technique is known as “cascading” (see sub-clause 4.5 of this chapter)
The technique is known as “cascading” (see [[Coordination between circuit-breakers]])


== The selection of main and principal circuit-breakers ==
== Circuit breakers suitable for IT systems ==


{{Highlightbox|
In IT system, circuit breakers may have to face an unusual situation called double earth fault when a second fault to earth occurs in presence of a first fault on the opposite side of a circuit breaker (see {{FigureRef|H42}} ).
The circuit-breaker at the output of the smallest transformer must have a short-circuit capacity adequate for a fault current which is higher than that through any of the other transformer LV circuit-breakers}}
 
In that case circuit breaker has to clear the fault with phase to phase voltage across a single pole instead of phase to neutral voltage. Breaking capacity of the breaker may be modified in such a situation.
 
Annex H of IEC60947-2 deals with this situation and circuit breaker used in IT system shall have been tested according to this annex.
 
When a circuit-breaker has not been tested according to this annex, a marking by the symbol [[File:Non tested CB.svg]] shall be used on the nameplate.
 
Regulation in some countries may add additional requirements.
 
{{FigImage|DB422437_EN|svg|H42|Double earth fault situation}}
 
== Selection of circuit breakers as main incomer and feeders  ==


=== A single transformer ===
=== Installation supplied by one transformer ===


If the transformer is located in a consumer’s substation, certain national standards require a LV circuit-breaker in which the open contacts are clearly visible such as Compact NSX withdrawable circuit-breaker.  
If the transformer is located in a consumer’s substation, certain national standards require a LV circuit breaker in which the open contacts are clearly visible such as
withdrawable circuit breaker.


=== Example ===
=== Example ===
(see {{FigRef|H44}})
(see {{FigRef|H43}})


What type of circuit-breaker is suitable for the main circuit-breaker of an installation supplied through a 250 kVA MV/LV (400 V) 3-phase transformer in a consumer’s substation?
What type of circuit-breaker is suitable for the main circuit-breaker of an installation supplied through a 250 kVA MV/LV (400 V) 3-phase transformer in a consumer’s substation?
Line 546: Line 477:
A Compact NSX400N with an adjustable tripping-unit range of 160 A - 400 A and a short-circuit breaking capacity (Icu) of 50 kA would be a suitable choice for this duty.  
A Compact NSX400N with an adjustable tripping-unit range of 160 A - 400 A and a short-circuit breaking capacity (Icu) of 50 kA would be a suitable choice for this duty.  


{{FigImage|DB422421_EN|svg|H44|Example of a transformer in a consumer’s substation}}
{{FigImage|DB422421_EN|svg|H43|Example of a transformer in a consumer’s substation}}


=== Several transformers in parallel ===
=== Installation supplied by several transformers in parallel ===
(see {{FigRef|H45}})  
(see {{FigRef|H44}})  


*The circuit-breakers CBP outgoing from the LV distribution board must each be capable of breaking the total fault current from all transformers connected to the busbars, viz: Isc1 + Isc2 + Isc3  
* The feeder circuit breakers CBP must each be capable of breaking the total fault current from all transformers connected to the busbars: Isc1 + Isc2 + Isc3
*The circuit-breakers CBM, each controlling the output of a transformer, must be capable of dealing with a maximum short-circuit current of (for example) Isc2 + Isc3 only, for a short-circuit located on the upstream side of CBM1.
* The main incomer circuit breakers CBM, must be capable of dealing with a maximum short-circuit current of (for example) Isc2 + Isc3 only, for a short-circuit located on the upstream side of CBM1.


From these considerations, it will be seen that the circuit-breaker of the smallest transformer will be subjected to the highest level of fault current in these circumstances, while the circuit-breaker of the largest transformer will pass the lowest level of short-circuit current  
From these considerations, it will be seen that the circuit-breaker of the smallest transformer will be subjected to the highest level of fault current in these circumstances, while the circuit-breaker of the largest transformer will pass the lowest level of short-circuit current  
Line 558: Line 489:
*The ratings of CBMs must be chosen according to the kVA ratings of the associated transformers
*The ratings of CBMs must be chosen according to the kVA ratings of the associated transformers


{{FigImage|DB422422_EN|svg|H45|Transformers in parallel}}
{{FigImage|DB422422_EN|svg|H44|Transformers in parallel}}


