TT system - Practical aspects: Difference between revisions

From Electrical Installation Guide
m (1 revision)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(18 intermediate revisions by 4 users not shown)
Line 1: Line 1:
{{Menu_Protection_against_electric_shocks}}
{{Menu_Protection_against_electric_shocks}}__TOC__
__TOC__
== Specified maximum disconnecting time ==
<br>
== Protection against indirect contact  ==


'''General case'''<br>Protection against indirect contact is assured by RCDs, the sensitivity IΔn of which complies with the condition <math>I\Delta n\le\frac{50V}{R_A}</math>&nbsp;(1)<br>The choice of sensitivity of the residual current device is a function of the resistance R<sub>A</sub> of the earth electrode for the installation, and is given in '''Figure F28'''.  
The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective selective protection.


{| class="wikitable" style="height: 10px" width="60%"
IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact:
* For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in {{FigRef|F13}}
* For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables selectivity between RCDs when installed on distribution circuits.
 
{{tb-start|id=Tab1151|num=F13|title=Maximum disconnecting times in TT system for final circuits not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment|cols=2}}
{| class="wikitable"
|-
! Uo{{tn|A}} (V AC)
! T (s)
|-
| 50 < Uo ≤ 120
| 0.3
|-
|-
| (1) 25 V for work-site installations, agricultural establishments, etc.
| 120 < Uo ≤ 230
| 0.2
|-
| 230 < Uo ≤ 400
| 0.07
|-
| Uo > 400
| 0.04
|}
|}
{{tb-notes
|A= Uo is the nominal phase to earth voltage }}


----
RCD is a general term for all devices operating on the residual-current principle.


<br>
RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD.


{| class="wikitable" style="width: 421px; height: 113px" width="421"
General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in {{FigRef|F14}}. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in [[Coordination of residual current protective devices]]. Industrial type RCD according to IEC 60947-2 provide more possibilities of selectivity due to their flexibility of time-delaying.
|-
 
! width="30%" | IΔn
{{tb-start|id=Tab1152|num=F14|title=Maximum operating time of RCDs (in seconds)|cols=3}}
! colspan="2" | Maximum resistance of the earth electrode
{| class="wikitable"
|-
|-
! x I<sub>Δn</sub>
!  
!  
! width="40%" | (50 V)
! 1
! (25 V)
! 2
! 5
! > 5
|-
|-
| 3 A
| rowspan="2" | Domestic
| 16 Ω
| Instantaneous
| 8 Ω
| 0.3  
| 0.15
| 0.04
| 0.04
|-
|-
| 1 A
| Type S
| 50 Ω
| 0.5
| 25 Ω
| 0.2
| 0.15
| 0.15
|-
|-
| 500 mA
| rowspan="3" | Industrial
| 100 Ω
| Instantaneous
| 50 Ω
| 0.3
| 0.15
| 0.04
| 0.04
|-
|-
| 300 mA
| Time-delay : 0.06 s
| 166 Ω
| 0.5
| 83 Ω
| 0.2
| 0.15
| 0.15
|-
|-
| 30 mA
| Time-delay (other)
| 1666 Ω
| colspan="4" | According to manufacturer
| 833 Ω
|}
|}


'''''Fig. F28:''' The upper limit of resistance for an installation earthing electrode which must not be exceeded, for given sensitivity levels of RCDs at U<sub>L</sub> voltage limits of 50 V and 25 V &nbsp; <br>''
== Case of distribution circuits ==
 
(see {{FigRef|F15}})
----
 
'''Case of distribution circuits '''(see '''Fig. F29''')
 
IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits). This allows a degree of selective discrimination to be achieved:
 
*At level A: RCD time-delayed, e.g. “S” type
*At level B: RCD instantaneous
 
----
 
[[File:FigF29.jpg|none]]
'''''Fig. F29:''' Distribution circuits''
 
----
 
'''Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode ('''see '''Fig. F30)'''
 
Protection against indirect contact by a RCD at the circuit-breaker level protecting each group or separately-earthed individual appliance.<br>In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.
 
