To limit the propagation of harmonics in the distribution network, different solutions are available and should be taken into account particularly when designing a new installation.  
To limit the propagation of harmonics in the distribution network, different solutions are available and should be taken into account particularly when designing a new installation.  


== Position the non-linear loads upstream in the system  ==
== Position the non-linear loads upstream in the system  ==


Overall harmonic disturbances increase as the short-circuit power decreases.<br>All economic considerations aside, it is preferable to connect the non-linear loads as far upstream as possible (see'''Fig. M16''').
Overall harmonic disturbances increase as the short-circuit power decreases.
 
----
<br>[[Image:FigM16.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. M16:''' Non-linear loads positioned as far upstream as possible (recommended layout)''


----
All economic considerations aside, it is preferable to connect the non-linear loads as far upstream as possible (see {{FigRef|M24}}).


== Group the non-linear loads''<br>'' ===
{{FigImage|DB422628_EN|svg|M24|Non-linear loads positioned as far upstream as possible (recommended layout)}}


When preparing the single-line diagram, the non-linear devices should be separated from the others (see '''Fig. M17'''). The two groups of devices should be supplied by different sets of busbars.
== Group the non-linear loads ==


----
When preparing the single-line diagram, the non-linear devices should be separated from the others (see {{FigRef|M25}}). The two groups of devices should be supplied by different sets of busbars.
<br>[[Image:FigM17.jpg|left]] <br><br><br><br><br><br><br><br><br><br>
'''''Fig. M17:''' Grouping of non-linear loads and connection as far upstream as possible (recommended layout)''


----
{{FigImage|DB422629_EN|svg|M25|Grouping of non-linear loads and connection as far upstream as possible (recommended layout)}}


== Create separate sources  ==
== Create separate sources  ==


In attempting to limit harmonics, an additional improvement can be obtained by creating a source via a separate transformer as indicated in the Figure M18.<br>The disadvantage is the increase in the cost of the installation.  
In attempting to limit harmonics, an additional improvement can be obtained by creating a source via a separate transformer as indicated in the {{FigureRef|M26}}.


----
The disadvantage is the increase in the cost of the installation.  
<br>[[Image:FigM18.jpg|left]] <br><br><br><br><br><br><br><br><br>'''''Fig. M18:''' Supply of non-linear loads via a separate transformer''


----
{{FigImage|DB422630_EN|svg|M26|Supply of non-linear loads via a separate transformer}}


== Transformers with special connections  ==
== Transformers with special connections  ==
Line 36: Line 28:
Different transformer connections can eliminate certain harmonic orders, as indicated in the examples below:  
Different transformer connections can eliminate certain harmonic orders, as indicated in the examples below:  


*A Dyd connection suppresses 5th and 7th harmonics (see Fig. M19)  
*A Dyd connection suppresses 5th and 7th harmonics (see {{FigRef|M27}})  
*A Dy connection suppresses the 3rd harmonic  
*A Dy connection suppresses the 3rd harmonic  
*A DZ 5 connection suppresses the 5th harmonic
*A DZ 5 connection suppresses the 5th harmonic


----
{{FigImage|DB422631|svg|M27|A Dyd transformer blocks propagation of the 5<sup>th</sup> and 7<sup>th</sup> harmonics to the upstream network}}
<br>[[Image:FigM19.jpg|left]] <br><br><br><br><br>'''''Fig. M19: '''A Dyd transformer blocks propagation of the 5th and 7th harmonics to the upstream network''
 
== Install reactors  ==


----
When variable-speed drives are supplied, it is possible to smooth the current by installing line reactors. By increasing the impedance of the supply circuit, the harmonic current is limited.


== Install reactors ==
Installation of harmonic suppression reactors on capacitor banks increases the impedance of the reactor/capacitor combination for high-order harmonics.