'''Note:''' The essential conditions for the successful operation of 3-phase transformers in parallel may be summarized as follows:
'''Note:''' The essential conditions for the successful operation of 3-phase transformers in parallel may be summarized as follows:
Line 577: Line 508:
*The switchgear is installed in a floormounted enclosed switchboard, in an ambient-air temperature of 30 °C
*The switchgear is installed in a floormounted enclosed switchboard, in an ambient-air temperature of 30 °C


Moreover, this table shows selected circuit-breakers of M-G manufacture recommended for main and principal circuit-breakers in each case.  
=== Example ===
(see {{FigureRef|H45}})
 
====Circuit-breaker selection for CBM duty====
 
For a 800 kVA transformer In = 1155 A; Icu (minimum) = 38 kA (from {{FigureRef|H46}}), the CBM indicated in the table is a Compact NS1250N (Icu = 50 kA)
 
====Circuit-breaker selection for CBP duty====
 
The s.c. breaking capacity (Icu) required for these circuit-breakers is given in the {{FigureRef|H46}} as 56 kA.
 
A recommended choice for the three outgoing circuits 1, 2 and 3 would be current-limiting circuit-breakers types NSX400 H, NSX250 H and NSX100 H. The Icu rating in each case = 70 kA.
 
These circuit-breakers provide the advantages of:
* Total selectivity with the upstream (CBM) breakers
* Exploitation of the “cascading” technique, with its associated savings for all downstream components
 
{{FigImage|DB422423_EN|svg|H45|Transformers in parallel}}


{{TableStart|Tab1273|5col}}
{{tb-start|id=Tab1273|num=H46|title=Maximum values of short-circuit current to be interrupted by incomer and feeder circuit breakers (CBM and CBP respectively), for several transformers in parallel|cols=5}}
{| class="wikitable"
|-
|-
! Number and kVA ratings of 20/0.4 kV transformers  
! Number and kVA ratings of 20/0.4 kV transformers || Minimum S.C breaking capacity of main CBs (Icu) kA || Main circuit breakers (CBM) total selectivity with outgoing circuit breakers (CBP)|| Minimum S.C breaking capacity of principal CBs (Icu) kA ||  Rated current In of principal circuit breaker (CPB) 250A
! Minimum S.C breaking capacity of main CBs <br>(Icu) kA  
! Main circuit-breakers (CBM)<br>total discrimination with out going circuit-breakers (CBP)  
! Minimum S.C breaking capacity of principal CBs<br>(Icu) kA  
! Rated current In of principal circuit-breaker<br>(CPB) 250A
|-
|-
| 2 x 400  
| 2 X 400 |14 || MTZ1 08H1 / MTZ2 08N1 / NS800N || 28  || NSX100-630F
| 14  
| NW08N1/NS800N  
| 27
| NSX250F
|-
|-
| 3 x 400  
| 3 X 400 || 28 ||  MTZ1 08H1 / MTZ2 08N1 / NS800N || 42 || NSX100-630N
| 28  
| NW08N1/NS800N  
| 42  
| NSX250N
|-
|-
| 2 x 630  
| 2 X 630 || 22 ||  MTZ1 10H1 / MTZ2 10N1 / NS1000N || 44  || NSX100-630N
| 22  
| NW10N1/NS1000N  
| 42
| NSX250N
|-
|-
| 3 x 630  
| 3 X 630 |44 ||  MTZ1 10H2 / MTZ2 10N1 / NS1000N || 66  || NSX100-630S
| 44  
| NW10N1/NS1000N  
| 67
| NSX250S
|-
|-
| 2 x 800  
| 2 X 800 |19 ||  MTZ1 12H1 / MTZ2 12N1 / NS1250N || 38 || NSX100-630N
| 19  
| NW12N1/NS1250N  
| 38  
| NSX250N
|-
|-
| 3 x 800  
| 3 X 800 || 38 ||  MTZ1 12H1 / MTZ2 12N1 / NS1250N || 57  || NSX100-630H
| 38  
| NW12N1/NS1250N  
| 56
| NSX250H
|-
|-
| 2 x 1,000
| 2 X 1000  || 23 ||  MTZ1 16H1 / MTZ2 16N1 / NS1600N || 46  || NSX100-630N
| 23  
| NW16N1/NS1600N  
| 47
| NSX250N
|-
|-
| 3 x 1,000
| 3 X 1000 || 46 ||  MTZ1 16H2 / MTZ2 16H1 / NS1600N || 69  || NSX100-630H
| 47
| NW16N1/NS1600N  
| 70
| NSX250H
|-
|-
| 2 x 1,250
| 2 X 1250  || 29 ||  MTZ2 20N1/NS2000N || 58  || NSX100-630H
| 29  
| NW20N1/NS2000N  
| 59
| NSX250H
|-
|-
| 3 x 1,250
| 3 X 1250  || 58 ||  MTZ2 20H1/NS2000N || 87  || NSX100-630S
| 59
| NW20N1/NS2000N  
| 88
| NSX250S
|-
|-
| 2 x 1,600
| 2 X 1600 || 36 ||  MTZ2 25N1/NS2500N || 72  || NSX100-630S
| 38
| NW25N1/NS2500N  
| 75
| NSX250S
|-
|-
| 3 x 1,600
| 3 X 1600  || 72  || MTZ2 25H2/NS2500H  || 108  || NSX100-630L
| 75
| NW25N1/NS2500N
| 113
| NSX250L
|-
|-
| 2 x 2,000
| 2 X 2000  || 45 ||  MTZ2 32H1/NS3200N || 90  || NSX100-630S
| 47
| NW32N1/NS3200N  
| 94
| NSX250S
|-
| 3 x 2,000
| 94
| NW32N1/NS3200N
| 141
| NSX250L
|-
|-
{{TableEnd|Tab1273|H46|Maximum values of short-circuit current to be interrupted by main and principal circuit-breakers (CBM and CBP respectively), for several transformers in parallel}}
| 3 X 2000 ||  90 || MTZ2 32H2 || 135  || NSX100-630L
 
