Coordination between circuit-breakers: Difference between revisions

From Electrical Installation Guide
Home > LV switchgear: functions and selection > Circuit-breaker > Coordination between circuit-breakers
*>CleanUpAuto
(clean-up 2016 - imported revision step 20)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(33 intermediate revisions by 4 users not shown)
Line 1: Line 1:
{{Menu_LV_switchgear_functions_and_selection}}
{{Menu_LV_switchgear_functions_and_selection}}__TOC__
__TOC__
 
<br>
== Cascading (or Back-up protection) ==
== Cascading (or Back-up protection) ==


{{Highlightbox|
{{Highlightbox|
The technique of “cascading” uses the properties of current-limiting circuit-breakers to permit the installation of all downstream switchgear, cables and other circuit components of significantly lower performance than would otherwise be necessary, thereby simplifying and reducing the cost of an installation
The technique of “cascading” uses the properties of current-limiting circuit-breakers to permit the installation of all downstream switchgear, cables and other circuit components of significantly lower performance than would otherwise be necessary, thereby simplifying and reducing the cost of an installation }}
}}


'''Definition of the cascading technique''' <br>By limiting the peak value of short-circuit current passing through it, a current-limiting CB permits the use, in all circuits downstream of its location, of switchgear and circuit components having much lower short-circuit breaking capacities, and thermal and electromechanical withstand capabilities than would otherwise be necessary. Reduced physical size and lower performance requirements lead to substantial economy and to the simplification of installation work. It may be noted that, while a current-limiting circuit-breaker has the effect on downstream circuits of (apparently) increasing the source impedance during short-circuit conditions, it has no such effect in any other condition; for example, during the starting of a large motor (where a low source impedance is highly desirable). The range of Compact NSX current-limiting circuit-breakers with powerful limiting performances is particularly interesting.
=== Definition of the cascading technique ===


By limiting the peak value of short-circuit current passing through it, a current-limiting CB permits the use, in all circuits downstream of its location, of switchgear and circuit components having much lower short-circuit breaking capacities, and thermal and electromechanical withstand capabilities than would otherwise be necessary. Reduced physical size and lower performance requirements lead to substantial economy and to the simplification of installation work. It may be noted that, while a current-limiting circuit-breaker has the effect on downstream circuits of (apparently) increasing the source impedance during short-circuit conditions, it has no such effect in any other condition; for example, during the starting of a large motor (where a low source impedance is highly desirable). The range of Compact NSX current-limiting circuit-breakers with powerful limiting performances is particularly interesting.


== Conditions of implementation ==
=== Conditions of implementation ===


{{Highlightbox|
{{Highlightbox|
In general, laboratory tests are necessary to ensure that the conditions of implementation required by national standards are met and compatible switchgear combinations must be provided by the manufacturer
In general, laboratory tests are necessary to ensure that the conditions of implementation required by national standards are met and compatible switchgear combinations must be provided by the manufacturer}}
}}


Most national standards admit the cascading technique, on condition that the amount of energy “let through” by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage.<br>In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, {{FigureRef|H48}} indicates the cascading possibilities of circuit-breaker types iC60, DT40N, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation.  
Most national standards admit the cascading technique, on condition that the amount of energy “let through” by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage.


In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, {{FigureRef|H47}} indicates the cascading possibilities of circuit-breaker types iC60, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation.