When variable-speed drives are supplied, it is possible to smooth the current by installing line reactors. By increasing the impedance of the supply circuit, the harmonic current is limited.<br>Installation of harmonic suppression reactors on capacitor banks increases the impedance of the reactor/capacitor combination for high-order harmonics.<br>This avoids resonance and protects the capacitors.  
This avoids resonance and protects the capacitors.  


== Select the suitable system earthing arrangement  ==
== Select the suitable system earthing arrangement  ==


'''TNC system'''
===TNC system===
 
In the TNC system, a single conductor (PEN) provides protection in the event of an earth fault and the flow of unbalance currents.
 
Under steady-state conditions, the harmonic currents flow in the PEN. Because of the PEN impedance, this results in slight differences in potential (a few volts) between devices that can cause electronic equipment to malfunction.


In the TNC system, a single conductor (PEN) provides protection in the event of an earth fault and the flow of unbalance currents.<br>Under steady-state conditions, the harmonic currents flow in the PEN. The latter, however, has a certain impedance with as a result slight differences in potential (a few volts) between devices that can cause electronic equipment to malfunction.<br>The TNC system must therefore be reserved for the supply of power circuits at the head of the installation and must not be used to supply sensitive loads.  
The TNC system must therefore be reserved for the supply of power circuits at the head of the installation and must not be used to supply sensitive loads.  


'''TNS system'''
===TNS system===


This system is recommended if harmonics are present.<br>The neutral conductor and the protection conductor PE are completely separate and the potential throughout the distribution network is therefore more uniform.
This system is recommended if harmonics are present.


[[ru:Основные рекомендации по ослаблению гармоник]]
The neutral conductor and the protection conductor PE are completely separate and the potential throughout the distribution network is therefore more uniform.
[[zh:抑制谐波的基本方法]]

Latest revision as of 09:49, 22 June 2022

To limit the propagation of harmonics in the distribution network, different solutions are available and should be taken into account particularly when designing a new installation.

Position the non-linear loads upstream in the system

Overall harmonic disturbances increase as the short-circuit power decreases.

All economic considerations aside, it is preferable to connect the non-linear loads as far upstream as possible (see Fig. M24).

Fig. M24 – Non-linear loads positioned as far upstream as possible (recommended layout)

Group the non-linear loads

When preparing the single-line diagram, the non-linear devices should be separated from the others (see Fig. M25). The two groups of devices should be supplied by different sets of busbars.

Fig. M25 – Grouping of non-linear loads and connection as far upstream as possible (recommended layout)

Create separate sources

In attempting to limit harmonics, an additional improvement can be obtained by creating a source via a separate transformer as indicated in the Figure M26.

The disadvantage is the increase in the cost of the installation.

Fig. M26 – Supply of non-linear loads via a separate transformer

Transformers with special connections

Different transformer connections can eliminate certain harmonic orders, as indicated in the examples below:

  • A Dyd connection suppresses 5th and 7th harmonics (see Fig. M27)
  • A Dy connection suppresses the 3rd harmonic
  • A DZ 5 connection suppresses the 5th harmonic
Fig. M27 – A Dyd transformer blocks propagation of the 5th and 7th harmonics to the upstream network

Install reactors

When variable-speed drives are supplied, it is possible to smooth the current by installing line reactors. By increasing the impedance of the supply circuit, the harmonic current is limited.

Installation of harmonic suppression reactors on capacitor banks increases the impedance of the reactor/capacitor combination for high-order harmonics.

This avoids resonance and protects the capacitors.

Select the suitable system earthing arrangement

TNC system

In the TNC system, a single conductor (PEN) provides protection in the event of an earth fault and the flow of unbalance currents.

Under steady-state conditions, the harmonic currents flow in the PEN. Because of the PEN impedance, this results in slight differences in potential (a few volts) between devices that can cause electronic equipment to malfunction.

The TNC system must therefore be reserved for the supply of power circuits at the head of the installation and must not be used to supply sensitive loads.

TNS system

This system is recommended if harmonics are present.

The neutral conductor and the protection conductor PE are completely separate and the potential throughout the distribution network is therefore more uniform.