|}
=== Example ===
(see {{FigureRef|H47}})
 
*'''Circuit-breaker selection for CBM duty''':
:For a 800 kVA transformer In = 1155 A; Icu (minimum) = 38 kA (from {{FigureRef|H46}}), the CBM indicated in the table is a Compact NS1250N (Icu = 50 kA)
*'''Circuit-breaker selection for CBP duty''':
: The s.c. breaking capacity (Icu) required for these circuit-breakers is given in the {{FigureRef|H46}} as 56 kA.
: A recommended choice for the three outgoing circuits 1, 2 and 3 would be current-limiting circuit-breakers types NSX400 L, NSX250 L and NSX100 L. The Icu rating in each case = 150 kA.
: These circuit-breakers provide the advantages of:
:* Absolute discrimination with the upstream (CBM) breakers
:* Exploitation of the “cascading” technique, with its associated savings for all downstream components
 
{{FigImage|DB422423_EN|svg|H47|Transformers in parallel}}


== Choice of outgoing-circuit CBs and final-circuit CBs  ==
== Selection of feeder CBs and final-circuit CBs  ==


{{Highlightbox|
{{Highlightbox|
Short-circuit fault-current levels at any point in an installation may be obtained from tables}}
Short-circuit fault-current levels at any point in an installation may be obtained from tables}}


=== Use of table G40 ===
=== Use of [[Isc at the receiving end of a feeder as a function of the Isc at its sending end#Tab1207|Table G42]] ===
From this table, the value of 3-phase short-circuit current can be determined rapidly for any point in the installation, knowing:  
 
*The value of short-circuit current at a point upstream of that intended for the CB concerned  
From this table, the value of 3-phase short-circuit current can be determined rapidly for any point in the installation, knowing:
*The length, c.s.a., and the composition of the conductors between the two points
* The value of short-circuit current at a point upstream of that intended for the CB concerned
* The length, c.s.a., and the composition of the conductors between the two points


A circuit-breaker rated for a short-circuit breaking capacity exceeding the tabulated value may then be selected.  
A circuit breaker rated for a short-circuit breaking capacity exceeding the tabulated value may then be selected.