{{tb-start|id=Tab1274|num=H47|title=Example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation|cols=4}}
{| class="wikitable"
{| class="wikitable"
|-
|-
!  
! rowspan="2" colspan="3" | Upstream CB
! kArms
! colspan="6" | NSX250
!  
|-
!  
! B
!  
! F
! N
! H
! S 
! L
|-
! colspan="3" style="text-align: right;" | Icu (kA)
! 25
! 36
! 50 
! 70
! 100
! 150
|-
| colspan="9" {{tb-HC1}} |'''Downstream CB'''
|-
|-
| rowspan="4" | '''Short-circuit breaking capacity of the upstream (limiter) CBs'''  
| {{tb-HC1}} | '''Type'''
| 150
| {{tb-HC1}} | ''' Rating (A)'''
|  
| {{tb-HC1}} | '''Icu (kA)'''
|  
| colspan="6" {{tb-HC1}} |'''Reinforced breaking capacity (kA)'''
| NSX250L
|-
|-
| 70
| iDPN{{tn|A}} 
|  
| 1-40 
| NSX250H
| 6
|  
| 10
| 10
| 10
| 10
| 10
| 10
|-
|-
| 50
| rowspan="2" | iDPN N{{tn|A}} 
| NSX250N
| 1-16
|  
| 10 
|  
| 20
| 20
| 20
| 20
| 20
| 20
|-
|-
|  
| 25-40
| [[File:Fleche.jpg|center]]
| 10
| [[File:Fleche.jpg|center]]
| 16
| [[File:Fleche.jpg|center]]
| 16
| 16
| 16 
| 16 
| 16
|-
|-
!
| rowspan="2" | iC60N
!
| 0,5-40
!
| 10
!
| 20 
!
| 25 
| 30
| 30
| 30
| 30
|-
|-
| rowspan="7" | '''Possible short-circuit breaking capacity of the downstream CBs (benefiting from the cascading technique)'''
| 50-63 
| 150
| 10 
|  
| 20
|  
| 25
| NG125L
| 25
| 25
| 25 
| 25
|-
|-
| 70
| rowspan="2" | iC60H
|  
| 0,5-40
| NG125L
| 15
|  
| 25
| 30
| 30 
| 30 
| 30 
| 30
|-
|-
| 36
| 50-63
| NG125N
| 15
| NG125N
| 25
|  
| 25
| 25
| 25
| 25 
| 25
|-
|-
| rowspan="3" | iC60L
| 0,5-25
| 25
| 25
| 30
| 30
| 30  
| 30  
| iC60N/H&lt;=32A
| 30 
| iC60N/H&lt;=32A
| 30
| iC60N/H&lt;=32A
|-
|-
| 32-40
| 20 
| 25
| 30
| 30  
| 30  
| iC60L&lt;=25A
| 30 
| iC60L&lt;=25A
| 30 
| iC60L&lt;=25A
| 30
|-
| 50-63
| 15
| 25
| 25
| 25
| 25
| 25
| 25
|-
| C120N
| 63-125
| 10
| 25
| 25
| 25
| 25
| 25 
| 25
|-
| C120H 
| 63-125
| 15
| 25
| 25
| 25 
| 25
| 25
| 25
|-
|-
| NG125N
| 1-125
| 25  
| 25  
| iC60H&gt;=40A<br>C120N/H
|
| iC60H&gt;=40A<br>C120N/H
|36
| iC60H&gt;=40A<br>C120N/H
|36
|36
|50
|70
|-
| NG125H 
| 1-125
| 36
|
|
|40
|50
|70
|100
|-
|-
| 20
| NG125L
| iC60N&gt;=40A
| 1-80
| iC60N&gt;=40A
| 50
| iC60N&gt;=40A
|
|
|50
|70
|100
|150
|}
|}
{{tb-notes
|A= 230 V phase to neutral
|txn1= '''Note''': for up-to-date cascading values, refer to manufacturer’s documentation, such as Schneider Electric’s [https://www.se.com/ww/en/download/document/LVPED318033EN/ Complementary Technical Information - Selectivity, Cascading and Coordination Guide]}}


'''''Fig. H48: '''Example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation''
=== Advantages of cascading ===


== Advantages of cascading  ==
The current limitation benefits all downstream circuits that are controlled by the current-limiting CB concerned.


The current limitation benefits all downstream circuits that are controlled by the current-limiting CB concerned.<br>The principle is not restrictive, i.e. current-limiting CBs can be installed at any point in an installation where the downstream circuits would otherwise be inadequately rated.<br>The result is:
The principle is not restrictive, i.e. current-limiting CBs can be installed at any point in an installation where the downstream circuits would otherwise be inadequately rated.


The result is:
*Simplified short-circuit current calculations  
*Simplified short-circuit current calculations  
*Simplification, i.e. a wider choice of downstream switchgear and appliances  
*Simplification, i.e. a wider choice of downstream switchgear and appliances  
Line 104: Line 207:
*Economy of space requirements, since light-duty equipment have generally a smaller volume
*Economy of space requirements, since light-duty equipment have generally a smaller volume


 
== Principles of Selectivity ==
== Principles of discriminative tripping (selectivity)  ==
 
{{Highlightbox|
Discrimination may be total or partial, and based on the principles of current levels, or time-delays, or a combination of both. A more recent development is based on the logic techniques.<br>The Schneider Electric system takes advantages of both current-limitation and discrimination
}}
 
Discrimination (selectivity) is achieved by automatic protective devices if a fault condition, occurring at any point in the installation, is cleared by the protective device located immediately upstream of the fault, while all other protective devices remain unaffected (see {{FigRef|H49}}).
 