----
 
[[File:FigF30.jpg|none]]
'''''Fig. F30:''' Separate earth electrode''
 
----
 
== High-sensitivity RCDs  ==
 
(see '''Fig. F31''')
 
According to IEC 60364-4-41, high sensitivity RCDs ( ≤ 30 mA) must be used for protection of socket outlets with rated current ≤ 20 A in all locations. The use of such RCDs is also recommended in the following cases:
 
*Socket-outlet circuits in wet locations at all current ratings
*Socket-outlet circuits in temporary installations
*Circuits supplying laundry rooms and swimming pools
*Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs
 
----
<br>
[[File:FigF31.jpg|none]]
'''''Fig. F31:''' Circuit supplying socket-outlets''
 
----


== In high fire risk locations  ==
IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits).


'''('''see '''Fig. F32)'''
This allows a degree of selectivity to be achieved:
* At level A: Time-delayed RCD, e.g. “S” type
* At level B: Instantaneous RCD.


RCD protection at the circuit-breaker controlling all supplies to the area at risk is necessary in some locations, and mandatory in many countries.<br>The sensitivity of the RCD must be ≤ 500 mA, but a 300 mA sensitivity is recommended.
{{FigImage|DB422239_EN|svg|F15|Distribution circuits}}


----
== Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode ==
<br>
(see {{FigRef|F16}})
[[File:FigF32.jpg|none]]
'''''Fig. F32:''' Fire-risk location''


----
Fault Protection is provided by a RCD at the circuit breaker level protecting each group or separately-earthed individual appliance.


== Protection when exposed conductive parts are not connected to earth ==
In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.


(see '''Fig. F33''')<br>(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).
{{FigImage|DB422240_EN|svg|F16|Separate earth electrode}}


RCDs of high sensitivity (≤ 30 mA) will afford both protection against indirect-contact hazards, and the additional protection against the dangers of direct-contact.
== Protection when exposed conductive parts are not connected to earth ==
(see {{FigRef|F17}})


----
(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).
<br>
[[File:FigF33.jpg|none]]
'''''Fig. F33: '''Unearthed exposed conductive parts (A)<br>''


----
RCDs of high sensitivity (≤ 30 mA) will afford both fault protection (against indirect contact hazards), and the additional protection against the dangers of contact with live parts (direct contact).


<br>
{{FigImage|DB422243|svg|F17|Unearthed exposed conductive parts (A)}}


[[ru:Система TT: защитные меры]]
[[fr:Protection contre les chocs et incendies électriques]]
[[zh:TT系统保护措施]]
[[de:Schutz gegen elektrischen Schlag]]

Latest revision as of 09:48, 22 June 2022

Specified maximum disconnecting time

The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective selective protection.

IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact:

  • For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in Fig. F13
  • For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables selectivity between RCDs when installed on distribution circuits.
Fig. F13 – Maximum disconnecting times in TT system for final circuits not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment
Uo[a] (V AC) T (s)
50 < Uo ≤ 120 0.3
120 < Uo ≤ 230 0.2
230 < Uo ≤ 400 0.07
Uo > 400 0.04
  1. ^ Uo is the nominal phase to earth voltage

RCD is a general term for all devices operating on the residual-current principle.

RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD.

General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in Fig. F14. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in Coordination of residual current protective devices. Industrial type RCD according to IEC 60947-2 provide more possibilities of selectivity due to their flexibility of time-delaying.

Fig. F14 – Maximum operating time of RCDs (in seconds)
x IΔn 1 2 5 > 5
Domestic Instantaneous 0.3 0.15 0.04 0.04
Type S 0.5 0.2 0.15 0.15
Industrial Instantaneous 0.3 0.15 0.04 0.04
Time-delay : 0.06 s 0.5 0.2 0.15 0.15
Time-delay (other) According to manufacturer

Case of distribution circuits

(see Fig. F15)

IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits).

This allows a degree of selectivity to be achieved:

  • At level A: Time-delayed RCD, e.g. “S” type
  • At level B: Instantaneous RCD.
Fig. F15 – Distribution circuits

Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode

(see Fig. F16)

Fault Protection is provided by a RCD at the circuit breaker level protecting each group or separately-earthed individual appliance.

In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.

Fig. F16 – Separate earth electrode

Protection when exposed conductive parts are not connected to earth

(see Fig. F17)

(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).

RCDs of high sensitivity (≤ 30 mA) will afford both fault protection (against indirect contact hazards), and the additional protection against the dangers of contact with live parts (direct contact).

Fig. F17 – Unearthed exposed conductive parts (A)
Share