=== Detailed calculation of the short-circuit current level ===
=== Detailed calculation of the short-circuit current level ===
In order to calculate more precisely the short-circuit current, notably, when the short-circuit current-breaking capacity of a CB is slightly less than that derived from the table, it is necessary to use the method indicated in [[Short-circuit current ]].  
In order to calculate more precisely the short-circuit current, notably, when the short-circuit current-breaking capacity of a CB is slightly less than that derived from the table, it is necessary to use the method indicated in [[Short-circuit current]].


=== Two-pole circuit-breakers (for phase and neutral) with one protected pole only ===
===Two-pole circuit breakers (for phase and neutral) with one protected pole only===
These CBs are generally provided with an overcurrent protective device on the phase pole only, and may be used in TT, TN-S and IT schemes. In an IT scheme, however, the following conditions must be respected:  
These CBs are generally provided with an overcurrent protective device on the phase pole only, and may be used in TT, TN-S and IT schemes. In an IT scheme, however, the following conditions must be respected:
*Condition (B) of table G67 for the protection of the neutral conductor against overcurrent in the case of a double fault  
* Condition (B) of table in [[Isolation of the neutral conductor#Tab122|{{FigureRef|G68}}]] for the protection of the neutral conductor against overcurrent in the case of a double fault
*Short-circuit current-breaking rating: A 2-pole phase-neutral CB must, by convention, be capable of breaking on one pole (at the phase-to-phase voltage) the current of a double fault equal to 15% of the 3-phase short-circuit current at the point of its installation, if that current is ≤ 10 kA; or 25% of the 3-phase short-circuit current if it exceeds 10 kA
* Short-circuit current-breaking rating: a 2-pole phase-neutral CB must be capable of breaking on one pole (at the phase-to-phase voltage) the current of a double fault
*Protection against indirect contact: this protection is provided according to the rules for IT schemes
* Protection against indirect contact: this protection is provided according to the rules for IT schemes


=== Insufficient short-circuit current breaking rating ===
{{Related-guides-intro}}
In low-voltage distribution systems it sometimes happens, especially in heavy-duty networks, that the Isc calculated exceeds the Icu rating of the CBs available for installation, or system changes upstream result in lower level CB ratings being exceeded
{{RelatedGuide
|image=Hp-highlight-selectivity-guide.png
|title=Selectivity, Cascading and Coordination Guide
|text=Get all required information to verify your electrical distribution design's robustness, considering overloads and short circuits.


*'''Solution 1''': Check whether or not appropriate CBs upstream of the CBs affected are of the current-limiting type, allowing the principle of cascading (described in [[Coordination between circuit-breakers ]]) to be applied
Combine the benefits of selectivity and cascading to maximize power availability of your LV design at optimized cost.
*'''Solution 2''': Install a range of CBs having a higher rating. This solution is economically interesting only where one or two CBs are affected
*'''Solution 3''': Associate current-limiting fuses (gG or aM) with the CBs concerned, on the upstream side. This arrangement must, however, respect the following rules:
** The fuse rating must be appropriate
** No fuse in the neutral conductor, except in certain IT installations where a double fault produces a current in the neutral which exceeds the short-circuit breaking rating of the CB. In this case, the blowing of the neutral fuse must cause the CB to trip on all phases.


[[ru:Выбор автоматического выключателя]]
Find Schneider Electric's coordination data for ACBs, MCCBs, MCBs, RCDs, busbar trunking (busways), motor starters and more.
[[zh:断路器的选择]]
|btn-text=Download the guide (.pdf)
|link=https://www.se.com/ww/en/download/document/LVPED318033EN/
}}

Latest revision as of 09:48, 22 June 2022

The choice of a range of circuit-breakers is determined by: the electrical characteristics of the installation, the environment, the loads and a need for remote control, together with the type of telecommunications system envisaged

Choice of a circuit-breaker

The choice of a CB is made in terms of:

  • Electrical characteristics (AC or DC, Voltage...) of the installation for which the CB is intended
  • Its environment: ambient temperature, in a kiosk or switchboard enclosure, climatic conditions, etc.
  • Presumed short-circuit current at the point of installation
  • Characteristics of the protected cables, busbars, busbar trunking system and application (distribution, motor...)
  • Co-ordination with upstream and/or downstream device: selectivity, cascading, coordination with switch disconnector, contactor...
  • Operational specifications: requirements (or not) for remote control and indication and related auxiliary contacts, auxiliary tripping coils, connection
  • Installation regulations; in particular: protection against electric shock and thermal effect (See Protection against electric shocks and electric fires)
  • Load characteristics, such as motors, fluorescent lighting, LED ligthing, LV/LV transformers

The following notes relate to the choice LV circuit breaker for use in distribution systems.