[[File:FigH49.jpg|none]]
 
'''''Fig. H49:''' Total and partial discrimination''
 
 
Discrimination between circuit-breakers A and B is total if the maximum value of short-circuit-current on circuit B (Isc B) does not exceed the short-circuit trip setting of circuit-breaker A (Im A). For this condition, B only will trip (see {{FigRef|H50}}).
 
[[File:FigH50.jpg|none]]
 
'''''Fig. H50:''' Total discrimination between CBs A and B''
 
 
Discrimination is partial if the maximum possible short-circuit current on circuit B exceeds the short-circuit trip-current setting of circuit-breaker A. For this maximum condition, both A and B will trip (see {{FigRef|H51}}).
 
[[File:FigH51.jpg|none]]
 
'''''Fig. H51:''' Partial discrimination between CBs A and B''
 
 
 
'''Protection against overload&nbsp;: discrimination based on current levels <br>'''(see {{FigRef|H52a}})<br>This method is realized by setting successive tripping thresholds at stepped levels, from downstream relays (lower settings) towards the source (higher settings). Discrimination is total or partial, depending on particular conditions, as noted above.
 
[[File:FigH52a.jpg|none]]
 
'''''Fig. H52a:'''''<i>&nbsp;Discrimination</i>
 
 
As a rule of thumb, discrimination is achieved when:'''<br>'''
 
*IrA/IrB &gt; 2:
 
'''Protection against low level short-circuit currents&nbsp;: discrimination based on stepped time delays '''(see {{FigRef|H52b}})<br>This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source.<br>In the two-level arrangement shown, upstream circuit-breaker A is delayed sufficiently to ensure total discrimination with B (for example: Masterpact with electronic trip unit).
 
 
[[File:FigH52b.jpg|none]]
 
'''''Fig. H52b:''' Discrimination''
 
 
'''Discrimination based on a combination of the two previous methods''' (see {{FigRef|H52c}})<br>A time-delay added to a current level scheme can improve the overall discrimination performance.<br>The upstream CB has two high-speed magnetic tripping thresholds:
 
*Im A: delayed magnetic trip or short-delay electronic trip
*Ii: instantaneous strip
 
Discrimination is total if Isc B &lt; Ii (instantaneous).
 
 
[[File:FigH52c.jpg|none]]
 
'''''Fig. H52c:''' Discrimination''
 
 
'''Protection against high level short-circuit currents: discrimination based on arc-energy levels'''<br>This technology implemented in the Compact NSX range (current limiting circuit- breaker) is extremely effective for achievement of total discrimination.<br>Principle: When a very high level short-circuit current is detected by the two circuits- breaker A and B, their contacts open simultaneously. As a result, the current is highly limited.
 
*The very high arc-energy at level B induces the tripping of circuit-breaker B
*Then, the arc-energy is limited at level A and is not sufficient to induce the tripping of A
 
As a rule of thumb, the discrimination between Compact NSX is total if the size ratio between A and B is greater than 2.5.'''<br>'''
 
 
== Current-level discrimination ==
 
 
This technique is directly linked to the staging of the Long Time (LT) tripping curves of two serial-connected circuit-breakers.
 
 
[[File:FigH53.jpg|none]]
 
'''''Fig. H53:''' Current discrimination''
 
 
The discrimination limit ls is:
 
*Is = Isd2 if the thresholds lsd1 and lsd2 are too close or merge,
*Is = Isd1 if the thresholds lsd1 and lsd2 are sufficiently far apart.
 
As a rule, current discrimination is achieved when:
 
*Ir1 / Ir2 &lt; 2,
*Isd1 / Isd2 &gt; 2.
 
The discrimination limit is:
 
*Is = Isd1.


{{Highlightbox|
{{Highlightbox|
'''Discrimination quality'''<br>Discrimination is total if Is &gt; Isc(D2), i.e. Isd1 &gt; Isc(D2). <br>This normally implies:
Selectivity is essential to ensure continuity of supply and fast fault localization.}}
*a relatively low level Isc(D2),
*a large difference between the ratings of circuit-breakers D1 and D2.


'''Current discrimination is normally used in final distribution.'''
Selectivity is achieved by overcurrent and earth fault protective devices if a fault condition, occurring at any point in the installation, is cleared by the protective device located immediately upstream of the fault, while all other protective devices remain unaffected (see {{FigureRef|H48}}).