Choice of rated current in terms of ambient temperature

The rated current of a circuit breaker is defined for operation at a given ambient temperature, in general:

  • 30°C for domestic-type CBs according to IEC 60898 series
  • 40°C by default for industrial-type CBs, according to IEC 60947 series. Different value may be proposed however.

Performance of these CBs in a different ambient temperature depends mainly on the technology of their tripping units (see Fig. H37).

Fig. H37 – Ambient temperature

Uncompensated thermal magnetic tripping units

Circuit-breakers with uncompensated thermal tripping units have a trip current level that depends on the surrounding temperature

Circuit-breakers with uncompensated thermal tripping elements have a tripping-current level that depends on the surrounding temperature. If the CB is installed in an enclosure, or in a hot location (boiler room, etc.), the current required to trip the CB on overload will be sensibly reduced. When the temperature in which the CB is located exceeds its reference temperature, it will therefore be “derated”. For this reason, CB manufacturers provide tables which indicate factors to apply at temperatures different to the CB reference temperature. It may be noted from typical examples of such tables (see Fig. H39) that a lower temperature than the reference value produces an up-rating of the CB. Moreover, small modular-type CBs mounted in juxtaposition, as shown typically in Figure H24, are usually mounted in a small closed metal case. In this situation, mutual heating, when passing normal load currents, generally requires them to be derated by a factor of 0.8.

Example

What rating (In) should be selected for a iC60 N?

  • Protecting a circuit, the maximum load current of which is estimated to be 34 A
  • Installed side-by-side with other CBs in a closed distribution box
  • In an ambient temperature of 60 °C

A iC60N circuit breaker rated at 40 A would be derated to 38.2 A in ambient air at 60°C (see Figure H39). To allow for mutual heating in the enclosed space, however, the 0.8 factor noted above must be employed, so that, 38.2 x 0.8 = 30.5 A, which is not suitable for the 34 A load.

A 50 A circuit breaker would therefore be selected, giving a (derated) current rating of 47.6 x 0.8 = 38 A.

Compensated thermal-magnetic tripping units

These tripping units include a bi-metal compensating strip which allows the overload trip-current setting (Ir or Irth) to be adjusted, within a specified range, irrespective of the ambient temperature.

For example:

  • In certain countries, the TT system is standard on LV distribution systems, and domestic (and similar) installations are protected at the service position by a circuit-breaker provided by the supply authority. This CB, besides affording protection against indirect-contact hazard, will trip on overload; in this case, if the consumer exceeds the current level stated in his supply contract with the power authority. The circuit-breaker (≤ 60 A) is compensated for a temperature range of - 5 °C to + 40 °C.
  • LV circuit-breakers at ratings ≤ 630 A are commonly equipped with compensated tripping units for this range (- 5 °C to + 40 °C)

Examples of tables giving the derated/uprated current values according to temperature, for circuit-breakers with uncompensated thermal tripping units

Circuit breaker thermal characteristics are given considering the section and type of conductor (Cu or Al) according to IEC60947-1 Table 9 & 10 and IEC60898-1 & 2 Table 10

iC60 (IEC 60947-2)

Fig. H38 – iC60 (IEC 60947-2) - derated/uprated current values according to ambient temperature
Rating Ambient temperature (°C)
(A) 10 15 20 25 30 35 40 45 50 55 60 65 70
0.5 0.58 0.57 0.56 0.55 0.54 0.53 0.52 0.51 0.5 0.49 0.48 0.47 0.45
1 1.16 1.14 1.12 1.1 1.08 1.06 1.04 1.02 1 0.98 0.96 0.93 0.91
2 2.4 2.36 2.31 2.26 2.21 2.16 2.11 2.05 2 1.94 1.89 1.83 1.76
3 3.62 3.55 3.48 3.4 3.32 3.25 3.17 3.08 3 2.91 2.82 2.73 2.64
4 4.83 4.74 4.64 4.54 4.44 4.33 4.22 4.11 4 3.88 3.76 3.64 3.51
6 7.31 7.16 7.01 6.85 6.69 6.52 6.35 6.18 6 5.81 5.62 5.43 5.22
10 11.7 11.5 11.3 11.1 10.9 10.7 10.5 10.2 10 9.8 9.5 9.3 9
13 15.1 14.8 14.6 14.3 14.1 13.8 13.6 13.3 13 12.7 12.4 12.1 11.8
16 18.6 18.3 18 17.7 17.3 17 16.7 16.3 16 15.7 15.3 14.9 14.5
20 23 22.7 22.3 21.9 21.6 21.2 20.8 20.4 20 19.6 19.2 18.7 18.3
25 28.5 28.1 27.6 27.2 26.8 26.4 25.9 25.5 25 24.5 24.1 23.6 23.1
32 37.1 36.5 35.9 35.3 34.6 34 33.3 32.7 32 31.3 30.6 29.9 29.1
40 46.4 45.6 44.9 44.1 43.3 42.5 41.7 40.9 40 39.1 38.2 37.3 36.4
50 58.7 57.7 56.7 55.6 54.5 53.4 52.3 51.2 50 48.8 47.6 46.3 45
63 74.9 73.5 72.1 70.7 69.2 67.7 66.2 64.6 63 61.4 59.7 57.9 56.1

Compact NSX100-250 equipped with TM-D or TM-G trip units

Fig. H39 – Compact NSX100-250 equipped with TM-D or TM-G trip units - derated/uprated current values according to ambient temperature
Rating Ambient temperature (°C)
(A) 10 15 20 25 30 35 40 45 50 55 60 65 70
16 18.4 18.7 18 18 17 16.6 16 15.6 15.2 14.8 14.5 14 13.8
25 28.8 28 27.5 25 26.3 25.6 25 24.5 24 23.5 23 22 21
32 36.8 36 35.2 34.4 33.6 32.8 32 31.3 30.5 30 29.5 29 28.5
40 46 45 44 43 42 41 40 39 38 37 36 35 34
50 57.5 56 55 54 52.5 51 50 49 48 47 46 45 44
63 72 71 69 68 66 65 63 61.5 60 58 57 55 54
80 92 90 88 86 84 82 80 78 76 74 72 70 68
100 115 113 110 108 105 103 100 97.5 95 92.5 90 87.5 85
125 144 141 138 134 131 128 125 122 119 116 113 109 106
160 184 180 176 172 168 164 160 156 152 148 144 140 136
200 230 225 220 215 210 205 200 195 190 185 180 175 170
250 288 281 277 269 263 256 250 244 238 231 225 219 213

Electronic trip units

Electronic tripping units are highly stable in changing temperature levels

An important advantage with electronic tripping units is their stable performance in changing temperature conditions. However, the switchgear itself often imposes operational limits in elevated temperatures, so that manufacturers generally provide an operating chart relating the maximum values of permissible trip-current levels to the ambient temperature (see Fig. H40).

Moreover, electronic trip units can provide information that can be used for a better management of the electrical distribution, including energy efficiency and power quality.

Fig. H40 – Derating of Masterpact MTZ2 circuit breaker, according to the temperature
Type of Drawout Masterpact MTZ2 N1 - H1 - H2 - H3 -L1 -H10
08 10 12 16 20[a] 20[b]
Ambient temperature (°C)
In front or rear horizontal 40 800 1000 1250 1600 2000 2000
45
50
55
60 1900
65 1830 1950
70 1520 1750 1900
In rear vertical 40 800 1000 1250 1600 2000 2000
45
50
55
60
65
70
  1. ^ Type: H1/H2/H3
  2. ^ Type: L1

Selection of an instantaneous, or short-time-delay, tripping threshold

Figure H41 below summarizes the main characteristics of the instantaneous or short-time delay trip units.