}}
{{FigImage|DB431076|svg|H48|Principle of selectivity}}


Selectivity is required for installation supplying critical loads where one fault on one circuit shall not cause the interruption of the supply of other circuits. In IEC 60364 series it is mandatory for installation supplying safety services (IEC60364-5-56 2009 560.7.4). Selectivity may also be required by some local regulation or for some special application like :
* Medical location
* Marine
* High-rise building


== Time discrimination  ==
Selectivity is highly recommended where continuity of supply is critical due to the nature of the loads.
* Data center
* Infrastructure (tunnel, airport…)
* Critical process


{{Highlightbox|
From installation point of view: Selectivity is achieved when the maximum short-circuit current at a point of installation is below selectivity limit of the circuit breakers supplying this point of installation.
Discrimination based on time-delayed tripping uses CBs referred to as “selective” (in some countries).<br>Implementation of these CBs is relatively simple and consists in delaying the instant of tripping of the several series-connected circuit-breakers in a stepped time sequence
}}


This is the extension of current discrimination and is obtained by staging over time of the tripping curves. This technique consists of giving a time delay of t to the Short Time (ST) tripping of D1.
Selectivity shall be checked for all circuits supplied by one source and for all type of fault:
* Overload
* Short-circuit
* Earth fault


When system can be supplied by different sources (Grid or generator set for instance) selectivity shall be checked in both cases.


[[File:FigH54.jpg|none]]
Selectivity between two circuit breakers may be
* Total : up to the breaking capacity of the downstream circuit breaker
* Partial : up to a specified value according to circuit breakers characteristics {{FigureRef|H49|H50|H51}}


'''''Fig. H54: '''Time discrimination''
Different solution are provided to achieve selectivity based on:
* Current
* Time
* Energy
* Logic


{{FigImage|DB422425_EN|svg|H49|Total and partial selectivity}}


The thresholds (Ir1, Isd1) of D1 and (Ir2, Isd2) comply with the staging rules of current discrimination. <br>The discrimination limit ls of the association is at least equal to li1, the instantaneous threshold of D1.
{{FigImage|DB422426_EN|svg|H50|Total selectivity between CBs A and B}}


{{Highlightbox|
{{FigImage|DB422427_EN|svg|H51|Partial selectivity between CBs A and B}}


'''Discrimination quality'''<br>
== Current based selectivity ==
see '''(a)''' of {{FigureRef|H52}}


There are two possible applications:
This method is realized by setting successive tripping thresholds at stepped levels, from downstream circuits (lower settings) towards the source (higher settings).
*'''on final and/or intermediate feeders'''


'''A category circuit-breakers '''can be used with time-delayed tripping of the upstream circuit-breaker. This allows extension of current discrimination up to the instantaneous threshold li1 of the upstream circuit-breaker: Is {{=}} li1.<br>'''If Isc(D2) is not too high - case of a final feeder - total discrimination can be obtained.'''
Selectivity is total or partial, depending on particular conditions, as noted above.


*'''on the incomers and feeders of the MSB'''
== Time based selectivity ==
see '''(b)''' of {{FigureRef|H52}}


At this level, as continuity of supply takes priority, the installation characteristics allow use of '''B category circuit-breakers '''designed for time-delayed tripping. These circuit-breakers have a high thermal withstand (Icw ≥ 50% Icn for t {{=}} 1s): Is {{=}} Icw1.<br>Even for high lsc(D2), '''time discrimination normally provides total discrimination: Icw1 &gt; Icc(D2).'''
This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source. In the two-level arrangement shown, upstream circuit breaker A is delayed sufficiently to ensure total selectivity with B (for example: Masterpact with electronic trip unit).


}}
Selectivity category B circuit breakers are designed for time based selectivity, the selectivity limit will be the upstream short time withstand value (Icw)


'''Note:''' Use of B category circuit-breakers means that the installation must withstand high electrodynamic and thermal stresses.<br>Consequently, these circuit-breakers have a high instantaneous threshold li that can be adjusted and disabled in order to protect the busbars if necessary.
== Selectivity based on a combination of the two previous methods ==
see '''(c)''' of {{FigureRef|H52}}


[[File:DB422433.svg|none]]
A time-delay added to a current level scheme can improve the overall selectivity performance.


'''Practical example of discrimination at several levels with Schneider Electric circuit-breakers (with electronic trip units)'''<br>"Masterpact NT is totally selective with any moulded-case Compact NSX circuit breaker, i.e., the downstream circuit-breaker will trip for any short-circuit value up to its breaking capacity. Further, all Compact NSX CBs are totally selective, as long as the ration between sizes is greater than 1.6 and the ratio between ratings is greater than 2.5. The same rules apply for the total selectivity with the miniature circuit-breakers Acti-9 further downstream (see {{FigRef|H55}}).
The upstream CB has two magnetic tripping thresholds:
* Im A: delayed magnetic trip or short-delay electronic trip
* Ii: instantaneous trip


[[File:FigH55.jpg]]
Selectivity is total if Isc B < Ii (instantaneous).


'''''Fig. H55: '''4 level discrimination with Schneider Electric circuit breakers : Masterpact NT, Compact NSX and Acti 9''
{{Gallery|H52|Current based selectivity, Time based selectivity, Combination of both||
|DB422428.svg|a|
|DB422429.svg|b|
|DB422430_EN.svg|c|}}


== Energy discrimination with current limitation  ==
== Protection against high level short-circuit currents: Selectivity based on arc-energy levels ==


Cascading between 2 devices is normally achieved by using the tripping of the upstream circuit-breaker A to help the downstream circuit-breaker B to break the current. The discrimination limit Is is consequently equal to the ultimate breaking current Icu B of circuit-breaker B acting alone, as cascading requires the tripping of both devices.<br>The energy discrimination technology implemented in Compact NSX circuit-breakers allows to improve the discrimination limit to a value higher than the ultimate breaking current Icu B of the downstream circuit-breaker. The principle is as follows:
Where time versus current curves are superposed selectivity is possible with limiter circuit breaker when they are properly coordinated.


*The downstream limiting circuit-breaker B sees a very high short-circuit current. The tripping is very fast (&lt;1 ms) and then, the current is limited
Principle: When a very high level short-circuit current is detected by the two circuit breakers A and B, their contacts open simultaneously. As a result, the current is highly limited.
*The upstream circuit-breaker A sees a limited short-circuit current compared to its breaking capability, but this current induces a repulsion of the contacts. As a result, the arcing voltage increases the current limitation. However, the arc energy is not high enough to induce the tripping of the circuit-breaker. So, the circuit-breaker A helps the circuit-breaker B to trip, without tripping itself. The discrimination limit can be higher than Icu B and the discrimination becomes total with a reduced cost of the devices
* The very high arc-energy at level B induces the tripping of circuit breaker B
* Then, the arc-energy is limited at level A and is not sufficient to induce the tripping of A


{{FigImage|DB431077_EN|svg|H53|Energy based selectivity}}


== Natural total discriminitation with Compact NSX ==
This approach requires an accurate coordination of limitation levels and tripping energy levels. It’s implemented inside the Compact NSX range (current limiting circuit breaker), and between compact NSX and acti 9 range. This solution is the only one to achieve selectivity up to high short-circuit current with selectivity category A circuit breaker according to IEC60947-2.


The major advantage of the Compact NSX range is to provide a natural total discrimination between two series-connected devices if:
{{FigImage|DB431078_EN|svg|H54|Practical example of selectivity at several levels with Schneider Electric circuit breakers(with electronic trip units)}}


*The ratio of the two trip-unit current ratings is &gt; 1.6
== Selectivity enhanced by cascading ==
*The ratio of rated currents of the two circuit-breakers is &gt; 2.5
Cascading between 2 devices is normally achieved by using the tripping of the upstream circuit breaker A to help the downstream circuit breaker B to break the current. By principle cascading is in contradiction with selectivity. But the energy selectivity technology implemented in Compact NSX circuit-breakers allows to improve the breaking capacity of downstream circuit-breakers and maintain high selectivity performance.


The principle is as follows:
* The downstream limiting circuit breaker B sees a very high short-circuit current. The tripping is very fast (<1 ms) and then, the current is limited
* The upstream circuit breaker A sees a limited short-circuit current compared to its breaking capability, but this current induces a repulsion of the contacts. As a result, the arcing voltage increases the current limitation. However, the arc energy is not high enough to induce the tripping of the circuit breaker. So, the circuit breaker A helps the circuit breaker B to trip, without tripping itself. The selectivity limit can
be higher than Icu B and the selectivity becomes total with a reduced cost of the devices


== Logic discrimination or “Zone Sequence Interlocking – ZSI” ==
== Logic selectivity or “Zone Sequence Interlocking – ZSI” ==


{{Highlightbox|
{{Highlightbox|
Discrimination schemes based on logic techniques are possible, using CBs equipped with electronic tripping units designed for the purpose (Compact, Masterpact) and interconnected with pilot wires
Selectivity schemes based on logic techniques are possible, using CBs equipped with electronic tripping units designed for the purpose (Compact, Masterpact) and interconnected with pilot wires.}}
}}
 
This type of discrimination can be achieved with circuit-breakers equipped with specially designed electronic trip units (Compact, Masterpact): only the Short Time Protection (STP) and Ground Fault Protection (GFP) functions of the controlled devices are managed by Logic Discrimination. In particular, the Instantaneous Protection function - inherent protection function - is not concerned.<br>'''Settings of controlled circuit-breakers'''
 
*time delay: there are no rules, but staging (if any)of the time delays of time discrimination must be applied (ΔtD1 ≥ ΔtD2 ≥ ΔtD3),
*thresholds: there are no threshold rules to be applied, but natural staging of the protection device ratings must be complied with (IcrD1 ≥ IcrD2 ≥ IcrD3).
 