Fig. H41 – Different tripping units, instantaneous or short-time-delayed
Type Tripping unit Applications
DB422417.png Low setting

type B

  • Sources producing low short-circuit- current levels (standby generators)
  • Long lengths of line or cable
DB422418.png Standard setting

type C

  • Protection of circuits: general case
DB422419.png High setting

type D or K

  • Protection of circuits having high initial transient current levels (e.g. motors, transformers, resistive loads)
DB422420.png 12 In

type MA

  • Protection of motors in association with contactors and overload protection

Selection of a circuit breaker according to the presumed short-circuit current

The installation of a LV circuit-breaker requires that its short-circuit breaking capacity (or that of the CB together with an associated device) be equal to or exceeds the calculated prospective short-circuit current at its point of installation

The installation of a circuit-breaker in a LV installation must fulfil one of the two following conditions:

  • Either have a rated short-circuit breaking capacity Icu (or Icn) which is equal to or exceeds the prospective short-circuit current calculated for its point of installation, or
  • If this is not the case, be associated with another device which is located upstream, and which has the required short-circuit breaking capacity

In the second case, the characteristics of the two devices must be co-ordinated such that the energy permitted to pass through the upstream device must not exceed that which the downstream device and all associated cables, wires and other components can withstand, without being damaged in any way. This technique is profitably employed in:

  • Associations of fuses and circuit-breakers
  • Associations of current-limiting circuit-breakers and standard circuit-breakers.

The technique is known as “cascading” (see Coordination between circuit-breakers)

Circuit breakers suitable for IT systems

In IT system, circuit breakers may have to face an unusual situation called double earth fault when a second fault to earth occurs in presence of a first fault on the opposite side of a circuit breaker (see Figure H42 ).

In that case circuit breaker has to clear the fault with phase to phase voltage across a single pole instead of phase to neutral voltage. Breaking capacity of the breaker may be modified in such a situation.

Annex H of IEC60947-2 deals with this situation and circuit breaker used in IT system shall have been tested according to this annex.

When a circuit-breaker has not been tested according to this annex, a marking by the symbol Non tested CB.svg shall be used on the nameplate.

Regulation in some countries may add additional requirements.

Fig. H42 – Double earth fault situation

Selection of circuit breakers as main incomer and feeders

Installation supplied by one transformer

If the transformer is located in a consumer’s substation, certain national standards require a LV circuit breaker in which the open contacts are clearly visible such as withdrawable circuit breaker.

Example

(see Fig. H43)

What type of circuit-breaker is suitable for the main circuit-breaker of an installation supplied through a 250 kVA MV/LV (400 V) 3-phase transformer in a consumer’s substation?

In transformer = 360 A

Isc (3-phase) = 9 kA

A Compact NSX400N with an adjustable tripping-unit range of 160 A - 400 A and a short-circuit breaking capacity (Icu) of 50 kA would be a suitable choice for this duty.

Fig. H43 – Example of a transformer in a consumer’s substation

Installation supplied by several transformers in parallel

(see Fig. H44)

  • The feeder circuit breakers CBP must each be capable of breaking the total fault current from all transformers connected to the busbars: Isc1 + Isc2 + Isc3
  • The main incomer circuit breakers CBM, must be capable of dealing with a maximum short-circuit current of (for example) Isc2 + Isc3 only, for a short-circuit located on the upstream side of CBM1.

From these considerations, it will be seen that the circuit-breaker of the smallest transformer will be subjected to the highest level of fault current in these circumstances, while the circuit-breaker of the largest transformer will pass the lowest level of short-circuit current

  • The ratings of CBMs must be chosen according to the kVA ratings of the associated transformers
Fig. H44 – Transformers in parallel

Note: The essential conditions for the successful operation of 3-phase transformers in parallel may be summarized as follows:

1. the phase shift of the voltages, primary to secondary, must be the same in all units to be paralleled.

2. the open-circuit voltage ratios, primary to secondary, must be the same in all units.

3. the short-circuit impedance voltage (Zsc%) must be the same for all units.

For example, a 750 kVA transformer with a Zsc = 6% will share the load correctly with a 1,000 kVA transformer having a Zsc of 6%, i.e. the transformers will be loaded automatically in proportion to their kVA ratings. For transformers having a ratio of kVA ratings exceeding 2, parallel operation is not recommended.