'''Note:''' This technique ensures discrimination even with circuit-breakers of similar ratings.
 
 
== Principles  ==
 
Activation of the Logic Discrimination function is via transmission of information on the pilot wire:
 
*ZSI input:
 
&nbsp; - low level (no downstream faults): the Protection function is on standby with a reduced time delay (y 0,1 s),<br>&nbsp; - high level (presence of downstream faults): the relevant Protection function moves to the time delay status set on the device.
 
*ZSI output:
 
&nbsp; - low level: the trip unit detects no faults and sends no orders,<br>&nbsp; - high level: the trip unit detects a fault and sends an order.


This type of selectivity can be achieved with circuit breakers equipped with specially designed electronic trip units (Compact, Masterpact): only the Short Time Protection (Isd, Tsd) and Ground Fault Protection (GFP) functions of the controlled devices are managed by Logic Selectivity. In particular, the Instantaneous Protection function is not concerned.


== Operation  ==
One benefit of this solution is to have a short tripping time wherever is located the fault with selectivity category B circuit breaker. Time based selectivity on multi level system implies long tripping time at the origin of the installation.


A pilot wire connects in cascading form the protection devices of an installation (see {{FigRef|H56}}). '''When a fault occurs, each circuit-breaker '''upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuit-breaker to its natural time delay (high level input). The circuitbreaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously.  
=== Settings of controlled circuit breakers ===
* time delay: Staging of the time delays is necessary at least for circuit breaker receiving a ZSI Input (ΔtD1 > trip time with no delay of D2 and ΔtD2 > trip time with no delay of D3)
* thresholds: there are no threshold rules to be applied, but natural staging of the protection device ratings must be complied with (IcrD1 > IcrD2 > IcrD3).


'''Note''': This technique ensures selectivity even with circuit breakers of similar ratings.


[[File:Fig H56.jpg|none]]
=== Principles ===
Activation of the Logic Selectivity function is via transmission of information on the pilot wire:
* ZSI input:
** low level (no downstream faults): the Protection function is on standby with no time delay,
** high level (presence of downstream faults): the relevant Protection function moves to the time delay status set on the device.
* ZSI output:
** low level: the trip unit detects no faults and sends no orders,
** high level: the trip unit detects a fault and sends an order.


'''''Fig. H56:''' Logic discrimination.''
=== Operation ===


A pilot wire connects in cascading form the protection devices of an installation (see {{FigureRef|H55}}). '''When a fault occurs, each circuit breaker''' upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuit breaker to its set time delay (high level input). The circuit breaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously.


{{Highlightbox|
{{FigImage|DB422434_EN|svg|H55|Logic selectivity.}}
'''Discrimination quality'''<br>This technique enables:
*easy achievement as standard of discrimination on 3 levels or more,
*elimination of important stresses on the installation, relating to time-delayed tripping of the protection device, in event of a fault directly on the upstream busbars.


'''All the protection devices are thus virtually instantaneous,'''
{{Related-guides-intro}}
{{RelatedGuide
|image=Hp-highlight-selectivity-guide.png
|title=Selectivity, Cascading and Coordination Guide
|text=Get all required information to verify your electrical distribution design's robustness, considering overloads and short circuits.


*easy achievement of downstream discrimination with non-controlled circuit-breakers.
Combine the benefits of selectivity and cascading to maximize power availability of your LV design at optimized cost.


Find Schneider Electric's coordination data for ACBs, MCCBs, MCBs, switches, busbar trunking (busways), motor starters and more.
|btn-text=Download the guide (.pdf)
|link=https://www.se.com/ww/en/download/document/LVPED318033EN/
}}
}}
[[ru:Согласование характеристик автоматических выключателей]]
[[zh:断路器间的配合]]

Latest revision as of 09:48, 22 June 2022

Cascading (or Back-up protection)

The technique of “cascading” uses the properties of current-limiting circuit-breakers to permit the installation of all downstream switchgear, cables and other circuit components of significantly lower performance than would otherwise be necessary, thereby simplifying and reducing the cost of an installation

Definition of the cascading technique

By limiting the peak value of short-circuit current passing through it, a current-limiting CB permits the use, in all circuits downstream of its location, of switchgear and circuit components having much lower short-circuit breaking capacities, and thermal and electromechanical withstand capabilities than would otherwise be necessary. Reduced physical size and lower performance requirements lead to substantial economy and to the simplification of installation work. It may be noted that, while a current-limiting circuit-breaker has the effect on downstream circuits of (apparently) increasing the source impedance during short-circuit conditions, it has no such effect in any other condition; for example, during the starting of a large motor (where a low source impedance is highly desirable). The range of Compact NSX current-limiting circuit-breakers with powerful limiting performances is particularly interesting.

Conditions of implementation

In general, laboratory tests are necessary to ensure that the conditions of implementation required by national standards are met and compatible switchgear combinations must be provided by the manufacturer

Most national standards admit the cascading technique, on condition that the amount of energy “let through” by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage.

In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, Figure H47 indicates the cascading possibilities of circuit-breaker types iC60, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation.

Fig. H47 – Example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation
Upstream CB NSX250
B F N H S L
Icu (kA) 25 36 50 70 100 150
Downstream CB
Type Rating (A) Icu (kA) Reinforced breaking capacity (kA)
iDPN[a] 1-40 6 10 10 10 10 10 10
iDPN N[a] 1-16 10 20 20 20 20 20 20
25-40 10 16 16 16 16 16 16
iC60N 0,5-40 10 20 25 30 30 30 30
50-63 10 20 25 25 25 25 25
iC60H 0,5-40 15 25 30 30 30 30 30
50-63 15 25 25 25 25 25 25
iC60L 0,5-25 25 25 30 30 30 30 30
32-40 20 25 30 30 30 30 30
50-63 15 25 25 25 25 25 25
C120N 63-125 10 25 25 25 25 25 25
C120H 63-125 15 25 25 25 25 25 25
NG125N 1-125 25 36 36 36 50 70
NG125H 1-125 36 40 50 70 100
NG125L 1-80 50 50 70 100 150
  1. ^ 1 2 230 V phase to neutral

Advantages of cascading

The current limitation benefits all downstream circuits that are controlled by the current-limiting CB concerned.

The principle is not restrictive, i.e. current-limiting CBs can be installed at any point in an installation where the downstream circuits would otherwise be inadequately rated.

The result is:

  • Simplified short-circuit current calculations
  • Simplification, i.e. a wider choice of downstream switchgear and appliances
  • The use of lighter-duty switchgear and appliances, with consequently lower cost
  • Economy of space requirements, since light-duty equipment have generally a smaller volume

Principles of Selectivity

Selectivity is essential to ensure continuity of supply and fast fault localization.

Selectivity is achieved by overcurrent and earth fault protective devices if a fault condition, occurring at any point in the installation, is cleared by the protective device located immediately upstream of the fault, while all other protective devices remain unaffected (see Figure H48).

Fig. H48 – Principle of selectivity

Selectivity is required for installation supplying critical loads where one fault on one circuit shall not cause the interruption of the supply of other circuits. In IEC 60364 series it is mandatory for installation supplying safety services (IEC60364-5-56 2009 560.7.4). Selectivity may also be required by some local regulation or for some special application like :

  • Medical location
  • Marine
  • High-rise building

Selectivity is highly recommended where continuity of supply is critical due to the nature of the loads.

  • Data center
  • Infrastructure (tunnel, airport…)
  • Critical process

From installation point of view: Selectivity is achieved when the maximum short-circuit current at a point of installation is below selectivity limit of the circuit breakers supplying this point of installation.

Selectivity shall be checked for all circuits supplied by one source and for all type of fault:

  • Overload
  • Short-circuit
  • Earth fault

When system can be supplied by different sources (Grid or generator set for instance) selectivity shall be checked in both cases.

Selectivity between two circuit breakers may be

  • Total : up to the breaking capacity of the downstream circuit breaker
  • Partial : up to a specified value according to circuit breakers characteristics Figure H49, H50 and H51

Different solution are provided to achieve selectivity based on:

  • Current
  • Time
  • Energy
  • Logic
Fig. H49 – Total and partial selectivity
Fig. H50 – Total selectivity between CBs A and B
Fig. H51 – Partial selectivity between CBs A and B

Current based selectivity

see (a) of Figure H52

This method is realized by setting successive tripping thresholds at stepped levels, from downstream circuits (lower settings) towards the source (higher settings).