Figure H46 indicates, for the most usual arrangement (2 or 3 transformers of equal kVA ratings) the maximum short-circuit currents to which main and principal CBs (CBM and CBP respectively, in Figure H45) are subjected. It is based on the following hypotheses:

  • The short-circuit 3-phase power on the MV side of the transformer is 500 MVA
  • The transformers are standard 20/0.4 kV distribution-type units rated as listed
  • The cables from each transformer to its LV circuit-breaker comprise 5 metres of single core conductors
  • Between each incoming-circuit CBM and each outgoing-circuit CBP there is 1 metre of busbar
  • The switchgear is installed in a floormounted enclosed switchboard, in an ambient-air temperature of 30 °C

Example

(see Figure H45)

Circuit-breaker selection for CBM duty

For a 800 kVA transformer In = 1155 A; Icu (minimum) = 38 kA (from Figure H46), the CBM indicated in the table is a Compact NS1250N (Icu = 50 kA)

Circuit-breaker selection for CBP duty

The s.c. breaking capacity (Icu) required for these circuit-breakers is given in the Figure H46 as 56 kA.

A recommended choice for the three outgoing circuits 1, 2 and 3 would be current-limiting circuit-breakers types NSX400 H, NSX250 H and NSX100 H. The Icu rating in each case = 70 kA.

These circuit-breakers provide the advantages of:

  • Total selectivity with the upstream (CBM) breakers
  • Exploitation of the “cascading” technique, with its associated savings for all downstream components
Fig. H45 – Transformers in parallel
Fig. H46 – Maximum values of short-circuit current to be interrupted by incomer and feeder circuit breakers (CBM and CBP respectively), for several transformers in parallel
Number and kVA ratings of 20/0.4 kV transformers Minimum S.C breaking capacity of main CBs (Icu) kA Main circuit breakers (CBM) total selectivity with outgoing circuit breakers (CBP) Minimum S.C breaking capacity of principal CBs (Icu) kA Rated current In of principal circuit breaker (CPB) 250A
2 X 400 14 MTZ1 08H1 / MTZ2 08N1 / NS800N 28 NSX100-630F
3 X 400 28 MTZ1 08H1 / MTZ2 08N1 / NS800N 42 NSX100-630N
2 X 630 22 MTZ1 10H1 / MTZ2 10N1 / NS1000N 44 NSX100-630N
3 X 630 44 MTZ1 10H2 / MTZ2 10N1 / NS1000N 66 NSX100-630S
2 X 800 19 MTZ1 12H1 / MTZ2 12N1 / NS1250N 38 NSX100-630N
3 X 800 38 MTZ1 12H1 / MTZ2 12N1 / NS1250N 57 NSX100-630H
2 X 1000 23 MTZ1 16H1 / MTZ2 16N1 / NS1600N 46 NSX100-630N
3 X 1000 46 MTZ1 16H2 / MTZ2 16H1 / NS1600N 69 NSX100-630H
2 X 1250 29 MTZ2 20N1/NS2000N 58 NSX100-630H
3 X 1250 58 MTZ2 20H1/NS2000N 87 NSX100-630S
2 X 1600 36 MTZ2 25N1/NS2500N 72 NSX100-630S
3 X 1600 72 MTZ2 25H2/NS2500H 108 NSX100-630L
2 X 2000 45 MTZ2 32H1/NS3200N 90 NSX100-630S
3 X 2000 90 MTZ2 32H2 135 NSX100-630L

Selection of feeder CBs and final-circuit CBs

Short-circuit fault-current levels at any point in an installation may be obtained from tables

Use of Table G42

From this table, the value of 3-phase short-circuit current can be determined rapidly for any point in the installation, knowing:

  • The value of short-circuit current at a point upstream of that intended for the CB concerned
  • The length, c.s.a., and the composition of the conductors between the two points

A circuit breaker rated for a short-circuit breaking capacity exceeding the tabulated value may then be selected.

Detailed calculation of the short-circuit current level

In order to calculate more precisely the short-circuit current, notably, when the short-circuit current-breaking capacity of a CB is slightly less than that derived from the table, it is necessary to use the method indicated in Short-circuit current.

Two-pole circuit breakers (for phase and neutral) with one protected pole only

These CBs are generally provided with an overcurrent protective device on the phase pole only, and may be used in TT, TN-S and IT schemes. In an IT scheme, however, the following conditions must be respected:

  • Condition (B) of table in Figure G68 for the protection of the neutral conductor against overcurrent in the case of a double fault
  • Short-circuit current-breaking rating: a 2-pole phase-neutral CB must be capable of breaking on one pole (at the phase-to-phase voltage) the current of a double fault
  • Protection against indirect contact: this protection is provided according to the rules for IT schemes
Share