Selectivity is total or partial, depending on particular conditions, as noted above.

Time based selectivity

see (b) of Figure H52

This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source. In the two-level arrangement shown, upstream circuit breaker A is delayed sufficiently to ensure total selectivity with B (for example: Masterpact with electronic trip unit).

Selectivity category B circuit breakers are designed for time based selectivity, the selectivity limit will be the upstream short time withstand value (Icw)

Selectivity based on a combination of the two previous methods

see (c) of Figure H52

A time-delay added to a current level scheme can improve the overall selectivity performance.

The upstream CB has two magnetic tripping thresholds:

  • Im A: delayed magnetic trip or short-delay electronic trip
  • Ii: instantaneous trip

Selectivity is total if Isc B < Ii (instantaneous).

Protection against high level short-circuit currents: Selectivity based on arc-energy levels

Where time versus current curves are superposed selectivity is possible with limiter circuit breaker when they are properly coordinated.

Principle: When a very high level short-circuit current is detected by the two circuit breakers A and B, their contacts open simultaneously. As a result, the current is highly limited.

  • The very high arc-energy at level B induces the tripping of circuit breaker B
  • Then, the arc-energy is limited at level A and is not sufficient to induce the tripping of A
Fig. H53 – Energy based selectivity

This approach requires an accurate coordination of limitation levels and tripping energy levels. It’s implemented inside the Compact NSX range (current limiting circuit breaker), and between compact NSX and acti 9 range. This solution is the only one to achieve selectivity up to high short-circuit current with selectivity category A circuit breaker according to IEC60947-2.

Fig. H54 – Practical example of selectivity at several levels with Schneider Electric circuit breakers(with electronic trip units)

Selectivity enhanced by cascading

Cascading between 2 devices is normally achieved by using the tripping of the upstream circuit breaker A to help the downstream circuit breaker B to break the current. By principle cascading is in contradiction with selectivity. But the energy selectivity technology implemented in Compact NSX circuit-breakers allows to improve the breaking capacity of downstream circuit-breakers and maintain high selectivity performance.

The principle is as follows:

  • The downstream limiting circuit breaker B sees a very high short-circuit current. The tripping is very fast (<1 ms) and then, the current is limited
  • The upstream circuit breaker A sees a limited short-circuit current compared to its breaking capability, but this current induces a repulsion of the contacts. As a result, the arcing voltage increases the current limitation. However, the arc energy is not high enough to induce the tripping of the circuit breaker. So, the circuit breaker A helps the circuit breaker B to trip, without tripping itself. The selectivity limit can

be higher than Icu B and the selectivity becomes total with a reduced cost of the devices

Logic selectivity or “Zone Sequence Interlocking – ZSI”

Selectivity schemes based on logic techniques are possible, using CBs equipped with electronic tripping units designed for the purpose (Compact, Masterpact) and interconnected with pilot wires.

This type of selectivity can be achieved with circuit breakers equipped with specially designed electronic trip units (Compact, Masterpact): only the Short Time Protection (Isd, Tsd) and Ground Fault Protection (GFP) functions of the controlled devices are managed by Logic Selectivity. In particular, the Instantaneous Protection function is not concerned.

One benefit of this solution is to have a short tripping time wherever is located the fault with selectivity category B circuit breaker. Time based selectivity on multi level system implies long tripping time at the origin of the installation.

Settings of controlled circuit breakers

  • time delay: Staging of the time delays is necessary at least for circuit breaker receiving a ZSI Input (ΔtD1 > trip time with no delay of D2 and ΔtD2 > trip time with no delay of D3)
  • thresholds: there are no threshold rules to be applied, but natural staging of the protection device ratings must be complied with (IcrD1 > IcrD2 > IcrD3).

Note: This technique ensures selectivity even with circuit breakers of similar ratings.

Principles

Activation of the Logic Selectivity function is via transmission of information on the pilot wire:

  • ZSI input:
    • low level (no downstream faults): the Protection function is on standby with no time delay,
    • high level (presence of downstream faults): the relevant Protection function moves to the time delay status set on the device.
  • ZSI output:
    • low level: the trip unit detects no faults and sends no orders,
    • high level: the trip unit detects a fault and sends an order.

Operation

A pilot wire connects in cascading form the protection devices of an installation (see Figure H55). When a fault occurs, each circuit breaker upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuit breaker to its set time delay (high level input). The circuit breaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously.

Fig. H55 – Logic selectivity.
Share